4930
17
2,11
12
4950
21,1
20,1
1,84
10
4971
18,1
23,1
1,57
7
4988
15,1
26,1
1,31
7
5007
12,1
29
1.06
6
HCF IP 54
50/40
0
5
10
15
20
24,2
4930
13,3
0,82
4
4950
15,9
16,4
0,69
4
4971
12,9
19,3
0,56
3
4988
9,91
22,3
0,43
4
5007
6,92
25,2
0,3
2
HCF IP 54
50/30
0
5
10
15
20
18,9
4930
12,7
1,57
7
4950
15,1
15,8
1,31
7
4971
12,1
18,8
1,05
6
4988
9,14
21,7
0,79
4
5007
6,23
24,6
0,54
3
HCF IP 54
40/30
0
5
10
15
20
18,1
6. ASSEMBLY
Water heaters Reventon Group Farmer can be assembled on the wall or ceiling
via rotating mounting bracket. The drawings below show the ways of assembly. In
the bigger accommodation it is recommended to assemble more than one device.
Follow the parameters which are provided on the drawings.
Reventon Group devices can be assembled on the wall or ceiling via rotating
mounting bracket. It is possible to assemble the device in parallel on the angle 60°
and 45°. Please follow the parameters as shown below.
Drawing 1. Assembly on the ceiling.
Drawing 2. Assembly on the wall.
0.15m
Drawing 3. Example arrangement for few devices in the room.
7. INSTALLATION INSTRUCTIONS
The installation should be made by the qualified staff, who possess the needed
rights to install electrical devices, as instructed in the following documentation.
To install the air water heater Reventon Group Farmer use the duct size 2 x 2,5
mm².
8.
All works concerning electrical installation should be made by the qualified stuff,
who possess the qualifications due to the domestic and local norms. These
recommendations include service and disassembly as well. Not following to the
recommendations may cause electrocution, device damages or its incorrect
work.
- Before service or exchange of the device it is obligatory.
- Do not cover the inlet and outlet of the device.
- Do not use the device in room with high moisture or close to the water basin, due
to the 2.1. of this documentation.
- Do not install, service the device with wet hands or barefoot.
- Do not use the device in room with flammable fumes, gas and high
concentration of dust.
- The device should be kept out of reach of children and animals.
- During the assembly use the filter on the hydraulic supply:
ź
vent valve in the highest place on the hydraulic installation,
ź
cut off valve on the supply and return of the device.
- The device should be secured against pressure increase in the water
installation.
- Before plugging the electric supply check the leak tightness.
- The device does not consist of the anti-frost protection. The temperature in the
room should not go below 0°C. In such case please empty the device out of water.
- It is recommended to check the electric installation before the first start.
- It is recommended to use the external current differential protection.
- After the turn off, the elements of device may be warm.
- After operating time of the device, please utilize it concerning the local norms
and regulations.
It is recommended to clean the device periodically:
ź
heating coil: blow through by compressed air,
ź
fan casing and blades: clean form the dirt.
- If the device is not used for a longer time disconnect the voltage supply.
- The device is transported with the closed air stators. It is essential to
open them in 30 % before the first start. Not keeping to the following
recommendation may cause the damages of the fan.
PRECAUTIONS & WARNINGS
- Opening the air stators must be made by two hands in parallel. Not keeping to
the following recommendation may cause the damages of the air stators.
–While plugging the device to the water installation do remember to hold its
stub pipes by pipes spanner, not keeping to the recommendation may cause the
damages of the heating coil.
Parameters
Inlet and outlet water
temperature[°C]
Air flowa [m3/h]
Heating capacity [kW]
Outlet air temperature [°C]
Water flow [m³/h]
Pressure drop in the heat
exchanger [kP]
Inlet air temperature [°C]
Parameters
Inlet and outlet water
temperature[°C]
Air flowa [m3/h]
Heating capacity [kW]
Outlet air temperature [°C]
Water flow [m³/h]
Pressure drop in the heat
exchanger [kP]
Inlet air temperature [°C]
Parameters
Inlet and outlet water
temperature[°C]
Air flowa [m3/h]
Heating capacity [kW]
Outlet air temperature [°C]
Water flow [m³/h]
Pressure drop in the heat
exchanger [kP]
Inlet air temperature [°C]
Содержание Farmer Series