Switch-on temperature difference
After-heating
(AH=Therm. or AH=Boiler)
If the temperature at the store sensor (S1, AH=Therm.) or
at both store sensors (S1 and S2, AH=Boiler), as the case
may be, underruns the flow set temperature by the value
∆
TAH on
, the after-heating (R5) is switched on.
3.1.15 HKM Expert
(from
DeltaSol
®
M SW-Version 1.10 on)
After-heating
arrangement/heat.circuits/HC Module/
HKM Expert/After-heating
Adjustment range: “None”, “Therm.”, “Boiler”
Factory setting: “None”
Remote Control
arrangement/heat.circuits/HC Module/
HKM Expert/MAN.-CORR.
Adjustment range: “Yes”, “No”
Factory Setting: “No”
If a RTA11-M remote control is connected, it has to be
activated in this menu (Adjustment:
Yes
)
.
Switch-off temperature difference
(AH=Therm. or AH=Boiler)
arrangement/heat.circuits/HC Module/
HKM Expert/
∆
TaH off
Adjustment range: -15 K ... +50 K
Factory setting: +4 K
The after-heating switches off if the temperature at the
store sensor (S1, AH=Therm.) or both store sensors (S1
and S2, AH=Boiler) exceeds the flow set temperature by
the value
∆
TaH off
.
Performance of the heating circuit pump when ex-
ceeding the flow maxiumum temperature
arrangement/heat.circuits/HC Module/HKM Expert/Pump
HKmax
Adjustment range: “On”, “Off”
Factory Setting: “Off”
With the adjustment
OFF,
the heating circuit pump is
switched off if the maximum flow temperature is reached.
With the adjustment
ON,
the heating circuit pump remains
switched on even if the maximum flow temperature is
reached. (Only the mixer will be shut down).
In this menu, the weather-compensated after-heating can
be activated. Select adjustment
therm.
(function refers
to S1) or
boiler
(function refers to S1 and S2). With the
adjustment
NONE
the function will be deactivated.
arrangement/heat.circuits/HC Module/
HKM Expert/
∆
TaH on
Adjustment range: -15 K ... +50 K
Factory setting: 4 K
The timer determines whether day correction or night
correction (set back) is used for changing the set flow tem-
perature. 21 different time frames (3 for each day) can be
set for night correction of the heating circuit.
If one of the time frames is set to ‘active’, night correction
will be active.
If none of them is active, the set flow temperature will be
adapted with day correction. The timers are pre-allocated
such that every day from 10:00 pm to 5:00 am (the following
day) night correction is activated.
The mode determines the operation mode of the timer:
Night/ day
time frame for night correction
off / day
time frame for heating circuit off
without
timer deactivated
3.1.14 Timer:
arrangement/heat.circuits/heating circuit/timer/mode
Selection: “Night / Day”, “Off / Day”, “Without”
Factory setting: “Night / Day”
arrangement/heat.circuits/heating circuit/timer/t1(...21)-
on
Adjustment range: 00: 00 ... 00:00
Factory setting: 22:00 (t1 ... t7-on)
arrangement/heat.circuits/heating circuit/timer/t1(...21)-off
Adjustment range: 00: 00 ... 00:00
Factory setting: 05:00 (t1 ... t7-off)
Example: The night correction runs from Monday to
Tuesday from 22:00 to 6:00 and Tuesday from 15:00 to 18:00,
when t1-on is set to mo,22:00, t1-off to tu,6:00 and t2-on
to tu,15:00 and t2-off to tu,18:00.