Installation
Indications,
functions and options
Messages
Commissioning
Operation and function
5/6 Collector minimum temperature
The minimum collector temperature is the minimum switch-on temperature which
must be exceeded for the solar pump (R1 / R2) to switch on. If the collector tem-
perature falls below the adjusted minimum temperature,
❄
is displayed (flashing).
Note
In systems with east- / west collectors, 2 separate menus (COL and COL 2)
will be displayed.
Tube collector function
This function is used for improving the switch-on behaviour in systems with
non-ideal sensor positions (e. g. with some tube collectors).
This function operates within an adjusted time frame. It activates the collector
circuit pump for an adjustable runtime between adjustable pauses in order to com-
pensate for the delayed temperature measurement.
If the runtime is set to more than 10 s, the pump will be run at 100 % for the first
10 s of the runtime. For the remaining runtime, the pump will be run at the adjusted
minimum speed.
If the collector sensor is defective or the collector is blocked, this function is sup-
pressed or switched off.
2-collector systems
In 2-collector systems, the tube collector function is available for each individual
collector field.
In 2-collector systems, the tube collector function will affect the inactive collector
field only. The solar pump of the active collector field will remain switched on until
the switch-off conditions are fulfilled.
Note
If the drainback option is activated, the tube collector function will not
be available.
OTCO (2)
Tube collector function
Selection: OFF / ON
Factory setting: OFF
TCST (2)
Starting time
Adjustment range: 00:00 … 23:00
Factory setting: 07:00
TCRU (2)
Runtime
Adjustment range: 30 … 600 s
in steps of 5 s
Factory setting: 30 s
TCEN (2)
Ending time
Adjustment range: 00:30 … 23:30
in steps of 00:30
Factory setting: 19:00
TCIN (2)
Standstill interval
Adjustment range: 5 … 60 min
in steps of 00:01
Factory setting: 30 min
OTCO
PUSH
CMIN (2)
Collector minimum temp.
Adjustment range: 10 … 90 °C
in steps of 1 °C
Factory setting: 10 °C
OCMI (2)
Collector minimum temp.
Selection: OFF / ON
Factory setting: OFF
OK
OK
OFF
OFF
ON
ON
OCMN
PUSH
c
c
a
a
BACK
PUSH
BACK
PUSH
5/6