System 4: Solar system with 1 store and 3-port valve for store loading in layers
The controller compares the temperature at sensor S1 to the temperatures at
sensors S2 and S3. If the measured temperature differences are higher than the
adjusted switch-on temperature differences, the pump (R1) will be activated and the
corresponding store zone will be loaded up to the adjusted store maximum or set
temperature respectively via the valve (R2). The priority logic effects prior loading
of the upper zone of the store.
System 4 system screen
Temperature sensors
S1
Temperature collector
1 / GND
S2
Temperature store
base
2 / GND
S3
Temperature store top 3 / GND
S4
Free
4 / GND
Relay
R1
Solar pump
R1 / N / PE
R2
Valve Solar
R2 / N / PE
R4
Free
R4 / R4
R2
R1
S3
S2
S1
N
N
N
N
10
11
3
3
2
2
2
3
VBus
VBus
V4
0
S4
S3
GND
Sensors
Relais
S2
S1
N
R2
R1
L
R4
R4
R2
R1
L
1
2
3
4
5
6
7
8
9
PWM
A
PWM
B
Mains
Flow direction when
normally open