resideo SV9440 Скачать руководство пользователя страница 3

SV9440, SV9540, AND SV9640 SMARTVALVE™ SYSTEM CONTROLS

3

69-1227—02

PLANNING THE INSTALLATION

WARNING

Fire or Explosion Hazard.

Can cause property damage, severe injury, or 

death.

Follow these warnings exactly:

1.

Plan the installation as outlined below.

2.

Plan for frequent maintenance as described in the 

Maintenance section.

Heavy demands are made on the gas controls when 

intermittent pilot systems are used on central heating 

equipment in barns, greenhouses, and commercial 

properties and on heating appliances such as 

commercial cookers, agricultural equipment, industrial 

heating equipment and pool heaters.

Special procedures may be required to prevent nuisance 

shutdowns and control failure due to frequent cycling, 

severe environmental conditions related to moisture, 

corrosive chemicals, dust or excessive heat. These 

applications require Residential Thermal Solutions 

Engineering review; contact your Resideo Sales 

Representative for assistance.

Review the following conditions that can apply to your 

specific installation and follow the precautions 

suggested.

Frequent Cycling

This control is designed for use on appliances that 

typically cycle three to four times an hour only during the 

heating season. In year-around applications with greater 

cycling rates, the control can wear out more quickly. 

Perform a monthly checkout.

Water or Steam Cleaning

If a control gets wet, replace it. If the appliance is likely to 

be cleaned with water or steam, protect (cover) the 

control and wiring from water or steam flow. Mount the 

control high enough above the bottom of the cabinet so it 

does not get wet during normal cleaning procedures.

High Humidity or Dripping Water

Dripping water can cause the control to fail. Never install 

an appliance where water can drip on the control. In 

addition, high ambient humidity can cause the control to 

corrode and fail. If the appliance is in a humid 

atmosphere, make sure air circulation around the control 

is adequate to prevent condensation. Also, regularly 

check out the system.

Corrosive Chemicals

Corrosive chemicals can attack the control, eventually 

causing a failure. If chemicals are used for routine 

cleaning, avoid contact with the control. Where 

chemicals are suspended in air, as in some industrial or 

agricultural applications, protect the control with an 

enclosure.

Dust or Grease Accumulation

Heavy accumulations of dust or grease can cause the 

control to malfunction. Where dust or grease can be a 

problem, provide covers for the control to limit 

contamination.

Heat

Excessively high temperatures can damage the control. 

Make sure the maximum ambient temperature at the 

control does not exceed the rating of the control. If the 

appliance operates at very high temperatures, use 

insulation, shielding, and air circulation, as necessary, to 

protect the control. Proper insulation or shielding should 

be provided by the appliance manufacturer; verify proper 

air circulation is maintained when the appliance is 

installed.

INSTALLATION

When Installing this Product…

1.

Read these instructions carefully. Failure to follow 

them could damage the product or cause a hazard-

ous condition.

2.

Check the ratings given in the instructions and on 

the product to make sure the product is suitable for 

your application.

3.

Installer must be a trained, experienced service 

technician.

4.

After installation is complete, check out product 

operation as provided in these instructions.

WARNING

Fire or Explosion Hazard.

Can cause property damage, severe injury or 

death.

Follow these warnings exactly:

1. Disconnect power supply before wiring to 

prevent electrical shock or equipment damage.

2. To avoid dangerous accumulation of fuel gas, 

turn off the gas supply at the appliance service 

valve before starting installation, and perform 

Gas Leak Test after installation is complete.

3. Do not bend pilot tubing at ignition system 

control or pilot burner after compression fitting 

is tightened, or gas leakage at the connection 

can result.

4. Always install a sediment trap in the gas supply 

line to prevent contamination of the ignition 

system control.

CAUTION

Electrical Shock or Equipment Damage Hazard.

Can shock individuals or short equipment 

circuitry.

1. Disconnect power supply before installation.

2. Never apply a jumper across or short any of the 

terminals in the SV9440, SV9540 or SV9640 

wiring harness. This can damage the system 

transformer or the control.

Follow the appliance manufacturer instructions, if 

available; otherwise, use these instructions as a guide.

IMPORTANT

These ignition system controls are shipped with 

protective seals over the inlet and outlet tap-

pings. Do not remove the seals until ready to 

install adapters or connect the piping.

Содержание SV9440

Страница 1: ... these controls do not provide a postpurge function because power to the control is removed when the thermostat call for heat ends The SV9440 SV9540 and SV9640 Systems are suitable for a wide range of fan assisted combustion gas fired appliances including furnaces rooftop furnaces boilers unit heaters infrared heaters water heaters and commercial cooking appliances The specific application of the ...

Страница 2: ...ble 1 Natural LP Gas Conversion Kits See Table 4 Table 4 Natural LP Gas Conversion Kits Pipe Adapters Angle and straight adapters available for 3 8 1 2 and 3 4 in pipe See Table 5 Flange kits include one flange with attached O ring four mounting screws a 9 64 in hex wrench and instructions Approvals International Approval Services IAS Design Certified C2030025 Table 5 Flange Adapter Part Numbers a...

Страница 3: ...ustrial or agricultural applications protect the control with an enclosure Dust or Grease Accumulation Heavy accumulations of dust or grease can cause the control to malfunction Where dust or grease can be a problem provide covers for the control to limit contamination Heat Excessively high temperatures can damage the control Make sure the maximum ambient temperature at the control does not exceed...

Страница 4: ...he ignition control as follows 1 Remove the pressure regulator cap Fig 1 2 Invert the cap so that the letters appear that repre sent the gas type appropriate for the appliance NAT for natural manufactured gas LP for liquid petroleum gas 3 Replace the cap and tighten firmly Fig 1 Top view of convertible pressure regulator cap Install Adapters To Control If adapters are being installed on the contro...

Страница 5: ... ignition system control If a flange is used place the wrench on the flange rather than on the ignition system control Refer to Fig 5 Connect Pilot Gas Tubing 1 Cut tubing to the desired length and bend as nec essary for routing to the pilot burner Do not make sharp bends or deform the tubing Do not bend the tubing at the ignition system control after the com pression nut is tightened because this...

Страница 6: ...liance manufacturer follow the appliance manufacturer instructions All wiring must comply with applicable electrical codes and ordinances Fig 5 Proper use of wrench on ignition system control with and without flanges Fig 6 Top view of ignition system control APPLY WRENCH FROM TOP OR BOTTOM OF IGNITION SYSTEM CONTROL TO EITHER SHADED AREA WHEN FLANGE IS NOT USED APPLY WRENCH TO FLANGE ONLY WHEN FLA...

Страница 7: ...n system con trol using the keyed connector See Fig 8 through Fig 12 Fig 8 Typical wiring connections in fan assisted warm air furnace with ST9160 Electronic Fan Timer IGNITION SYSTEM CONTROL TIGHTEN NUT ONE TURN BEYOND FINGER TIGHT FITTING BREAKS OFF AND CLINCHES TUBING AS NUT IS TIGHTENED TO PILOT BURNER M3346A C1 P1 C2 C3 40 VA TRANSFORMER CONT EAC HEAT HUM M2 MOTOR PARKING TERMINALS M1 L1 NEUT...

Страница 8: ...AC INSTALLATIONS THERE MUST BE NO MORE THAN 120 V BETWEEN L1 AND APPLIANCE CHASSIS 1 2 1 1 1 1 2 2 2 2 3 3 3 3 4 4 4 4 5 5 6 6 7 8 C1 C2 C3 40 VA TRANSFORMER L1 L2 LOAD COMMON THERMOSTAT M12172D PRESSURE SWITCH NEUTRAL HOT L2 L1 HOT TO 120 240 VAC 60 HZ POWER SUPPLY ROLLOUT SWITCH LIMIT SWITCH INDUCER BLOWER MOTOR R R W 24 VAC Q3450 IGNITER SENSOR AIR DATA SV9440 SV9540 SV9640 POWER SUPPLY PROVIDE...

Страница 9: ...NTROL CENTER Q3450 IGNITER SENSOR SV9440 SV9540 SV9640 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED CONNECT THE 120V HOT LEAD AS SHOWN DATA AND R LINES MUST BE CONNECTED TO AQUASTAT CONTROL FOR PROPER SYSTEM OPERATION IN THIS APPLICATION POSTPURGE FUNCTION IS NOT AVAILABLE AND THE LED FUNCTIONS ONLY DURING A CALL FOR HEAT 1 2 3 4 4 CIRCULATOR R C G Y W 1 3 4 6 L2 L1 HO...

Страница 10: ...Test WARNING Fire or Explosion Hazard Can cause property damage severe injury or death Perform Gas Leak Test every time work is done on a gas system IMPORTANT Do not spray soap and water solution on the SmartValve housing Do not use an excessive amount of soap and water solution to perform the gas leak test These can damage the con trol 1 2 3 4 3 4 2 1 2 6 1 5 4 8 3 7 2 6 9 1 5 4 8 3 7 SMART VALVE...

Страница 11: ...or deduct their consumption from the meter reading Convert flow rate to Btuh as described in form 70 2602 Gas Controls Handbook and compare to Btuh input rating on appliance nameplate 3 IF CHECKING GAS INPUT WITH MANOMETER Make sure the ignition system control is in the OFF position before removing outlet pressure tap plug to connect manometer pressure gauge Also move the ignition system control s...

Страница 12: ...nt adjustment of high and low pressure settings The following sequence details adjusting the high pressure first and then adjusting the low pressure 1 Set thermostat ten degrees above room tempera ture 2 Carefully check the main burner lightoff Make sure that the main burner lights smoothly and that all ports remain lit 3 Check the full rate high manifold pressure listed on the appliance nameplate...

Страница 13: ...e 20 000 times annually should be checked monthly Intermittent use Appliances that are used seasonally should be checked before shutdown and again before the next use Consequence of unexpected shutdown Where the cost of an unexpected shutdown would be high the system should be checked more often Dusty wet or corrosive environments Since these environments can cause the gas control to deteriorate m...

Страница 14: ...AIR PROVING SWITCH PROVED OPEN COMBUSTION AIR BLOWER ON PILOT VALVE OPENS IGNITER POWERED PILOT LIGHTS AND FLAME IS SENSED DURING TRIAL FOR IGNITION CIRCULATING AIR FAN ON AFTER DELAY MAIN VALVE OPENS IGNITER OFF FLAME SENSE LOST THERMOSTAT CALL FOR HEAT ENDS FIVE MINUTE WAIT PERIOD WAIT FOR AIR PROVING SWITCH TO OPEN FLAME SENSE LOST MORE THAN FIVE TIMES IN THIS CALL FOR HEAT OR OTHER ABNORMAL OP...

Страница 15: ...F AFTER POST PURGE CIRCULATING AIR FAN OFF AFTER DELAY WAIT FOR NEXT CALL FOR HEAT THREE SECOND FLAME FAILURE RECYCLE DELAY NO YES YES YES YES NO NO PILOT AND MAIN VALVES CLOSE YES NO YES NO M10964D SV9440 SV9540 SV9640 INTERMITTENT PILOT SmartValve SYSTEM CONTROL SEQUENCE OF OPERATION WITH ST9162A 2 STAGE ELECTRONIC FAN TIMER 2 1 3 3 CIRCULATING AIR FAN OFF AFTER DELAY 1 2 3 IGNITER TURNS OFF ABO...

Страница 16: ...r a call for heat begins Combustion air blower is not energized until airflow proving switch opens 1 Airflow proving switch stuck closed 2 Airflow proving switch miswired or jum pered 3 flashes Airflow proving switch remains open longer than 30 seconds after combustion air blower energized System goes into 5 minute delay period with combustion air blower off At the end of the 5 minute delay anothe...

Страница 17: ... energized The heat speed circulating blower is energized after the heat on fan delay 1 Open manual reset or auto reset burner roll out switch 2 Open high temperature or auxiliary limit switch 3 Limit and rollout switch wiring is in good condition and securely connected 5 flashes Flame signal sensed out of proper sequence Combustion air blower is energized The heat speed circulating blower is ener...

Страница 18: ...in Table 11 Table 11 Troubleshooting without LED indicator assistance for ignition controls using an ST9160 Fan Timer or 208907 Terminal Board If And Check Repair Combustion air blower does not energize 2 flash code does not come on 30 seconds after call for heat starts 1 Combustion air blower wiring 2 Combustion air blower 3 Wiring between ST9160 and SV9540 Combustion air blower does not energize...

Страница 19: ...before thermostat call for heat ends 4 flash code comes on 1 Open manual reset or auto reset burner roll out switch 2 Open high temperature or auxiliary limit switch 3 Limit and rollout switch string wiring is in good condition and securely connected Main burner goes out before thermostat call for heat ends 4 flash code does not come on 1 Intermittent wiring connection between SV9440 SV9540 or SV9...

Страница 20: ...e information below describes a typical igni tion system control application but the specific controls used and the procedures outlined in your appliance manufacturer s instructions can differ requiring special instructions STOP Read the Warnings Above Before Proceeding The pilot flame is lit automatically If the appliance does not turn on when the thermostat is set several degrees above room temp...

Отзывы: