4.1.2 

Maximum airflow 

 

Special attention must be given to ensure 
that the temperature rise of the air, 
passing through the enclosure (duct 
channel) around the heat exchanger 
tubes, is high enough to avoid 
condensation forming within the tubes.  
This condensation forming could occur 
by super cooling of the products of 
combustion.  Such condensation can be 
the source of severe corrosion and 
damage to tubes or part of the tubes. 

 

Figure 6 indicates the probability of 
condensation forming within the tubes 
reference : 

the temperature rise of the air 
through the enclosure around the 
tubes (see table 1- fig. 4). 

the inlet air temperature passing over 
the heat exchanger 

 
In function of the expected minimum 
inlet air temperature, the minimum 
required temperature rise (to avoid 
condensation) must be derived from the 
chart shown in figure 6. 

Example 

• 

expected minimum inlet temperature = -5°C 

• 

minimum required temperature rise shown on 
the chart = +13°K 

 
Table 2 indicates the heat output (kW) of the 
different models. 
 
The maximum allowable airflow 

[

through the 

enclosure (duct channel) around the tubes

]

 can 

be calculated as follows : 
 

0,3423

minimum

T

1000

(kW)

input

heat

(m³/h)

max

V

×

×

=

?

 

 

Example : 

<

Tmin = 13K 

model 4072 at 100% heat input : 72,00kW 
results into Vmax = 16180m³/h 
 

Remark

 

For air heaters with the option 2 stage gas valve 
(50% minimum heat input) or the option 
modulating gas valve (30% minimum heat input) 
attention must be given to determine the 
maximum allowable airflow in function of the 
appropriate heat input. 

 

Figure 6 

 

 

Dew-point occurrence chart (condensation zone)

 

¦

¦

¦

Содержание EURO-C 4000 DJL

Страница 1: ...an air handler or as part of an air handling system These appliances meet the following EC Directives Dir CE 90 396 EEC GAD Dir CE 89 336 EEC EMC Dir CE 73 23 EEC LVD Dir CE 89 392 EEC MD annex ll su...

Страница 2: ...18 4024 4030 4047 4060 4072 4100 Are destined to be incorporated in other machines air handlers or to be combined with other machines air handling systems and is not entirely in compliance with the ma...

Страница 3: ...ICAL APPLICATION 11 4 0 LIMITATIONS FOR USE 12 5 0 BURNER CONTROLS SECTION 14 6 0 GAS CONNECTION 15 7 0 ELECTRICAL EQUIPMENT 15 8 0 COMBUSTION CIRCUIT EURO C RJL 16 9 0 COMBUSTION CIRCUIT EURO C DJL 2...

Страница 4: ...that the water vapour in the combustion products condenses out 2 Basic information 2 1 The instructions contained in this document apply to model EURO C 4000 RJL and or EURO C DJL gas fired fan assis...

Страница 5: ...Euro C 4000 JLGBEN 5 31 Figure 1 Dimensions EURO C 4011 15 RJL DJL Fig 1 A Fig 1 B...

Страница 6: ...Euro C 4000 JLGBEN 6 31 Fig 1 C...

Страница 7: ...Euro C 4000 JLGBEN 7 31 Figure 2 Dimensions EURO C 4018 72 RJL DJL Fig 2 A Fig 2 B...

Страница 8: ...Euro C 4000 JLGBEN 8 31 Fig 2 C...

Страница 9: ...Euro C 4000 JLGBEN 9 31 Figure 3 Dimensions EURO C 4100 RJL DJL Fig 3 A Fig 3 B...

Страница 10: ...Euro C 4000 JLGBEN 10 31 Fig 3 C...

Страница 11: ...ion Figure 4 Compartment dimensions key reference Table 1 For horizontal airflow For vertical airflow Table 1 Dimensions of enclosures duct channel for EURO C 4000 heating modules re fig 4 Dimension D...

Страница 12: ...h air heaters The minimum airflow duty through the heating section enclosure see fig 4 table 1 must be observed as indicated in table 2 Table 2 AIRFLOW DUTY MODEL Min air volume required through enclo...

Страница 13: ...ger In function of the expected minimum inlet air temperature the minimum required temperature rise to avoid condensation must be derived from the chart shown in figure 6 Example expected minimum inle...

Страница 14: ...RJL roof top outdoor unit the enclosure into which it is fitted must comply with protection grade IP 45 5 1 3 Access to compartments enclosing the burner and its controls must be provided with panels...

Страница 15: ...out be appropriately qualified persons 6 1 2 Clearances around connections shall be adequate so as to afford access to allow the use of tools to connect and disconnect the gas service connections 6 1...

Страница 16: ...r Consequently included with the heating module are 100 terminal outlet length 300mm PN 60 50712 300 90 elbow with sealing ring dia 100 PN 60 50733 100 Flue outlet combustion air inlet panel assembly...

Страница 17: ...Euro C 4000 JLGBEN 17 31 Figure 7 General arrangement combustion air inlet and flue products outlet Model 4011 72 Model 4100...

Страница 18: ...Euro C 4000 JLGBEN 18 31 Figure 8a models 4011 72 Figure 8b model 4100...

Страница 19: ...Euro C 4000 JLGBEN 19 31 Figure 8c all models Figure 9a models 4011 72...

Страница 20: ...the protection cap std length 300mm is 700mm 8 1 4 Attention must be given to properly seal the mounting flange of the heating module see figure 9 NOTE OTHER FLUE ARRANGEMENTS THAN THOSE DESCRIBED AND...

Страница 21: ...tube sealing ring PN 06 22783 125 2 teflon sealing rings PN 06 22786 084 dia 80 mod 4011 15 PN 06 22786 104 dia 100 mod 4018 24 30 PN 06 22786 134 dia 130 mod 4036 47 60 72 100 As shown in figure 10a...

Страница 22: ...Euro C 4000 JLGBEN 22 31 Figure 10b MODELS 4011 72 MODEL 4100...

Страница 23: ...g is also provided for the appliance for size R The hole size required for this seal ring in the casing is 50 mm diameter All cables and wires passing through the casing of the burner controls section...

Страница 24: ...Euro C 4000 JLGBEN 24 31 Figure 12 Models 4011 72 Model 4100...

Страница 25: ...is added to the application and for airflow conditions as indicated in figure 4 Figure 13 Pressure drop through RJL DJL 4011 15 18 24 30 heating module Figure 14 Pressure drop through RJL DJL 4036 47...

Страница 26: ...em the resulting air flow over the heating section will be equal to the minimal air duty as shown in table 2 In fact the recommended dimensions are maximal allowable dimensions for the by pass This ca...

Страница 27: ...section must be used in figures 13 to 19 to extract the correct pressure drop over the heat exchanger Example Application on Euro C 4011 RJL DJL By Pass 300 mm wide x 310 mm high Total Air Flow 1 m s...

Страница 28: ...by pass 11 2 1 This calculation is applicable for total airflow conditions above V table 7 A The by pass can either be mounted on top of the heat exchanger or besides the heat exchanger as shown in fi...

Страница 29: ...s Vtot Total air flow m s x1 Recommended by pass dim C or D as calculated in section 11 2 x2 Applied by pass dim mm Then VHS air flow through heat exchanger enclosure can be calculated as As explaine...

Страница 30: ...0 66 00 60 00 6 99 5 35 5 23 0 153 4072 87 90 79 15 72 00 8 39 6 42 6 28 0 153 4100 122 00 110 00 98 00 11 64 8 91 8 71 0 153 Notes to table 1 1 GCV Hs 2 NCV Hi 3 Natural gas G20 gross calorific value...

Страница 31: ...ze Burner pressure mbar 1 Model Quantity mm marking Butane Propane 4011 3 1 00 100 27 9 36 9 4015 4 1 00 100 27 8 36 8 4018 5 1 00 100 27 8 36 9 4024 5 1 20 120 28 7 36 5 4030 6 1 20 120 27 5 36 5 403...

Отзывы: