Switch-on temperature difference 
After-heating 

(AH=Therm. or AH=Boiler)

If the temperature at the store sensor (S1, AH=Therm.) or 
at both store sensors (S1 and S2, AH=Boiler), as the case 
may be, underruns the flow set temperature by the value 

TAH on

, the after-heating (R5) is switched on.

3.1.15 HKM Expert

(from 

DeltaSol

®

 M SW-Version 1.10 on)

After-heating

arrangement/heat.circuits/HC  Module/  
HKM Expert/After-heating

Adjustment range: “None”, “Therm.”, “Boiler”
Factory setting: “None”

Remote Control

arrangement/heat.circuits/HC Module/ 
HKM Expert/MAN.-CORR.

Adjustment range: “Yes”, “No”
Factory Setting: “No”

If a RTA11-M remote control is connected, it has to be 
activated in this menu (Adjustment: 

Yes

)

.

Switch-off temperature difference  

(AH=Therm. or AH=Boiler)

arrangement/heat.circuits/HC  Module/ 
HKM Expert/

TaH off

Adjustment range: -15 K ... +50 K

Factory setting: +4 K

The after-heating switches off if the temperature at the 
store sensor (S1, AH=Therm.) or both store sensors (S1 
and S2, AH=Boiler) exceeds the flow set temperature by 
the value 

TaH off

.

Performance of the heating circuit pump when ex-

ceeding the flow maxiumum temperature

arrangement/heat.circuits/HC Module/HKM Expert/Pump 
HKmax

Adjustment range: “On”, “Off”
Factory Setting: “Off”

With the adjustment 

OFF, 

the heating circuit pump is 

switched off if the maximum flow temperature is reached. 
With the adjustment 

ON, 

the heating circuit pump remains 

switched on even if the maximum flow temperature is 
reached. (Only the mixer will be shut down).

In this menu, the weather-compensated after-heating can 
be activated. Select adjustment 

therm. 

(function refers 

to S1) or 

boiler

 (function refers to S1 and S2). With the 

adjustment 

NONE 

the function will be deactivated.

arrangement/heat.circuits/HC Module/
HKM Expert/

TaH on

Adjustment range: -15 K ... +50 K
Factory setting: 4 K

The timer determines whether day correction or night 
correction (set back) is used for changing the set flow tem-
perature. 21 different time frames (3 for each day) can be 
set for night correction of the heating circuit. 
If one of the time frames is set to ‘active’, night correction 
will be active. 
If none of them is active, the set flow temperature will be 
adapted with day correction. The timers are pre-allocated 
such that every day from 10:00 pm to 5:00 am (the following 
day) night correction is activated.

The mode determines the operation mode of the timer:

Night/ day

 

time frame for night correction

off / day 

 

time frame for heating circuit off

without

   

timer deactivated

3.1.14 Timer:

arrangement/heat.circuits/heating circuit/timer/mode

Selection: “Night / Day”, “Off / Day”, “Without”

Factory setting: “Night / Day”

arrangement/heat.circuits/heating circuit/timer/t1(...21)-
on 

Adjustment range: 00: 00 ... 00:00   
Factory setting: 22:00 (t1 ... t7-on) 
 

arrangement/heat.circuits/heating circuit/timer/t1(...21)-off

Adjustment range: 00: 00 ... 00:00   
Factory setting: 05:00 (t1 ... t7-off)

Example: The night correction runs from Monday to 
Tuesday from 22:00 to 6:00 and Tuesday from 15:00 to 18:00, 
when t1-on is set to mo,22:00, t1-off to tu,6:00 and t2-on 
to tu,15:00 and t2-off to tu,18:00.

Содержание HKM2

Страница 1: ...uit module HKM2 Operation Mounting Electrical Connection 48001390 48001390 manual Thank you for buying this RESOL product Please read this manual carefully to get the best performance from this unit P...

Страница 2: ...omestic water priority 11 3 1 14 Timer 11 3 1 15 HKM expert 12 3 1 16 Manual operation 13 3 1 17 Operating control lamp flashing codes 13 4 Commissioning 13 5 Tips for fault localisation 13 5 1 Troubl...

Страница 3: ...eating circuit module for a weather compensated heating circuit incl outdoor temperature sensor FAP13 and flow temperature sensor FRP21 Can fuse T4A Attachment opening Sensor terminals Net terminals L...

Страница 4: ...outputs Operating control lamp Manual control switch Technical data Housing plastic plug in Protection type IP20 EN 60529 Size 208 x 141 x 65 mm Ambient temperature 0 40 C Inputs 4 sensor inputs Pt100...

Страница 5: ...cables WARNING Switch off power supply before opening the housing 1 1 Wall mounting 1 Installation The HKM2 is designed for wall mounting Please pay at tention to the fact that the back of the wall ho...

Страница 6: ...angeover contact terminals 1 2 The connection of the load must be effected at the terminals 17 to 28 with correct polarity Rx N see terminal scheme fig 2 The protective conductors are to be connected...

Страница 7: ...anging the flow set tempe rature If one of the time frames of the timer is active the night correction is used If none of the time frames is active the flow set value is changed due to the day cor rec...

Страница 8: ...ng circuit during domes tic hot water after heating For this purpose the option domestic hot water priority has to be activated and the after heating has to be effected by the boiler charge con trol 2...

Страница 9: ...ion ofVBus Adjustment channel HKM2 MM Manual Mode State of the relays only if manual control switch is set to I 0 R1 on R3 on 1 R1 on R2 on 2 R1 on PG ProGramme Hardware version Display channel HKM2 V...

Страница 10: ...justment of the value is to be exclusively effected at the external remote control RESOL RTA11 M which has to be activated from the DeltaSol M Version 1 10 on in the heat circuits expert menu The valu...

Страница 11: ...he deviation of the current flow temperature from the flow set temperature The mixer is activated for four seconds in each case factory setting The pause is calcu lated from the deviation from the set...

Страница 12: ...the maximum flow temperature is reached Only the mixer will be shut down In this menu the weather compensated after heating can be activated Select adjustment therm function refers to S1 or boiler fun...

Страница 13: ...nts 1 Power supply If the operating control lamp is off please check the power supply of the controller The HKM2 is protected by a can fuseT4A which is accessible and can be replaced by opening the co...

Страница 14: ...ating heats very slowly Adjusted value for mixer runtime is too low In spite of heating pauses it is constantly too warm Please check the adjusted heating curve decrease it if necessary Flow maximum t...

Страница 15: ...work by cleaning the contact area and by applying heat con ductive paste between sensor and pipe In order to protect the sensor cable against external temperature influences we recommend insulating th...

Страница 16: ...gen GmbH This especially applies for copies translations microfilms and the storage into electronic systems Editor RESOL Elektronische Regelungen GmbH Important notice We took a lot of care with the t...

Отзывы: