HKM2

| 

6

VBus

®

-connection

not assigned

1
2
3
4
5
6
7
8
9

10

11
12
13

14
15

16

Sensor flow

Outdoor temperature 

sensor

Store sensor 1

Store sensor 2

Remote control  

(optional)

without function

17

18
19

20

21

22
23

24

25
26
27
28
29

30

Medium contact 5 *

Standard relay 3

Standard relay 2

Standard relay 1

Mains connection 

1.3 Terminals

The connection of the remote control can be effected by 
terminals 3 and 4. The connection of the sensors can be 
effected at the terminals 5 to 12 with either polarity (see 
terminal scheme figure 1).
The main controller and the HKM2 module are connected 
via the RESOL VBus

®

 .The connection is effected by ither 

polarity at terminals 13 and 14. The configuration of the mo-
dule is effected at the main controller. Activate HC Module 
within the menu of the main controller. From 

DeltaSol

®

 

M version 1.10 on, you can choose between “No”, “HKM1” 
and “HKM2”, in the previous versions be tween “Yes” and 
“No”. All adjustments and display values are listed in the 
corresponding menu (HC Module). 

fig.1

without function

fig. 2

Changeover contact 

(terminals 1-2)

The connection of the load must be effected at the terminals 
17 to 28 with correct polarity (Rx/N) (see terminal scheme, 
fig. 2). The protective conductors are to be connected to 
the protective conductor common terminal block (fig. 3).

* The HKM comes with an insulated jumper from terminal 
19 to terminal 20. The removal of the jumper results in a 
potential-free changeover relay at the terminals 17, 18 and 
19 (break, work, common center).

The mains connection is to be effected at the terminals:
29 = neutral conductor N 
30 = conductor L 
protective conductor (common terminal block) 
R1 = HL-pump
R2 = Mixer ON
R3 = Mixer OFF
R4 = without function
R5 = After-heating

Take the protective conductor common terminal block 
from the accessory bag. Connect all protective conductors 
in currentless state and insert them into the slots of the 
terminal block (see position fig. 3).

fig. 3

protective conductor - 
common terminal 

In  the  case  of  the  adjustment  AH = Boiler  (from 
 

DeltaSol

®

 M 1.10 on) two store sensors can be used.

In case of the adjustment AH=Therm. or AH=Boiler

Conductor L

1000 

1360 

1000 

1000 

Note:
The terminals (1-8) are factory-installed with 1000 ohms or 
1360 ohms resistors. In case of an appropriate allocation of 
the terminals, please remove the resistors.

Содержание HKM2

Страница 1: ...uit module HKM2 Operation Mounting Electrical Connection 48001390 48001390 manual Thank you for buying this RESOL product Please read this manual carefully to get the best performance from this unit P...

Страница 2: ...omestic water priority 11 3 1 14 Timer 11 3 1 15 HKM expert 12 3 1 16 Manual operation 13 3 1 17 Operating control lamp flashing codes 13 4 Commissioning 13 5 Tips for fault localisation 13 5 1 Troubl...

Страница 3: ...eating circuit module for a weather compensated heating circuit incl outdoor temperature sensor FAP13 and flow temperature sensor FRP21 Can fuse T4A Attachment opening Sensor terminals Net terminals L...

Страница 4: ...outputs Operating control lamp Manual control switch Technical data Housing plastic plug in Protection type IP20 EN 60529 Size 208 x 141 x 65 mm Ambient temperature 0 40 C Inputs 4 sensor inputs Pt100...

Страница 5: ...cables WARNING Switch off power supply before opening the housing 1 1 Wall mounting 1 Installation The HKM2 is designed for wall mounting Please pay at tention to the fact that the back of the wall ho...

Страница 6: ...angeover contact terminals 1 2 The connection of the load must be effected at the terminals 17 to 28 with correct polarity Rx N see terminal scheme fig 2 The protective conductors are to be connected...

Страница 7: ...anging the flow set tempe rature If one of the time frames of the timer is active the night correction is used If none of the time frames is active the flow set value is changed due to the day cor rec...

Страница 8: ...ng circuit during domes tic hot water after heating For this purpose the option domestic hot water priority has to be activated and the after heating has to be effected by the boiler charge con trol 2...

Страница 9: ...ion ofVBus Adjustment channel HKM2 MM Manual Mode State of the relays only if manual control switch is set to I 0 R1 on R3 on 1 R1 on R2 on 2 R1 on PG ProGramme Hardware version Display channel HKM2 V...

Страница 10: ...justment of the value is to be exclusively effected at the external remote control RESOL RTA11 M which has to be activated from the DeltaSol M Version 1 10 on in the heat circuits expert menu The valu...

Страница 11: ...he deviation of the current flow temperature from the flow set temperature The mixer is activated for four seconds in each case factory setting The pause is calcu lated from the deviation from the set...

Страница 12: ...the maximum flow temperature is reached Only the mixer will be shut down In this menu the weather compensated after heating can be activated Select adjustment therm function refers to S1 or boiler fun...

Страница 13: ...nts 1 Power supply If the operating control lamp is off please check the power supply of the controller The HKM2 is protected by a can fuseT4A which is accessible and can be replaced by opening the co...

Страница 14: ...ating heats very slowly Adjusted value for mixer runtime is too low In spite of heating pauses it is constantly too warm Please check the adjusted heating curve decrease it if necessary Flow maximum t...

Страница 15: ...work by cleaning the contact area and by applying heat con ductive paste between sensor and pipe In order to protect the sensor cable against external temperature influences we recommend insulating th...

Страница 16: ...gen GmbH This especially applies for copies translations microfilms and the storage into electronic systems Editor RESOL Elektronische Regelungen GmbH Important notice We took a lot of care with the t...

Отзывы: