4  Error Indication

The frequency converter can record the reasons of the last 4 errors and can dis-

play them after resetting from errors.

Error

code

Error name

Possible reason

Solution

O.C.-1

Over cur-

rent at con-

stant speed

Excessively reduced accelera-

tion/ deceleration time

Increase acceleration/ deceleration time

Load short circuit or sudden

changes in load

Check the load

Low grid voltage

Check input power supply

A special motor or a motor larg-

er than the maximum allowable

capacity

Use a frequency converter with suitable

power

O.C.-2

Over cur-

rent during

acceleration

Too short acceleration time

Increase acceleration time

Improper V/f curve

Enable automatic torque increasing or man-

ually adjust V/f curve settings

The frequency converter power

is too low

Select a frequency converter with higher

power

O.C.-3

Over cur-

rent during

decelera-

tion

Too short deceleration time

Increase deceleration time

Large load inertia torque or po-

tential load

Add an appropriate dynamic brake chopper

The frequency converter power

is too low

Select a frequency converter with higher

power

O.E.-1

Over volt-

age at con-

stant speed

Too high input voltage of power

supply

Keep the input voltage of power supply with-

in the specified range

Excessively reduced accelera-

tion/ deceleration time

Increase acceleration/ deceleration time

Abnormality in load

Check the load

O.E.-2

Over volt-

age during
acceleration

Abnormality in input voltage of

power supply

Check input power supply

Abnormality in load

Check the load

O.E.-3

Over volt-

age during
decelera-

tion

Too large moment of inertia of

load

Increase the deceleration time to suit the

load inertia, or purchase a dynamic brake

chopper

Bosch Rexroth AG
Error Indication

 

26/31

DOK-RCON01-FE*********-IN04-EN-P

Содержание Fe Series

Страница 1: ...Rexroth Frequency Converter The Drive Control Company Fe Series Edition 04 Instruction Manual Quick Start R912004884...

Страница 2: ...able in other type or language please consult your lo cal sales partner or check www boschrexroth com fe Copyright Bosch Rexroth Xi an Electric Drives and Controls Co Ltd 2014 This document as well as...

Страница 3: ...4 Dimensions 3 2 Electric Installation 6 2 1 Cable Specifications 6 2 2 Power Terminals 10 2 3 Interface Connection for Signals 12 3 Parameter Settings 17 3 1 Operating Panel 17 3 2 Start up 18 3 3 O...

Страница 4: ...Bosch Rexroth AG II DOK RCON01 FE IN04 EN P...

Страница 5: ...our Bosch Rexroth sales partner 1 2 Ambient Conditions If it is to function perfectly the frequency converter must be installed in an envi ronment matching the data provided below Ambient temperature...

Страница 6: ...wn above is Frame 1 The minimum installation spacing stated applies to Frame 1 to Frame 7 The frequency converter must be vertically installed If one frequency converter is arranged above another make...

Страница 7: ...10 9 FECx02 1 18K5 3 275 200 463 443 218 9 5 16 2 FECx02 1 22K0 16 9 FECx02 1 30K0 4 290 200 574 550 236 11 21 5 FECx02 1 37K0 22 FECx02 1 45K0 5 364 260 602 576 260 11 33 2 FECx02 1 55K0 33 8 FECx02...

Страница 8: ...Fig 1 2 Frame 1 Fig 1 3 Frame 2 3 4 Bosch Rexroth AG Mechanical Installation 4 31 DOK RCON01 FE IN04 EN P...

Страница 9: ...Fig 1 4 Frame 5 6 Fig 1 5 Frame 7 Bosch Rexroth AG Mechanical Installation DOK RCON01 FE IN04 EN P 5 31...

Страница 10: ...2K20 16 1 5 1 5 1 5 1 8 M4 10 1 8 M4 4K00 20 2 5 2 5 2 5 1 8 M4 10 1 8 M4 5K50 25 4 4 2 5 1 8 M4 10 1 8 M4 7K50 25 4 4 2 5 1 8 M4 10 1 8 M4 11K0 32 6 6 4 2 2 8 M5 10 2 2 8 M5 15K0 50 10 10 10 2 2 8 M5...

Страница 11: ...8 1 8 M4 1K50 10 14 1 8 M4 8 1 8 M4 2K20 15 14 1 8 M4 8 1 8 M4 4K00 25 10 1 8 M4 8 1 8 M4 5K50 30 10 1 8 M4 8 1 8 M4 7K50 40 10 1 8 M4 8 1 8 M4 11K0 50 6 2 2 8 M5 8 2 2 8 M5 15K0 60 6 2 2 8 M5 8 2 2...

Страница 12: ...mm2 cable length max 20 m analog inputs 10 V VR1 VR2 I and GND use shielded cables analog inputs I and GND to eliminate interference from external influences connect I and GND on the transducer with a...

Страница 13: ...2 1 3 Overview of Electric Connections Fig 2 1 Block diagram Fe up to 15K0 have internal brake choppers Bosch Rexroth AG Electric Installation DOK RCON01 FE IN04 EN P 9 31...

Страница 14: ...y converters P1 DC positive bus outputs DC negative bus output Grounding Tab 2 3 Power terminals description Depending on size the position and sequence of the power terminals on the in dividual frequ...

Страница 15: ...132K 160K 1 For 11K0 160K the main circuit terminals are on the bottom of the frequency converters 2 For 45K0 160K UL marked connectors and cables should be used for wiring of the terminal blocks The...

Страница 16: ...above are factory defaults 2 3 2 Communication Port Fig 2 10 RS485 communication port Crimp terminal wiring range AWG 22 AWG 12 Crimp terminal wire type 75 and above copper only Crimp terminal torque...

Страница 17: ...SW determines 1 The internal 24 V power supply or an external 24 V power supply 2 The inputs are activated by connection of 24 V to an input PNP active in put or connection of 0 V to an input NPN pass...

Страница 18: ...l circuit terminals description Terminal Signal function Description Signal requirement SF Forward stop See parameters b00 and E38 Opto electronic coupler isolated input 24 VDC for external power supp...

Страница 19: ...ated from COM Tab 2 5 Analog inputs Terminal Signal function Description Signal requirement OUT1 Open collector output 1 Programmable digital output with multiple functions See parameters E16 E17 for...

Страница 20: ...7 Analog outputs Terminal Signal function Description Signal requirement PGP COM Supply voltage nonbreak function Power supply for the encoder Max output current 100 mA A Encoder signal A JP2 positio...

Страница 21: ...settings and state of the frequency converter The keys allow the user to program the frequency convert er Fig 3 1 Fe operating panel For frequency converters of 0K75 7K50 the potentiometer is con fig...

Страница 22: ...whether all the work listed has been performed correctly before beginning the start up Light grey boxes start up described on the following pages Dark grey boxes to prevent damage proceed as is descri...

Страница 23: ...3 3 Operating Descriptions Fig 3 3 Navigation and parameter settings Bosch Rexroth AG Parameter Settings DOK RCON01 FE IN04 EN P 19 31...

Страница 24: ...frequency converter is in run mode Parameter setting cannot be modified directly Tab 3 1 Parameter attributes and descriptions Code means function parameter code written in bxx Exx Pxx and Hxx Value o...

Страница 25: ...1 6 500 0 s b17 Deceleration time 0 1 6 500 0 s b32 Starting frequency 0 00 60 00 Hz 0 50 b33 Starting holding time 0 0 10 0 s 0 0 b00 setting range 0 Run Stop control with digital operating panel 1 E...

Страница 26: ...terminal Kv 10 0 V 7 Direct action of external terminal Ki 4 20 mA 8 Inverse action of external terminal Ki 20 4 mA 9 External terminal Kv 0 5 V Ki 4 20 mA or External terminal Kv 0 10 V Ki 4 20 mA 1...

Страница 27: ...setting 0 50 9 99 1 00 E08 FM channel mode 0 3 0 E09 Pulse output selection 0 3 2 E10 Maximum output pulse frequency 0 1 50 0 kHz 10 0 kHz E11 Frequency level detection FDT1 0 00 599 00 Hz 50 00 Hz E...

Страница 28: ...tion signal 2 FDT2 3 Frequency arrival signal FAR 4 Reserved 5 Under voltage 6 Overload O L 7 Reserved 8 Zero speed lower than starting frequency 9 E Stop 10 Low voltage 11 No trip action 12 Error 13...

Страница 29: ...ration 6 O E 3 over voltage during deceleration 7 O L motor overload 8 O H frequency converter overheat 9 d r drive protection 10 CPU EMI 11 IPH L input phase loss 12 oPH L output phase loss 13 E St s...

Страница 30: ...lect a frequency converter with higher power O C 3 Over cur rent during decelera tion Too short deceleration time Increase deceleration time Large load inertia torque or po tential load Add an appropr...

Страница 31: ...rnal interference Remove nearby interference or other EMI IPH L Phase loss at input side Phase loss of the frequency converter s 3 phase input pow er supply Check 3 phase input power supply or seek te...

Страница 32: ...g at low speed Use a special motor if it is necessary to run at low speed for a long time Too large load Check the load CPUE EMI CPU incorrect operation due to internal interference or damage Remove n...

Страница 33: ...Bosch Rexroth AG DOK RCON01 FE IN04 EN P 29 31...

Страница 34: ...Bosch Rexroth AG 30 31 DOK RCON01 FE IN04 EN P...

Страница 35: ...Notes Bosch Rexroth AG...

Страница 36: ...exroth AG Electric Drives and Controls P O Box 13 57 97803 Lohr Germany Bgm Dr Nebel Str 2 97816 Lohr Germany Tel 49 9352 40 5060 Fax 49 9352 18 4941 service svc boschrexroth de www boschrexroth com D...

Отзывы: