CMN / CMN1 / CMN2:
col. minimum temperature 
Adjustment range 50 ... 195°F 
Factory setting 50°F

CMX CMX1 / CMX2:  
collector maximum temperature 
Adjustment range 210 ... 380°F 
Factory setting 250°F

4.1.11 System cooling

If the adjusted maximum tank temperature is reached, the 
solar system switches-off. If now the collector temperatu-
re rises to the adjusted maximum collector temperature 
(CMX CMX1 / CMX2), the solar pump remains activa-
ted until this temperature limitation value is again underrun. 
The tank temperature might continue to rise (subordinated 
active maximum tank temperature), but only up to 400°F 
(emergency shutdown of the tank). If the tank temperature 
is higher than the maximum tank temperature (S MX 
S1MX S2MX) and the collector temperature is by at 
least 10°RA lower than the tank temperature, the solar 
system remains activated until the tank is cooled down again 
by the collector and the tubes below the adjusted maximum 
temperature (S MX S1MX S2MX)(only by activated 
OREC function). 
In case of an activated system 

 is shown on the display 

(blinking). Due to the cooling function, the solar system can 
be kept operable for a longer period on hot summer days 
and a thermal release of the collector and the heat transfer 
medium is ensured as well.

OCX OCX1 / OCX2:  
Option System cooling 
Adjustment range OFF ... ON    
Factory setting OFF

4.1.12 Option collector minimum limitation

OCN OCN1 / OCN2:  
collector minimum limitation 
OFF / ON 
Factory setting OFF

The minimum collector temperature is a minimum switching 
temperature  which  must  be  exceeded  so  that  the  solar 
pump (R1/R2) is switched-on. The minimum temperature 
shall avoid a steady starting-up of the solar pump (or solid 
fuel boiler charging pumps) for low collector temperatures. 
If the minimum temperature is underrun, 

 is shown on 

the display (blinking).

CFR / CFR1 / CFR2
antifreeze temperature 
Adjustment range 15 ... 50°F 
Factory setting 40°F

4.1.13 Option antifreeze

OCF OCF1 / OCF2:  
antifreeze function 
Adjustment range OFF / ON 
Factory setting OFF

4.1.10  Collector temperature limitation 

  Emergency shut down of the collector

If  the  adjusted  collector  limit  temperature  (EM  /  EM1  
EM2) is exceeded the solar pump (R1/R2) is deactivated 
in  order  to  avoid  a  damaging  overheating  of  the  solar 
components (collector emergency shutdown). The factory 
setting for the temperature limitation is 285°F - it can be 
changed within the adjustment range of 230 ... 400°F. Symbol 

 is shown on the display (blinking).

EM EM1 EM2
temperature limitation corector 
Adjustment range 230 ... 400°F 
Factory setting 285°F

The antifreeze function activates the loading circuit between 
collector and tank if the adjusted antifreeze function is un-
derrun in order to protect the medium against freezing or 
„thickening“. If the adjusted frost protection temperature is 
exceeded by 2°F, the loading circuit will be deactivated.
Please note:
As there is only a limited heat quantity of the tank available 
for this function, the antifreeze function should only be used 
in regions with few days of temperatures around freezing 
point.

Содержание DeltaSol BS Pro

Страница 1: ...ww resol de Thanks for buying a RESOL product Read this manual carefully to get the best perfomance from this unit RESOL DeltaSol BS Pro Mounting Connection Handling Fault localization Examples manual 48002700 48002700 ...

Страница 2: ...copying This mounting and operation manual including all parts is copyrighted Another use outside the copyright requires the approval of RESOL Elektronische Regelungen GmbH This especially applies for copies translations micro films and the storage into electronic systems Editor RESOL Elektronische Regelungen GmbH Important notice We took a lot of care over the texts and drawings of this manual an...

Страница 3: ...sys tem visualisation 16 segment display 7 segment display 8 symbols for system status and operating control lamp Operation by 3 pushbuttons in the front of the housing Functions Differential temperature controller with optionally add on system functions Func ti on con trol according to BAW guidelines operating hours counter for solar pump tube collector special function and heat quantity balancin...

Страница 4: ...t the underground 1 Installation Warning Switch off power supply before opening the housing 1 2 Electrical wiring The power supply to the controller must only be made by an external power supply switch last step of installation and the line voltage must be 12 Volt Flexible lines have to be fixed at the housing by enclosed strain relief supports and screws The controller is equipped with 2 standard...

Страница 5: ...d for heat quantity balancing Solar system and heat exchange of existing store with 1 store 4 sensors and 2 pumps R1 Arr 1 Arr 2 S3 store 1 store 2 Symbol Specification S1 collector sensor S2 store sensor lower S3 store sensor at the top S4 store sensor 2 R1 solar pump R2 pump for heat exchange Symbol Specification S1 Collector sensor S2 Store sensor lower S3 Store sensor at the top optionally S4 ...

Страница 6: ... charge in layers with 1 store 3 sensors 1 solar pump and 3 way valve for store charge in layers The sensor S4 TRF can optionally be used for heat quantity balancing S4 TRF Arr 3 Arr 4 Symbol Specification S1 collector sensor S2 store sensor lower S3 store sensor at the top S4 TRF sensor for heat quantity balancing optionally R1 solar pump R2 pump for heat exchange Symbol Specification S1 collecto...

Страница 7: ... be used for heat quantity balancing R2 S4 TRF S1 R1 S2 S3 2 store solar system with pump logic with 2 stores 3 sensors and 2 solar pumps Arr 5 Arr 6 store 1 store 2 Store 1 Store 2 S4 Symbol Specification S1 collector sensor S2 store sensor 1 S3 store sensor 2 S4 TRF sensor for heat quantity balancing optionally R1 solar pump R2 3 way valve Symbol Specification S1 collector sensor S2 store sensor...

Страница 8: ...2 S3 Solar system with after heating by solid fuel boiler with 1 store 4 sensors 1 solar pump and 1 pump for after heating Arr 7 Arr 8 Symbol Specification S1 collector sensor 1 S2 store sensor S3 collector sensor 2 R1 solar pump collector 1 R2 solar pump collector 2 Symbol Specification S1 collector sensor S2 store sensor lower S3 store sensor at the top S4 sensor for solid hot fuel boiler R1 sol...

Страница 9: ... for system 9 Solar system and heating circuit reverse raising with 1 store 4 sensors 1 solar pump and 1 3 way valve for heating circuit reverse raising Arr 9 Symbol Specification S1 collector sensor S2 store sensor lower S3 store sensor at the top S4 heating circuit return R1 solar pump R2 3 way valve ...

Страница 10: ...is used for scrolling forward through the indication menu or to increase the adjustment values The backwards key 2 is accordingly used for the reverse function For adjustment of last indication channel keep button 1 pressed for 3 seconds If an adjustment value is shown on the display SEt is indicated In this case you can press the key Set 3 in order to change into input mode Select a channel by ke...

Страница 11: ...with collector sensor Pump 3 way valves The flow direction or the current bre aking capacity are always shown Heating circuit Store 1 and 2 with heat exchanger After heating with burner symbol Temperature sensor 2 2 3 System screen only system screen Constantly green everything all right Red green blinking initialisation phase manual operation Red blinking sensor defect sensor symbol is quickly bl...

Страница 12: ...ment is saved by pressing button Now the controller is ready for operation and should enable an optimum operation of the solar system by the factory settings made System survey Arr 1 standard solar system Arr 2 solar system with heat exchange Arr 3 solar system with after heating Arr 4 solar system with store charge in layers Arr 5 2 store solar system with valve logic Arr 6 2 store solar system w...

Страница 13: ...emperature tank 1 15 TSTU x x x x Temperature tank 1 below 15 TST1 x x x Temperature tank 1 below 15 TSTO x x x x x Temperature tank 1 at the top 15 TST2 x x x Temperature tank 2 below 15 TFSB x Temperature solid hot fuel boiler 15 TRET x Temperature heating circuit 15 COL2 x Temperature collector 2 15 S3 x Temperature sensor 3 15 TRF Temperature return sensor 15 S4 x x Temperature sensor 4 15 hP ...

Страница 14: ...ion miminum limitation collector 2 18 CMN2 x minium temperature collector 2 18 OCF2 x option antifreeze collector 2 18 CFR2 x antifreeze temperature collector 2 18 PRIO x x x priority 19 tST x x x stop time 19 tRUN x x x Ciruclation time 19 OREC x x x x x x x x x option reccoling 19 O TC x x x x x x x x x option tube collector 19 DT3O x x switch on temperature difference 3 17 DT3F x x switch off t...

Страница 15: ...re tank 1 TST2 temperature tank 2 TST TSTL TSTU TST1 TST2 Tank temperatures Display range 40 480 F 4 1 3 Indication of sensor 3 and sensor 4 Shows the current temperature of the corresponding addi tional sensor without control function S3 temperature sensor 3 S4 temperature sensor 4 Please note S3 and S4 are only shown if the temperature sensors are connected S3 S4 S3 S4 Sensor temperatures Displa...

Страница 16: ...king and the value for heat quantity will be set to 0 In order to finish the RESET procedure the button must be pressed in order to confirm the data In order to interrupt the RESET procedure no button should be pressed for about 5 seconds The controller re turns automatically into the indicaton mode FMAX Volume flow in l min Adjustment range 0 20 in steps of 0 1 Factory setting 6 0 kWh MWh Heat qu...

Страница 17: ...mitation Adjustment range 30 205 F Factory setting MX3O 140 F MX3F 136 F Minimum temperature limitation MN3O MN3F Minimum temperature limitation Adjustment range 30 195 F Factory setting Arr 2 MN3O 40 F MN3F 50F Arr 8 MN3O 140 F MN3F 150 F 4 1 9 T controller solid fuel boiler and heat exchange Please note Switch on temperature difference DO must be at least 2 Ra higher than the switch off tempe ra...

Страница 18: ...CN2 collector minimum limitation OFF ON Factory setting OFF The minimum collector temperature is a minimum switching temperature which must be exceeded so that the solar pump R1 R2 is switched on The minimum temperature shall avoid a steady starting up of the solar pump or solid fuel boiler charging pumps for low collector temperatures If the minimum temperature is underrun is shown on the display...

Страница 19: ...ches on for 30 seconds If the switch on difference between collector and tank is again exceeded during the runtime of the solar pump or the standstill of the system the controller automatically switches over to solar charging If the collector temperature drops by 4 Ra during standstill the switch on value for the special tube collector function will be recalculated OTC Tube collector special funct...

Страница 20: ...r an after heating AH O AH F the thermostat function is used for after heating NH O AH F the thermostat function is used for use of surplus energy On the display is shown if the second relay output is activated 4 1 17Thermostat function Arr 3 after heating use of surpluse energy 4 1 19 Language The menu language can be adjusted in this channel dE German En English It Italiano Fr French LANG Adjust...

Страница 21: ...8 77 1097 194 1347 86 1117 203 1366 95 1136 212 1385 104 1155 221 1404 113 1175 230 1423 122 1194 239 1442 Resistance values of the Pt1000 sensors Check the power supply o k The can fuse of the controller is defective It can be replaced after removal of the front cover spare fuse is enclosed in the accessory bag Sensor defect An error code is shown on the relevant sensor indication channel instead...

Страница 22: ... Replace Decalification no Heat exchanger plugged yes no Cleaning Heat exchanger too small yes New calculation of the dimension no Plausibility control of the option tube collector spe cial function Change Ton and Toff accordingly Switch on temperatu re difference Ton too large no yes Collector sensor un favour able placed e g contact sensor instead of immersion sleeve sensor o k no Pump is overhe...

Страница 23: ...s the pump start up in manual operation yes There is no current check fuses replace them and check power supply The adjusted tempe rature difference for starting the pump is too high choose a matching setting no Is the current of the pump released by the controller yes Is the pump stuck Put the pump into operati on by means of a screwdri ver is it passable now Is the pump out of order replace if n...

Страница 24: ...r e g by lightening Sensors Our product range includes high precision platin temperatu re sensors flatscrew sensors ambient temperature sensors indoor temperature sensors cylindrical clip on sensors and irradiation sensors also to be used as full sensors with sensor pocket Flowmeter If you are interested in realising a heat quantity balancing you need a flowmeter for measuring the volume flow in y...

Отзывы: