3.4.2 Quick Start Parameters
Access & motor nameplate parameters
Code
Name
Setting range
Default
At-
trib.
H39 Rated motor power
0.4...999.9 kW
Depends
on model
●
H40 Rated motor current
0.1...999.9 A
●
Start-up parameters
Code
Name
Setting range
Default
At-
trib.
b00 Set the source of control commands (option
1 and 3 have frequency command source) 0...7
0
●
b02
Set the source of frequency commands
(5 types of sources)
0...12
1
●
b03 Highest frequency – HF
50.00...599.00 Hz
50.00
●
b04 Base frequency – BF
20.00 Hz...HF
50.00
●
b05 Base voltage – BV
400 V class: 240.0...480.0 V
380.0
●
b06 V/f curve mode
OFF; H-00...H-15;
P-00...P-15
Depends
on model
●
b16 Acceleration time
0.1...6,500.0 s
b17 Deceleration time
0.1...6,500.0 s
b32 Starting frequency
0.00...60.00 Hz
0.50
b33 Starting holding time
0.0...10.0 s
0.0
b00 setting range:
0: Run/Stop control with digital operating panel
1: External via control terminals, Up/Down control
2: External via control terminals (including multi-speed), while <Stop> key is ac-
tivated
3: Logic control
4: External via control terminals (X3 is used to switch between internal/external
sources of frequency command, while Stop key is activated)
5: External computer controls Run/Stop, while <Stop> key is activated
6: External computer controls Run/Stop, while <Stop> key is deactivated
7: External via control terminals (X1, X2 and X3 are used to switch between
sources of frequency command, while <Stop> key is activated)
b02 setting range:
Bosch Rexroth AG
Parameter Settings
DOK-RCON01-FE*********-IN04-EN-P
21/31