This function is now complete
Display
From the function menu scroll to and select diSP.
Press enter and one of the following values will be shown: -
0. Controller display will show the whole number and tenths value of a temperature reading. (Default)
1. Controller display will show temperatures as a whole number.
Parameter Tables
Number Parameter
Range
o
C (
o
F )
Step
Units
Default LT
o
C (
o
F )
Default HT
o
C (
o
F )
P-01
Cut-in Temp.
-42 to 30 (-43.6 to 86)
0.1
Deg
-20 (-4)
3.5 (38.3)
P-02
Cut In Differential
0 to 10 (0 to 18)
0.1
Deg
2.5 (4.5)
2.5 (4.5)
P-03
Control Weight
0 to 100
1
%
40
30
P-04
Display Weight
0 to 100
1
%
40
30
P-05
Lag Comp Delay
00:00 to 15:00
00:05
mm:ss
00:40
00:10
P-06
Anti SC Time
00:00 to 15:00
00:05
mm:ss
07:00
07:00
P-07
Lag Cut Out Diff
0 to 10 (0 to 18)
0.1
Deg
2.5 (4.5)
2.5 (4.5)
P-85
Key-switch Mode
0 = Case Off
1 = Fans only
2 = toggle
1
0
0
P-87
Control Probe type
0 = Use Air on Probe
1 = Use Log Probe
1
0
0
P-90
Resistor Case Off
0 (Disabled),1(Enabled)
0
0
P-92
Fans temperature mode
0 = Off
1 = Temperature
2 = Over-temperature
3 = Temp/OT
1
0
0
P-93
Fans Off Temperature
-42 to 30 (-43.6 to 86)
0.1
Deg
-10 (14)
8 (46.4)
P-15
Probe 5 Select
0 = Defrost, 1 = Monitor
1
0
0
P-16
Relay 3 Mode
0 = Lights, 1 = Alarm
1
0
0
P-29
Probe 3 Resistor function
0 = Plant fault,
1 = External defrost
1
0
0
P-18
Service Interval time
0 to 128
1
KHrs
60
60
P-19
Switch Resistors
0 (Off), 1(On)
1
1
P-98
Lights Case Off
0 (Off), 1 (On),
2 (Unused)
0
0
P-99
Load Shedding
0 (Off), 1 (Mode 1),
2 (Mode 2)
1
0
0
P-30
Do (enable) Discharge Stop Compressor A
0 (Off), 1(On)
1
0
0
P-31
Do (enable) Discharge Stop Compressor B
0 (Off), 1(On)
1
0
0
P-32
Discharge Stop Value
-49 to 128
0.1
Deg
55
55
P-33
Discharge Stop Differential
-42 to 30
0.1
Deg
10
10
P-34
Maximum Compressor Run Time
00:00 to 99:00
01:00
mm:ss
00:00
00:00
P-35
Comp Stop Both
0 = Yes
1 = No
1
0
0
P-20
Alarm Delay
00:00 to 99:00
01:00
mm:ss
20:00
20:00
P-21
UT Alarm
-49 to 60 (-56.2 to 140)
0.1
Deg
-30 (-22)
-2 (28.4)
P-22
OT Alarm
-49 to 60 (-56.2 to 140)
0.1
Deg
-15 (5)
5 (41)
P-23
Log Probe Type
0 (Off), 1 (Logging),
2 (Logging/Alarm)
Off
Off
P-24
Slug Log Probe
0 (Off), 1 (On)
Off
Off
P-25
Log Alarm Delay
00:00 to 99:00
01:00
mm:ss
20:00
20:00
P-26
Log UT Alarm
-49 to 60 (-56.2 to 140)
0.1
Deg
-35 (-31)
-1 (30.2)
P-27
Log OT Alarm
-49 to 60 (-56.2 to 140)
0.1
Deg
-12 (10.4)
6 (42.8)
P-28
Monitor OT Alarm
-49 to 60 (-56.2 to 140)
0.1
Deg
20 (68)
20 (68)
P-40
Defrost Mode
0 (Local), 1 (Remote),
2 (External)
Local
Local
P-41
Defrost Start
00:00 to 23:59
00:01
hh:mm
01:00
01:00
P-42
Defrosts per Day
0 to 8
1
6
6
P-43
No Defrost Time
0 to 25
1
hours
12
12
P-44
Def Terminate Temp.
-42 to 30 (-43.6 to 86)
0.1
Deg
14 (57.2)
10 (50)