2.6 Flow set temperature:

The flow set temperature results from the measured 
outdoor temperature and the chosen heating curve. The 
correction value of the remote control as well as the day 
correction or night correction are added to these values. 
The flow set temperature = heating curve tempe  
remote c (day correction or night correction). If 
the calculated flow set temperature is higher than the adju-
sted maximum flow tempe rature, the flow set temperature 
is equated with the maximum flow tempe rature.

2.7 Mixer control:

The mixer control is used for matching the flow tempera-
ture with the flow set temperature. For this purpose the 
mixer is started up/shut down according to the deviation. 
The mixer is activated for the runtime of four seconds 
(factory setting). The break time is calculated from the 
set and actual value. 

2.8 Priority of domestic hot water

This function switches off the heating circuit during domes-
tic hot water after-heating. For this purpose the option 
domestic hot water priority has to be activated and the 
after-heating has to be effected by the boiler charge con-
trol. 

2.9 Blocking protection for heating circuit pumps:

The heating circuit pump is switched on every day at 
12 o’clock for 30 seconds to prevent the pump from getting 
stuck. This function does not work if the flow set value is 
reached, the flow sensor is damaged or the function do-
mestic water priority is activated.

2.10 Anti-freeze function

If the temperature at the flow sensor falls below 8 °C, 
the heating circuit is switched on. If the flow temperature 
 reaches 10 °C, the heating circuit is switched off again. 

2.11 Store after-heating (Differential controller):

In order to start up the after-heating (abbr.: AH) of the 
heating circuit, the difference between the calculated flow 
set temperature and one (AH=thermal) or two store sen-
sors (AH=boiler) is measured. If the difference between 
both temperatures is too low, the after-heating is activated. 
The after heating is switched off if the difference between 

store and flow set temperature is high enough.

Содержание HKM2

Страница 1: ...uit module HKM2 Operation Mounting Electrical Connection 48001390 48001390 manual Thank you for buying this RESOL product Please read this manual carefully to get the best performance from this unit P...

Страница 2: ...omestic water priority 11 3 1 14 Timer 11 3 1 15 HKM expert 12 3 1 16 Manual operation 13 3 1 17 Operating control lamp flashing codes 13 4 Commissioning 13 5 Tips for fault localisation 13 5 1 Troubl...

Страница 3: ...eating circuit module for a weather compensated heating circuit incl outdoor temperature sensor FAP13 and flow temperature sensor FRP21 Can fuse T4A Attachment opening Sensor terminals Net terminals L...

Страница 4: ...outputs Operating control lamp Manual control switch Technical data Housing plastic plug in Protection type IP20 EN 60529 Size 208 x 141 x 65 mm Ambient temperature 0 40 C Inputs 4 sensor inputs Pt100...

Страница 5: ...cables WARNING Switch off power supply before opening the housing 1 1 Wall mounting 1 Installation The HKM2 is designed for wall mounting Please pay at tention to the fact that the back of the wall ho...

Страница 6: ...angeover contact terminals 1 2 The connection of the load must be effected at the terminals 17 to 28 with correct polarity Rx N see terminal scheme fig 2 The protective conductors are to be connected...

Страница 7: ...anging the flow set tempe rature If one of the time frames of the timer is active the night correction is used If none of the time frames is active the flow set value is changed due to the day cor rec...

Страница 8: ...ng circuit during domes tic hot water after heating For this purpose the option domestic hot water priority has to be activated and the after heating has to be effected by the boiler charge con trol 2...

Страница 9: ...ion ofVBus Adjustment channel HKM2 MM Manual Mode State of the relays only if manual control switch is set to I 0 R1 on R3 on 1 R1 on R2 on 2 R1 on PG ProGramme Hardware version Display channel HKM2 V...

Страница 10: ...justment of the value is to be exclusively effected at the external remote control RESOL RTA11 M which has to be activated from the DeltaSol M Version 1 10 on in the heat circuits expert menu The valu...

Страница 11: ...he deviation of the current flow temperature from the flow set temperature The mixer is activated for four seconds in each case factory setting The pause is calcu lated from the deviation from the set...

Страница 12: ...the maximum flow temperature is reached Only the mixer will be shut down In this menu the weather compensated after heating can be activated Select adjustment therm function refers to S1 or boiler fun...

Страница 13: ...nts 1 Power supply If the operating control lamp is off please check the power supply of the controller The HKM2 is protected by a can fuseT4A which is accessible and can be replaced by opening the co...

Страница 14: ...ating heats very slowly Adjusted value for mixer runtime is too low In spite of heating pauses it is constantly too warm Please check the adjusted heating curve decrease it if necessary Flow maximum t...

Страница 15: ...work by cleaning the contact area and by applying heat con ductive paste between sensor and pipe In order to protect the sensor cable against external temperature influences we recommend insulating th...