SV9440, SV9540, AND SV9640 SMARTVALVE™ SYSTEM CONTROLS

5

69-1227—02

Fig. 2. Firmly fasten flange to valve, but do not 

overtighten screws.

Install Piping to Control

All piping must comply with local codes and ordinances 

or with the National Fuel Gas Code (ANSI Z223.1, NFPA 

No. 54), whichever applies. Tubing installation must 

comply with approved standards and practices.

1.

Use new, properly reamed pipe that is free from 

chips. If tubing is used, make sure the ends are 

square, deburred and clean. All tubing bends must 

be smooth and without deformation.

2.

Run pipe or tubing to the ignition system control. If 

tubing is used, obtain a tube-to-pipe coupling to 

connect the tubing to the ignition system control.

3.

Install a sediment trap in the supply line to the igni-

tion system control. See Fig. 3.

Install Control

1.

Mount 0 to 90 degrees in any direction, including 

vertically, from the upright position of the ignition 

system control switch.

2.

Mount so the gas flow is in the direction of the 

arrow on the bottom of the ignition system control.

3.

Thread the pipe the amount shown in Table 6 for 

insertion into ignition system control or adapters. 

Do not thread pipe too far. Valve distortion or mal-

function can result if the pipe is inserted too 

deeply.

Table 6. NPT Pipe Thread Length (in.).

4.

Apply a moderate amount of good quality pipe 

compound (do not use Teflon tape) only to the pipe, 

leaving two end threads bare. On LP installations, 

use a compound resistant to LP gas. See Fig. 4.

Fig. 3. Sediment trap installation.

Fig. 4. Use moderate amount of pipe compound.

5.

Remove the seals over the ignition system control 

inlet and outlet if necessary.

6.

Connect the pipe to the ignition system control 

inlet and outlet. Use a wrench on the square ends 

of the ignition system control. If a flange is used, 

place the wrench on the flange rather than on the 

ignition system control. Refer to Fig. 5.

Connect Pilot Gas Tubing

1.

Cut tubing to the desired length and bend as nec-

essary for routing to the pilot burner. Do not make 

sharp bends or deform the tubing. Do not bend the 

tubing at the ignition system control after the com-

pression nut is tightened because this can result in 

gas leakage at the connection.

2.

Square off and remove burrs from the end of the 

tubing.

3.

Unscrew the brass compression fitting from the 

pilot outlet (Fig. 6). Slip the fitting over the tubing 

and slide out of the way. See Fig. 7.

4.

Push the tubing into the pilot gas tapping on the 

outlet end of the control until it bottoms. While 

holding the tubing all the way in, slide the fitting 

into place and engage the threads, then turn until 

finger tight. Tighten one more turn with a wrench, 

but do not overtighten.

Pipe Size

Thread Pipe this 

Amount

Maximum Depth Pipe can 

be Inserted into Control

3/8

9/16

3/8

1/2

3/4

1/2

3/4

13/16

3/4

M12168A

VALVE OUTLET

FLANGE

9/64 INCH 

HEX 

SCREWS 

(4) 

1

1 DO NOT USE FLANGES ON 3/4 IN. INLET 

AND 3/4 IN. OUTLET MODELS, AND ON 

THE 3/4 IN. OUTLET SIDE OF 1/2 IN. 

INLET AND 3/4 IN. OUTLET MODELS.

 

HORIZONTAL

DROP

PIPED

GAS

SUPPLY

PIPED

GAS

SUPPLY

3 IN.

(76 MM)

MINIMUM

3 IN.

(76 MM)

MINIMUM

RISER

IGNITION

SYSTEM

CONTROL

TUBING

GAS

SUPPLY

HORIZONTAL

DROP

3 IN.

(76 MM)

MINIMUM

RISER

M3343E

1

IGNITION

SYSTEM

CONTROL

IGNITION

SYSTEM

CONTROL

1

CAUTION

GAS LEAKAGE HAZARD. 

FAILURE TO FOLLOW PRECAUTIONS CAN RESULT IN A GAS-FILLED 

WORK AREA. SHUT OFF THE MAIN GAS SUPPLY BEFORE 

REMOVING END CAP. TEST FOR GAS LEAKAGE WHEN 

INSTALLATION IS COMPLETE.

ALL BENDS IN METALLIC TUBING MUST BE SMOOTH.

TWO 

IMPERFECT 

THREADS

IGNITION 

SYSTEM 

CONTROL

THREAD PIPE THE AMOUNT 

SHOWN IN TABLE FOR INSERTION 

INTO IGNITION SYSTEM CONTROL 

APPLY A MODERATE AMOUNT OF

PIPE COMPOUND ONLY TO PIPE 

(LEAVE TWO END THREADS BARE).

M3344A

PIPE

Содержание SV9440

Страница 1: ... these controls do not provide a postpurge function because power to the control is removed when the thermostat call for heat ends The SV9440 SV9540 and SV9640 Systems are suitable for a wide range of fan assisted combustion gas fired appliances including furnaces rooftop furnaces boilers unit heaters infrared heaters water heaters and commercial cooking appliances The specific application of the ...

Страница 2: ...ble 1 Natural LP Gas Conversion Kits See Table 4 Table 4 Natural LP Gas Conversion Kits Pipe Adapters Angle and straight adapters available for 3 8 1 2 and 3 4 in pipe See Table 5 Flange kits include one flange with attached O ring four mounting screws a 9 64 in hex wrench and instructions Approvals International Approval Services IAS Design Certified C2030025 Table 5 Flange Adapter Part Numbers a...

Страница 3: ...ustrial or agricultural applications protect the control with an enclosure Dust or Grease Accumulation Heavy accumulations of dust or grease can cause the control to malfunction Where dust or grease can be a problem provide covers for the control to limit contamination Heat Excessively high temperatures can damage the control Make sure the maximum ambient temperature at the control does not exceed...

Страница 4: ...he ignition control as follows 1 Remove the pressure regulator cap Fig 1 2 Invert the cap so that the letters appear that repre sent the gas type appropriate for the appliance NAT for natural manufactured gas LP for liquid petroleum gas 3 Replace the cap and tighten firmly Fig 1 Top view of convertible pressure regulator cap Install Adapters To Control If adapters are being installed on the contro...

Страница 5: ... ignition system control If a flange is used place the wrench on the flange rather than on the ignition system control Refer to Fig 5 Connect Pilot Gas Tubing 1 Cut tubing to the desired length and bend as nec essary for routing to the pilot burner Do not make sharp bends or deform the tubing Do not bend the tubing at the ignition system control after the com pression nut is tightened because this...

Страница 6: ...liance manufacturer follow the appliance manufacturer instructions All wiring must comply with applicable electrical codes and ordinances Fig 5 Proper use of wrench on ignition system control with and without flanges Fig 6 Top view of ignition system control APPLY WRENCH FROM TOP OR BOTTOM OF IGNITION SYSTEM CONTROL TO EITHER SHADED AREA WHEN FLANGE IS NOT USED APPLY WRENCH TO FLANGE ONLY WHEN FLA...

Страница 7: ...n system con trol using the keyed connector See Fig 8 through Fig 12 Fig 8 Typical wiring connections in fan assisted warm air furnace with ST9160 Electronic Fan Timer IGNITION SYSTEM CONTROL TIGHTEN NUT ONE TURN BEYOND FINGER TIGHT FITTING BREAKS OFF AND CLINCHES TUBING AS NUT IS TIGHTENED TO PILOT BURNER M3346A C1 P1 C2 C3 40 VA TRANSFORMER CONT EAC HEAT HUM M2 MOTOR PARKING TERMINALS M1 L1 NEUT...

Страница 8: ...AC INSTALLATIONS THERE MUST BE NO MORE THAN 120 V BETWEEN L1 AND APPLIANCE CHASSIS 1 2 1 1 1 1 2 2 2 2 3 3 3 3 4 4 4 4 5 5 6 6 7 8 C1 C2 C3 40 VA TRANSFORMER L1 L2 LOAD COMMON THERMOSTAT M12172D PRESSURE SWITCH NEUTRAL HOT L2 L1 HOT TO 120 240 VAC 60 HZ POWER SUPPLY ROLLOUT SWITCH LIMIT SWITCH INDUCER BLOWER MOTOR R R W 24 VAC Q3450 IGNITER SENSOR AIR DATA SV9440 SV9540 SV9640 POWER SUPPLY PROVIDE...

Страница 9: ...NTROL CENTER Q3450 IGNITER SENSOR SV9440 SV9540 SV9640 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED CONNECT THE 120V HOT LEAD AS SHOWN DATA AND R LINES MUST BE CONNECTED TO AQUASTAT CONTROL FOR PROPER SYSTEM OPERATION IN THIS APPLICATION POSTPURGE FUNCTION IS NOT AVAILABLE AND THE LED FUNCTIONS ONLY DURING A CALL FOR HEAT 1 2 3 4 4 CIRCULATOR R C G Y W 1 3 4 6 L2 L1 HO...

Страница 10: ...Test WARNING Fire or Explosion Hazard Can cause property damage severe injury or death Perform Gas Leak Test every time work is done on a gas system IMPORTANT Do not spray soap and water solution on the SmartValve housing Do not use an excessive amount of soap and water solution to perform the gas leak test These can damage the con trol 1 2 3 4 3 4 2 1 2 6 1 5 4 8 3 7 2 6 9 1 5 4 8 3 7 SMART VALVE...

Страница 11: ...or deduct their consumption from the meter reading Convert flow rate to Btuh as described in form 70 2602 Gas Controls Handbook and compare to Btuh input rating on appliance nameplate 3 IF CHECKING GAS INPUT WITH MANOMETER Make sure the ignition system control is in the OFF position before removing outlet pressure tap plug to connect manometer pressure gauge Also move the ignition system control s...

Страница 12: ...nt adjustment of high and low pressure settings The following sequence details adjusting the high pressure first and then adjusting the low pressure 1 Set thermostat ten degrees above room tempera ture 2 Carefully check the main burner lightoff Make sure that the main burner lights smoothly and that all ports remain lit 3 Check the full rate high manifold pressure listed on the appliance nameplate...

Страница 13: ...e 20 000 times annually should be checked monthly Intermittent use Appliances that are used seasonally should be checked before shutdown and again before the next use Consequence of unexpected shutdown Where the cost of an unexpected shutdown would be high the system should be checked more often Dusty wet or corrosive environments Since these environments can cause the gas control to deteriorate m...

Страница 14: ...AIR PROVING SWITCH PROVED OPEN COMBUSTION AIR BLOWER ON PILOT VALVE OPENS IGNITER POWERED PILOT LIGHTS AND FLAME IS SENSED DURING TRIAL FOR IGNITION CIRCULATING AIR FAN ON AFTER DELAY MAIN VALVE OPENS IGNITER OFF FLAME SENSE LOST THERMOSTAT CALL FOR HEAT ENDS FIVE MINUTE WAIT PERIOD WAIT FOR AIR PROVING SWITCH TO OPEN FLAME SENSE LOST MORE THAN FIVE TIMES IN THIS CALL FOR HEAT OR OTHER ABNORMAL OP...

Страница 15: ...F AFTER POST PURGE CIRCULATING AIR FAN OFF AFTER DELAY WAIT FOR NEXT CALL FOR HEAT THREE SECOND FLAME FAILURE RECYCLE DELAY NO YES YES YES YES NO NO PILOT AND MAIN VALVES CLOSE YES NO YES NO M10964D SV9440 SV9540 SV9640 INTERMITTENT PILOT SmartValve SYSTEM CONTROL SEQUENCE OF OPERATION WITH ST9162A 2 STAGE ELECTRONIC FAN TIMER 2 1 3 3 CIRCULATING AIR FAN OFF AFTER DELAY 1 2 3 IGNITER TURNS OFF ABO...

Страница 16: ...r a call for heat begins Combustion air blower is not energized until airflow proving switch opens 1 Airflow proving switch stuck closed 2 Airflow proving switch miswired or jum pered 3 flashes Airflow proving switch remains open longer than 30 seconds after combustion air blower energized System goes into 5 minute delay period with combustion air blower off At the end of the 5 minute delay anothe...

Страница 17: ... energized The heat speed circulating blower is energized after the heat on fan delay 1 Open manual reset or auto reset burner roll out switch 2 Open high temperature or auxiliary limit switch 3 Limit and rollout switch wiring is in good condition and securely connected 5 flashes Flame signal sensed out of proper sequence Combustion air blower is energized The heat speed circulating blower is ener...

Страница 18: ...in Table 11 Table 11 Troubleshooting without LED indicator assistance for ignition controls using an ST9160 Fan Timer or 208907 Terminal Board If And Check Repair Combustion air blower does not energize 2 flash code does not come on 30 seconds after call for heat starts 1 Combustion air blower wiring 2 Combustion air blower 3 Wiring between ST9160 and SV9540 Combustion air blower does not energize...

Страница 19: ...before thermostat call for heat ends 4 flash code comes on 1 Open manual reset or auto reset burner roll out switch 2 Open high temperature or auxiliary limit switch 3 Limit and rollout switch string wiring is in good condition and securely connected Main burner goes out before thermostat call for heat ends 4 flash code does not come on 1 Intermittent wiring connection between SV9440 SV9540 or SV9...

Страница 20: ...e information below describes a typical igni tion system control application but the specific controls used and the procedures outlined in your appliance manufacturer s instructions can differ requiring special instructions STOP Read the Warnings Above Before Proceeding The pilot flame is lit automatically If the appliance does not turn on when the thermostat is set several degrees above room temp...

Отзывы: