background image

chimney, in a wall cavity, or if the prevailing 
air draughts carry the smoke or heat away.  
Installing Smoke Alarms on both sides of closed 
doors and installing more than one Alarm as 
recommended in this leaflet very significantly 
improve the probability of early detection.
• The Smoke Alarms may not be heard.
• A Smoke Alarm may not wake a person who 
has taken drugs or alcohol.
• The Alarms may not detect every type of 
fire to give sufficient early warning. They 
are particularly ineffective with: fires caused 
by smoking in bed, escaping gas, violent 
explosions, poor storage of flammable rags 
and/or liquids, (for example petrol, paint, 
spirits etc), overloaded electrical circuits, arson, 
children playing with matches.
• Current studies have shown smoke alarms 
may not awaken all sleeping individuals, and 
that it is the responsibility of individuals in the 
household that are capable of assisting others 
to provide assistance to those who may not 
be awakened by the alarm sound, or to those 
who may be incapable of safely evacuating the 
area unassisted

Limitations of Heat Alarms

There are various situations where a Heat 
Alarm may not be effective:
• Fires where the victim is intimate with a 
flaming initiated fire; for example, when a 
person’s clothes catch fire while cooking.
• Fires where the heat is prevented from 
reaching the Heat Alarm due to a closed door 
or other obstruction.
• Incendiary fires where the fire grows so 
rapidly that an occupant’s egress is blocked 
even with properly located Heat Alarms

5. Getting Your Alarm Serviced

If your Alarm fails to work after you have 
read the sections on “Installation”, “Testing, 
Maintenance and Power Supply Monitoring”, 
then contact Customer Assistance at the nearest 
address given at the end of this leaflet. If it needs 
to be returned for repair or replacement put it 
in a padded box with the battery disconnected. 
Send it to “Customer Assistance” at the nearest 
address given on the Alarm or in this leaflet. State 
the nature of the fault, where the Alarm was 
purchased and the date of purchase.

6. Installation

Installation Procedure

1. Select a location complying with the advice 
in Section 2.
2. Lift off the mounting plate from the Smoke 
Alarm.

3. Place the mounting plate on the ceiling 
exactly where you want to mount the Alarm. 
With a pencil, mark the location of the two 
screw holes.
4. Taking care to avoid any electrical wiring in the 
ceiling, drill holes using a 5.0mm drill bit through 
the centre of the marked locations. Push the 
plastic screw anchors provided into the drilled 
holes. Screw the mounting plate to the ceiling.
5. Insert the battery or batteries as per the 
Quick Start Guide, ensuring the orientation 
is correct. If the battery is already installed in 
your Alarm just pull the battery tab to power 
the Alarm.

Figure 5

ROTATE UNIT ANTI-CLOCKWISE

UNIT WILL NOT TWIST OFF - IT MAY BE

TAMPERPROOFED - SEE FIGURE 8

6. Carefully line up the Alarm on to the 
mounting plate, gentle press home and twist 
clockwise. 
Install all the other Alarms similarly.
7. Press the Test button on each Alarm to ensure 
that the Alarm works (see 

Figure 6

).  

Figure 6

Smoke Alarm

Tamperproofing the Alarm

The Alarm can be made tamperproof to prevent 
unauthorised removal of the Alarm.
Break off the small pillar on the base as shown 
in 

Figure 7a

.  To remove the Alarm from 

the ceiling it is now necessary to use a small 
screwdriver, to release the catch (push catch 
towards the ceiling) and then twist off the 

7

Содержание RE314 DSC

Страница 1: ...mode and then holding down the smoke s test button until the smoke alarm beeps 5 Remove the mounting plate and refer to Sections 2 and 6 for positioning and installation 6 After mounting plate is inst...

Страница 2: ...ED Sounder Low Battery Off 1 Flash every 48 sec 1 Beep Faulty Smoke Sensor Off 2 Flashes every 48 sec 2 Beeps Faulty Heat Sensor Off 2 Flashes every 48 sec 2 Beeps End of Life Off 3 Flashes every 48 s...

Страница 3: ...tors The installation of smoke detectors in kitchens attics finished or unfinished or garages is not normally recommended as these locations occasionally experience conditions that can result in impro...

Страница 4: ...ALARMS 610mm 24 FROM APEX DEAD AIR SPACE Wall Mounting If ceiling mounting is impractical Smoke Alarms may be mounted on a wall provided that a the top of the detection element is between 150mm 6 and...

Страница 5: ...e quickly silenced by fanning vigorously with a newspaper or similar to remove the smoke or press the test hush button Do not attempt to recharge or burn the battery as it may explode If it is necessa...

Страница 6: ...nsurance The supplier or manufacturer is not your insurer Fire Safety Hints Store petrol and other flammable materials in proper containers Discard oily or flammable rags Always use a metal fireplace...

Страница 7: ...ng Maintenance and Power Supply Monitoring then contact Customer Assistance at the nearest address given at the end of this leaflet If it needs to be returned for repair or replacement put it in a pad...

Страница 8: ...l other Alarms in the system WARNING Do not test with flame This can set fire to the Alarm and damage the house We do not recommend testing with smoke as the results can be misleading unless special a...

Страница 9: ...ery 8 seconds to indicate that the unit has been silenced 2 The Smoke Alarm will reset to normal sensitivity at the end of the silenced period 10 minutes If additional silenced time is required simply...

Страница 10: ...sects or cobwebs in the vicinity of the Smoke Alarm should be promptly removed In certain circumstances even with regular cleaning contamination can build up in the smoke sensing chamber causing the A...

Страница 11: ...larm fails to sound when the Test button is pressed Check the age of the unit see the replace by label on side of unit If necessary replace the battery or batteries with Panasonic CR123A 9 System Comp...

Страница 12: ...ice may not cause interference and 2 This device must accept any interference including interference that may cause undesired operation of the device Le pr sent appareil est conforme aux cnr d Industr...

Отзывы: