Warning
Please Note
The specifications of the product detailed on this
Set-Up Guide may change without notice. RDM
Ltd. shall not be liable for errors or for incidental
or consequential damages, directly and indirectly,
in connection with the furnishing, performance or
misuse of this product or document.
Ensure that all power is
switched off before
installing or maintaining
this product
Mercury 2 & Intuitive Mobile Controller User Guide
www.resourcedm.com
Specification
Warning: Relay 5 output has hazardous voltages (Supply input voltage potential)
This does not apply to the Intuitive Mercury controller
Mercury Mk2 Controller
PR0710-MOB & PR0720-MOB
Intuitive Mercury controller
PR0750-MOB & PR0760-MOB
Power requirements
Supply Voltage Range
100 - 240 Vac ±10%
100 - 240 Vac ±10%
Supply Frequency
50 - 60 Hz
50 - 60 Hz
Maximum supply current
5.2 Amps (when relay 5 is fully loaded)
2 Amps
Typical supply current
<1 Amp
<1 Amp
General
Operating temperature range
+5
0
C to +50
0
C
+5
0
C to +50
0
C
Storage temperature range
-20
0
C to +65
0
C
-20
0
C to +65
0
C
Environmental
Indoor use at altitudes up to 2000m, pollution
degree 1, installation category II. Voltage
fluctuations not to exceed ±10% of nominal
voltage.
Indoor use at altitudes up to 2000m, pollution
degree 1, installation category II. Voltage
fluctuations not to exceed ±10% of nominal
voltage.
Size
78mm (W) x 36mm (H) x 110mm (D)
157mm (W) x 67mm (H) x 120 (D)
Approx Weight
170 grams
500 grams
Safety
EN61010
EN61010
EMC
EN61326; 1997 +Amdt. A1; 1998
EN61326; 1997 +Amdt. A1; 1998
Ventilation
There is no requirement for forced cooling
ventilation
There is no requirement for forced cooling
ventilation
Class 2 Insulation
No
protective Earth is required and
none
should be fitted
No
protective Earth is required and
none
should
be fitted
Supply Fuse
The host equipment must provide a suitable
external over-current protection device such
as: -
Fuse: 6.3A 240 Vac Antisurge (T) HRC
conforming to IEC 60127
Built in fuse holder, fuse 2A 240Vac Antisurge (T)
HRC conforming to IEC60127, 32 x 6.3mm
Or MCB
6A, 240 VAC Type C conforming to BS EN
60898
2A, 240 VAC Type C conforming to BS EN 60898
(Note: controller has integral 2A fuse)
Relay Fuse
Not Fitted
10A 240Vac Antisurge (T) HRC conforming to
IEC60127, 32 x 6.3mm
Relay Specification
Relays 1-4 Mechanical Type (M)
Exclusive common
Max current
6A Resistive (CosØ = 1)
2A Inductive ( CosØ = 0.4)
10A Resistive (CosØ = 1)
3A Inductive ( CosØ = 0.4)
Max voltage
250Vac, 30V dc
250Vac. 30V dc
Relay Fuse
N/A
10A 240Vac Antisurge (T) HRC conforming to
IEC60127, 32 x 6.3mm
Relay 5 Mechanical Type (M)
Common connected to supply
live
Relay 5 Mechanical Type (M)
Exclusive common
Max current
3A (non inductive), COS
=0.4 2A (inductive
load) 200,000 operations
10A Resistive (CosØ = 1)
3A Inductive ( CosØ = 0.4)
Max voltage
250Vac (Internal supply)
250Vac. 30V dc (external supply)
For compliance with the LVD, relays 3, 4 and 5
commons must be at the same potential as the
supply voltage
All relays are independent and can operate at
different potentials to the supply voltage.
!