IndraControl L40
Installation and Maintenance
8-3
DOK-CONTRL-IC*L40*****-PR03-EN-P
Remove the end clamp (4).
Pull the function module to the left (D) away from the control or the
neighboring module.
Pull down the mounting rail interlock (3) with a screw driver and tilt the
function module forwards (F).
A circulation of the surrounding air has to be ensured.
If there are several rows of function modules, the supply air has to be
measured under each row and its limit value has to be kept.
The following minimum distances have to be realized:
30 mm to the left and right side measured from the outer edge of the
control or the end plate behind the last Rexroth Inline disk.
100 mm upwards and downwards measured from the outer edge of the
control.
At least 30 mm forwards measured from the outer edge of the control.
Additionally, the clearance for mounting, dismounting, connectors and
cable outlets has to be provided.
Attach the end clamps to either side of the Rexroth Inline station. These
end clamps ensure that the station is securely mounted to the top-hat rail
and are also provided as lateral termination elements. These termination
elements are included in the scope of delivery of the IndraControl L40.
Dismounting the IndraControl L40
To dismount the IndraControl L40, first disconnect the additional modules
mounted to the left of the IndraControl L40 from the latter. First remove
the left-hand end clamp (CLIPFIX) and slide the additional modules along
the top-hat rail to the left until you have severed the plug connection of the
PCI
PLUS
bus.
Thereafter, remove the first Rexroth Inline module that is mounted to the
right of the IndraControl L40. Proceed as follows:
•
Remove the labeling field, if present.
Note:
If any of the modules is provided with more connectors than
one, all these connectors must be removed from the module.
•
Pry out the connector of the module to be removed by pressing on the
rear connector shaft latch.
•
Remove the connector(s).
•
Remove the power connector from the IndraControl L40. This ensures
that the feathers of the voltage jumpers and the keyway/feather key
connection are prevented from damage. Moreover, the module can be
accessed more easily.
•
Actuate the release mechanism (1 in Fig. 8-3) and remove the
electronic socket perpendicularly to the top-hat rail (2 in Fig. 8-3).
Removing a Function Module
Minimum Distances
Attaching the End Clamps /
CLIPFIX Clamps
Disconnecting the Additional
Modules from the
IndraControl L40
Removing the First Rexroth
Inline module