background image

3

Installation and Operation
Blood Bank Refrigerators

4.5

Door Seal

To check the door seal, complete the following steps:

1. Open the door.
2. Insert a strip of paper (a couple of inches wide) between the 

door gasket and the cabinet flange and close the door.

3. Slowly pull the paper strip from the outside. You should feel 

some resistance.

4. Repeat this test at 4-inch intervals around the door. If the 

door does not seal properly, you need to either replace the 
gasket, or adjust the door (see Section 4.4).

CAUTION!

Door seal integrity is critical for blood 

bank refrigerators. A loose fitting gasket allows moist 
air to be drawn into the cabinet, resulting in quicker 
frost buildup on the evaporator coil, longer running 
time, poor temperature maintenance, and increased 
operation cost.

The door seals on 12 ft

3

 models can be adjusted. To correct a 

faulty seal on these units, complete the following steps:

1. Open the door completely.
2. Remove the hinge pin cover to expose the door mounting 

screws. This cover pops off.

3. Loosen the screws and move the door side of the hinge to 

decrease the clearance between the gasket and the cabinet.

4. Tighten the screws and snap the hinge pin covers on.
5. Recheck the seal.
6. If the door does not seal properly, replace the gasket.

4.6

Final Checks

Before start up, complete the following steps:

1. Make sure that the unit is free of all wood or cardboard 

shipping materials, both inside and outside.

2. Check the positions of the stainless steel drawers. If you 

want to adjust the drawer slides in an Upright unit, follow the 
instructions in Section 5.3.

3. Verify that the unit is connected to a dedicated circuit. 

5

Drawers

5.1

Removing the Drawers

To remove the drawers in Upright models (23 ft

3

 and larger) 

complete the following steps (refer to Figure 2):

1. Pull the drawer toward you until the slides are fully extended.
2. Lift the back of the drawer to disengage the mounting tabs 

from the slots on the slides.

Note:

The drawers fit snugly between the slides. Push the back 
of the drawer from underneath to remove the drawer.

3. Raise the back of the drawer almost to a vertical position and 

disengage the front mounting clips from the slides.

To remove the drawers on Space Saver models, depress the 
hooks located on both sides of the drawers (about 1/3 of the way 
back) and slide the drawers up and out.

Figure 2.  Drawer Removal (Upright Models)

5.2

Reinstalling the Drawers

To reinstall the drawers in Upright models, complete the 
following steps (refer to Figure 2):

1. Pull both drawer slides toward you until the slides are fully 

extended.

2. Position the drawer between the slides and insert the front 

mounting clips into the slots on front of the slides.

3. Push the back of the drawer down between the slides and 

insert the drawer tabs into the back slots.

Note:

The drawers fit snugly between the slides. Push on the 
back of the drawer from the inside to insert the drawer 
tabs completely into the slots. Make sure both drawer 
tabs are aligned with the slots on the slides before 
pushing the drawer down between the slides.

5.3

Changing Drawer Slide Position

The drawer slides are adjustable. You can position these slides in 
the vertical slots which are spaced at one-inch intervals.

Drawer slides have a small wire safety clip at the front pilaster 
which prevents the slides from falling when the drawers are 
removed. To change the position of the drawer slides, complete 
the following steps:

1. Locate the safety clip.
2. Slip your fingernail or a small screwdriver under the bottom 

of the wire clip and pry the clip out toward the inside of the 
refrigerator.

3. Lift up the slide at the front. The slide is free to move from 

the front pilaster.

4. The drawer slide must be removed from the rear pilaster at 

approximately a 45 degree angle toward the center of the 
cabinet.

5. Pull the slide toward the front of the cabinet.

CAUTION!

Drawer slides do 

not

 require lubrication. 

Additional lubricant could impede movement of the 
drawers when the lubricant is cold.

Tabs

Drawer slide

Slot

Содержание REB-1204

Страница 1: ...ining this product please be sure to read this manual and product warning labels carefully Failure to follow these instructions may cause this product to malfunction which could result in injury or damage Below are important safety precautions that apply to this product Use this product only in the way described in the product literature and in this manual Before using it verify that this product ...

Страница 2: ...ed power lines Always connect the equipment to a dedicated separate circuit Electrical codes require fuse or circuit breaker protection for branch circuit conductors Use time delay fuses for 12 AWG circuits For all blood bank models the wiring diagram is attached to the back of the cabinet 4 3 Leveling The unit must be level Rotate the leveling screws located under the front corners of the unit un...

Страница 3: ...g tabs from the slots on the slides Note The drawers fit snugly between the slides Push the back of the drawer from underneath to remove the drawer 3 Raise the back of the drawer almost to a vertical position and disengage the front mounting clips from the slides To remove the drawers on Space Saver models depress the hooks located on both sides of the drawers about 1 3 of the way back and slide t...

Страница 4: ...nts are 8ºC and 0ºC Then the number of bars illuminated indicates cabinet temperature as follows bulb only 0ºC cold alarm 6 bars 4 8 1 bar 0 8 7 bars 5 6 2 bars 1 6 8 bars 6 4 3 bars 2 4 9 bars 7 2 4 bars 3 2 10 bars 8 warm alarm 5 bars 4 setpoint When cabinet temperature exceeds the warm alarm setpoint the top bar of the thermometer flashes When temperature is lower than the cold alarm setpoint t...

Страница 5: ...larm test Test by simulating warm alarm conditions Press and simultaneously hold for five seconds Display and thermometer show simulated cabinet temperature alarms flash and sound as appropriate Display blinks twice when test is completed Lower sensor Display lower cabinet temperature Press and simultaneously and hold Display shows lower cabinet temperature while buttons are held returns to upper ...

Страница 6: ...r critical applications such as blood storage be sure that the alarm systems are working and active before you load any product 7 3 Automatic Defrost The defrosting process on all models is primarily accomplished by air circulated during off cycle periods All models are equipped with a built in on demand defrost feature which is preset at the factory The units defrost only under the most severe co...

Страница 7: ...e purple and red white wires must be tied together in this application The wiring diagram is attached to the inside of the alarm back cover 9 4 Alarm Test Note It is important to test your alarm system after any maintenance operation or temperature control adjustment 9 4 1 Theory of Operation This test procedure applies to both factory installed built in alarms and optional field installed remote ...

Страница 8: ... needs to be changed 10 3 Changing Chart Paper To change the chart paper complete the following steps 1 Locate the pressure sensitive buttons at the front upper left of the recorder panel 2 Press and hold the change chart button for one second The pen will move off the scale 3 Unscrew the center nut remove the old chart paper and install new chart paper Carefully align the day and time with the re...

Страница 9: ...Condensers should be cleaned at least every six months In heavy traffic areas condensers load with dirt more quickly Failure to keep the condenser clean can result in equipment warm up or erratic temperatures CAUTION Never clean near condensers with your fingers Some surfaces are sharp Periodically check the condenser to make sure that it is clean In all models the condenser is located in the top ...

Страница 10: ...mperature continues to fluctuate call an authorized Revco service representative Unit warms up Door is open Make sure the door is completely closed Door seal Check the door seal following instructions in Section 4 5 on page 3 Warm product recently loaded in unit Allow ample time to recover from loading warm product Power supply Check for proper voltage to the unit If there is no voltage to the uni...

Страница 11: ...Can dial up to four telephone numbers to advise of alarm condition across any telephone system which accepts pulse dialing One system can monitor up to four individual cabinets In addition the system can monitor up to three groups of cabinets Contact Revco for detailed specifications Customer installed 6224 Description Catalog No Temperature recorder 6 in circular chart seven day drive free standi...

Страница 12: ...months from the date of shipment by Revco If any part is found to contain a manufacturing defect in material or workmanship Revco assumes no responsibility for any labor expenses for service removal or reinstallation required to replace part or for incidental repairs and such costs are the responsibility of the Owner unless a service labor agreement exists between the Owner and his Dealer The warr...

Страница 13: ...plate attached to the equipment If available please provide the date purchased the source of purchase Revco or specific agent rep organization and purchase order number If You Need Assistance REVCO SALES DIVISION Phone 828 658 2711 800 252 7100 FAX 828 645 3368 LABORATORY PARTS and SERVICE Phone 800 438 4851 FAX 828 658 2576 TECHNICAL SUPPORT Phone 800 438 4851 275 Aiken Road Asheville NC 28804 U ...

Отзывы: