Only the maintenance works at the device listed in this chapter are
permitted.
For further information in the event of repair, please contact the
Bosch Rexroth Service.
Loss of IP degree of protection due to incorrect
maintenance
NOTICE
Ensure that the IP degree of protection remains during maintenance!
Damages to the device due to electrostatic dis-
charges!
NOTICE
Comply with all ESD protective measures while working with modules and com-
ponents! Avoid electrostatic discharges!
Destruction of screw terminals, insufficient con-
tact and loss of UL certification if no copper
wire is used and/or wrong tightening torque
NOTICE
Use only copper wires to wire connection terminals. Tighten the screws of the
screw terminal blocks with a torque of 2.25 lb in (0.22 Nm).
14.2 Tightening torques and stripping length
Torques
Thread
Tightening torque
M2,5
0.4 Nm
M3
0.7 Nm
M4
1.4 Nm
M5
2.8 Nm
Tab. 14-1: Torques for the screws M2,5 ... M5
Stripping length
The stripping length for female connector strips is 10 mm.