Variant pump:
The allocated relay is energised with 100 %, if the collector temperature reaches the
adjusted switch-on temperature.
If the collector temperature falls by 5 K below the adjusted collector overtemper-
ature, the relay will be switched off. In the variant pump, the heat dump function
works independent from solar loading.
Variant valve:
The allocated relay will be energised in parallel to the solar pump, if the collector
temperature reaches the adjusted collector overtemperature. If the collector tem-
perature falls by 5 K below the adjusted collector overtemperature, the relay will
be switched off.
If the store temperature exceeds its maximum temperature by more than 5 K while
the heat dump function is being active, the function will be deactivated. If the tem-
perature falls below this value by the hysteresis maximum store temperature
(HYSP(2) in BEL(2)), the heat dump function is will be available again.
Note
In system 1, the adjustable value OTCL is blocked against the collector
emergency temperature by 10 K. This function will only be available if the
collector cooling function, the heat dump function, and the drainback option
are deactivated.
10
9
a
d
e
f
OTCL
Overtemperature collector
Adjustment range:
40 … 160 °C
Factory setting: 110 °C
OTPUM
Pump or valve logic
Selection: OFF / ON
Factory setting: OFF
SFB 9
PUSH
DTSFO
Switch-on temperature diff.
Adjustment range:
1.0 … 50.0 K
Factory setting: 6.0 K
DTSFF
Switch-on temperature diff.
Adjustment range:
0.5 … 49.5 K
Factory setting: 4.0 K
DTSFS
Set temperature diff.
Adjustment range:
1.5 … 50.0 K
Factory setting: 10.0 K
MNSFO
Minimum limitation
Adjustment range:
0.5 … 89.5 °C
Factory setting: 60.0 °C
MXSFS
Maximum limitation
Adjustment range:
0.5 … 95.0 °C
Factory setting: 60.0 °C
9 Solid fuel boiler
The solid fuel boiler function can be used for transferring heat from a solid fuel
boiler to a store.
The relay (system-dependent) is energised when all switch-on conditions are ful-
filled:
• the temperature difference between the sensors heat source and heat sink has
exceeded the switch-on temperature difference.
• the temperature at the solid fuel boiler sensor has exceeded the minimum tem-
perature
• the temperature at the store sensor has fallen below the maximum temperature
When the Set temperature difference is exceeded, pump speed control starts. For
every increase or decrease by the rise value, the pump speed will be adjusted by 10 %.
The switch-on hysteresis is -5 K.