resideo SV9440 Скачать руководство пользователя страница 12

SV9440, SV9540, AND SV9640 SMARTVALVE™ SYSTEM CONTROLS

69-1227—02

12

NOTE:

If the burner firing rate is above 150,000 Btuh on 

SV9540 models (see Table 1 for SV9640 capaci-

ties), it may not be possible to deliver the 

desired outlet pressure. This is an application 

issue, not a control failure. Take whatever steps 

are required to correct the situation.

Step-Opening (P) Models

Step-opening models require that you check and adjust 

the full-rate pressure first and then check the step 

pressure. The step pressure is not field adjustable.

1.

Carefully check the main burner lightoff. Make sure 

that the main burner lights smoothly and that all 

ports remain lit.

2.

Check the full rate manifold pressure listed on the 

appliance nameplate. Ignition system control full 

rate outlet pressure should match this rating.

3.

With main burner operating, check the ignition sys-

tem control flow rate using the meter clocking 

method or check pressure using a manometer con-

nected to the outlet pressure tap on the ignition 

system control. See Fig. 6.

4.

If necessary, adjust the pressure regulator to 

match the appliance rating. See Table 7 and 

Table 8 for factory-set nominal outlet pressure and 

adjustment range.

a. Remove the pressure regulator adjustment cap 

screw.

b. Using a screwdriver, turn the inner adjustment 

screw (Fig. 6) clockwise 

 to increase or 

counterclockwise 

 to decrease the gas 

pressure to the burner.

c. Always replace the cap screw and tighten 

firmly to prevent gas leakage.

5.

If the desired outlet pressure or flow rate cannot be 

achieved by adjusting the ignition system control, 

check the ignition system control inlet pressure 

using a manometer at the inlet pressure tap of the 

ignition system control. If the inlet pressure is in 

the nominal range (see Table 7 and Table 8), 

replace the ignition system control. Otherwise, take 

the necessary steps to provide proper gas pressure 

to the control.

6.

Carefully check the burner lightoff at step pressure. 

Make sure the burner lights smoothly and without 

flashback to the orifice. Make sure all ports remain 

lit. Cycle the burner several times, allowing at least 

60 seconds between cycles for the regulator to 

resume the step function. Repeat after allowing the 

burner to cool. Readjust the full rate outlet pres-

sure, if necessary, to improve lightoff characteris-

tics.

Two-Stage (Q) Models

Two-stage models allow independent adjustment of high 

and low pressure settings. The following sequence 

details adjusting the high pressure first and then 

adjusting the low pressure.

1.

Set thermostat ten degrees above room tempera-

ture.

2.

Carefully check the main burner lightoff. Make sure 

that the main burner lights smoothly and that all 

ports remain lit.

3.

Check the full rate (high) manifold pressure listed 

on the appliance nameplate for high pressure. The 

Ignition system control full rate outlet pressure 

should match this rating.

4.

With main burner operating, check the ignition sys-

tem control flow rate using the meter clocking 

method or check pressure using a manometer con-

nected to the outlet pressure tap on the ignition 

system control. See Fig. 6.

5.

If necessary, adjust the high pressure regulator to 

match the appliance rating. See Table 7 an

Table 8 for factory-set nominal outlet pressure and 

adjustment range.

a. Remove the pressure regulator adjustment cap 

(Fig. 6).

b. Using a screwdriver, turn the inner adjustment 

screw for HI pressure clockwise 

 to increase 

or counterclockwise 

 to decrease the gas 

pressure to the burner.

6.

After high pressure is checked, check low pressure 

regulation by removing the wire from terminal W2 

of the ST9162 fan timer (to prevent ignition control 

from moving to high stage).

7.

Check the low rate manifold pressure listed on the 

appliance nameplate. Ignition system control low 

rate outlet pressure should match this rating.

8.

With main burner operating, check the ignition sys-

tem control flow rate as before (using the meter 

clocking method or check pressure using a 

manometer connected to the outlet pressure tap 

on the ignition system control).

9.

If necessary, adjust the low pressure regulator to 

match the appliance rating. See Table 7 an

Table 8 for factory-set nominal outlet pressure and 

adjustment range.

a. Remove the pressure regulator adjustment cap 

(Fig. 6).

b. Using a screwdriver, turn the inner adjustment 

screw for LO pressure clockwise 

 to 

increase or counterclockwise 

 to decrease 

the gas pressure to the burner.

10.

Once high and low pressure are checked and 

adjusted, replace pressure regulator adjustment 

cap. If the desired outlet pressure or flow rate can-

not be achieved by adjusting the ignition system 

control, check the ignition system control inlet 

pressure using a manometer at the inlet pressure 

tap of the ignition system control. If the inlet pres-

sure is in the nominal range (see Table 7 and 

Table 8), replace the ignition system control. Other-

wise, take the necessary steps to provide proper 

gas pressure to the control.

Содержание SV9440

Страница 1: ... these controls do not provide a postpurge function because power to the control is removed when the thermostat call for heat ends The SV9440 SV9540 and SV9640 Systems are suitable for a wide range of fan assisted combustion gas fired appliances including furnaces rooftop furnaces boilers unit heaters infrared heaters water heaters and commercial cooking appliances The specific application of the ...

Страница 2: ...ble 1 Natural LP Gas Conversion Kits See Table 4 Table 4 Natural LP Gas Conversion Kits Pipe Adapters Angle and straight adapters available for 3 8 1 2 and 3 4 in pipe See Table 5 Flange kits include one flange with attached O ring four mounting screws a 9 64 in hex wrench and instructions Approvals International Approval Services IAS Design Certified C2030025 Table 5 Flange Adapter Part Numbers a...

Страница 3: ...ustrial or agricultural applications protect the control with an enclosure Dust or Grease Accumulation Heavy accumulations of dust or grease can cause the control to malfunction Where dust or grease can be a problem provide covers for the control to limit contamination Heat Excessively high temperatures can damage the control Make sure the maximum ambient temperature at the control does not exceed...

Страница 4: ...he ignition control as follows 1 Remove the pressure regulator cap Fig 1 2 Invert the cap so that the letters appear that repre sent the gas type appropriate for the appliance NAT for natural manufactured gas LP for liquid petroleum gas 3 Replace the cap and tighten firmly Fig 1 Top view of convertible pressure regulator cap Install Adapters To Control If adapters are being installed on the contro...

Страница 5: ... ignition system control If a flange is used place the wrench on the flange rather than on the ignition system control Refer to Fig 5 Connect Pilot Gas Tubing 1 Cut tubing to the desired length and bend as nec essary for routing to the pilot burner Do not make sharp bends or deform the tubing Do not bend the tubing at the ignition system control after the com pression nut is tightened because this...

Страница 6: ...liance manufacturer follow the appliance manufacturer instructions All wiring must comply with applicable electrical codes and ordinances Fig 5 Proper use of wrench on ignition system control with and without flanges Fig 6 Top view of ignition system control APPLY WRENCH FROM TOP OR BOTTOM OF IGNITION SYSTEM CONTROL TO EITHER SHADED AREA WHEN FLANGE IS NOT USED APPLY WRENCH TO FLANGE ONLY WHEN FLA...

Страница 7: ...n system con trol using the keyed connector See Fig 8 through Fig 12 Fig 8 Typical wiring connections in fan assisted warm air furnace with ST9160 Electronic Fan Timer IGNITION SYSTEM CONTROL TIGHTEN NUT ONE TURN BEYOND FINGER TIGHT FITTING BREAKS OFF AND CLINCHES TUBING AS NUT IS TIGHTENED TO PILOT BURNER M3346A C1 P1 C2 C3 40 VA TRANSFORMER CONT EAC HEAT HUM M2 MOTOR PARKING TERMINALS M1 L1 NEUT...

Страница 8: ...AC INSTALLATIONS THERE MUST BE NO MORE THAN 120 V BETWEEN L1 AND APPLIANCE CHASSIS 1 2 1 1 1 1 2 2 2 2 3 3 3 3 4 4 4 4 5 5 6 6 7 8 C1 C2 C3 40 VA TRANSFORMER L1 L2 LOAD COMMON THERMOSTAT M12172D PRESSURE SWITCH NEUTRAL HOT L2 L1 HOT TO 120 240 VAC 60 HZ POWER SUPPLY ROLLOUT SWITCH LIMIT SWITCH INDUCER BLOWER MOTOR R R W 24 VAC Q3450 IGNITER SENSOR AIR DATA SV9440 SV9540 SV9640 POWER SUPPLY PROVIDE...

Страница 9: ...NTROL CENTER Q3450 IGNITER SENSOR SV9440 SV9540 SV9640 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED CONNECT THE 120V HOT LEAD AS SHOWN DATA AND R LINES MUST BE CONNECTED TO AQUASTAT CONTROL FOR PROPER SYSTEM OPERATION IN THIS APPLICATION POSTPURGE FUNCTION IS NOT AVAILABLE AND THE LED FUNCTIONS ONLY DURING A CALL FOR HEAT 1 2 3 4 4 CIRCULATOR R C G Y W 1 3 4 6 L2 L1 HO...

Страница 10: ...Test WARNING Fire or Explosion Hazard Can cause property damage severe injury or death Perform Gas Leak Test every time work is done on a gas system IMPORTANT Do not spray soap and water solution on the SmartValve housing Do not use an excessive amount of soap and water solution to perform the gas leak test These can damage the con trol 1 2 3 4 3 4 2 1 2 6 1 5 4 8 3 7 2 6 9 1 5 4 8 3 7 SMART VALVE...

Страница 11: ...or deduct their consumption from the meter reading Convert flow rate to Btuh as described in form 70 2602 Gas Controls Handbook and compare to Btuh input rating on appliance nameplate 3 IF CHECKING GAS INPUT WITH MANOMETER Make sure the ignition system control is in the OFF position before removing outlet pressure tap plug to connect manometer pressure gauge Also move the ignition system control s...

Страница 12: ...nt adjustment of high and low pressure settings The following sequence details adjusting the high pressure first and then adjusting the low pressure 1 Set thermostat ten degrees above room tempera ture 2 Carefully check the main burner lightoff Make sure that the main burner lights smoothly and that all ports remain lit 3 Check the full rate high manifold pressure listed on the appliance nameplate...

Страница 13: ...e 20 000 times annually should be checked monthly Intermittent use Appliances that are used seasonally should be checked before shutdown and again before the next use Consequence of unexpected shutdown Where the cost of an unexpected shutdown would be high the system should be checked more often Dusty wet or corrosive environments Since these environments can cause the gas control to deteriorate m...

Страница 14: ...AIR PROVING SWITCH PROVED OPEN COMBUSTION AIR BLOWER ON PILOT VALVE OPENS IGNITER POWERED PILOT LIGHTS AND FLAME IS SENSED DURING TRIAL FOR IGNITION CIRCULATING AIR FAN ON AFTER DELAY MAIN VALVE OPENS IGNITER OFF FLAME SENSE LOST THERMOSTAT CALL FOR HEAT ENDS FIVE MINUTE WAIT PERIOD WAIT FOR AIR PROVING SWITCH TO OPEN FLAME SENSE LOST MORE THAN FIVE TIMES IN THIS CALL FOR HEAT OR OTHER ABNORMAL OP...

Страница 15: ...F AFTER POST PURGE CIRCULATING AIR FAN OFF AFTER DELAY WAIT FOR NEXT CALL FOR HEAT THREE SECOND FLAME FAILURE RECYCLE DELAY NO YES YES YES YES NO NO PILOT AND MAIN VALVES CLOSE YES NO YES NO M10964D SV9440 SV9540 SV9640 INTERMITTENT PILOT SmartValve SYSTEM CONTROL SEQUENCE OF OPERATION WITH ST9162A 2 STAGE ELECTRONIC FAN TIMER 2 1 3 3 CIRCULATING AIR FAN OFF AFTER DELAY 1 2 3 IGNITER TURNS OFF ABO...

Страница 16: ...r a call for heat begins Combustion air blower is not energized until airflow proving switch opens 1 Airflow proving switch stuck closed 2 Airflow proving switch miswired or jum pered 3 flashes Airflow proving switch remains open longer than 30 seconds after combustion air blower energized System goes into 5 minute delay period with combustion air blower off At the end of the 5 minute delay anothe...

Страница 17: ... energized The heat speed circulating blower is energized after the heat on fan delay 1 Open manual reset or auto reset burner roll out switch 2 Open high temperature or auxiliary limit switch 3 Limit and rollout switch wiring is in good condition and securely connected 5 flashes Flame signal sensed out of proper sequence Combustion air blower is energized The heat speed circulating blower is ener...

Страница 18: ...in Table 11 Table 11 Troubleshooting without LED indicator assistance for ignition controls using an ST9160 Fan Timer or 208907 Terminal Board If And Check Repair Combustion air blower does not energize 2 flash code does not come on 30 seconds after call for heat starts 1 Combustion air blower wiring 2 Combustion air blower 3 Wiring between ST9160 and SV9540 Combustion air blower does not energize...

Страница 19: ...before thermostat call for heat ends 4 flash code comes on 1 Open manual reset or auto reset burner roll out switch 2 Open high temperature or auxiliary limit switch 3 Limit and rollout switch string wiring is in good condition and securely connected Main burner goes out before thermostat call for heat ends 4 flash code does not come on 1 Intermittent wiring connection between SV9440 SV9540 or SV9...

Страница 20: ...e information below describes a typical igni tion system control application but the specific controls used and the procedures outlined in your appliance manufacturer s instructions can differ requiring special instructions STOP Read the Warnings Above Before Proceeding The pilot flame is lit automatically If the appliance does not turn on when the thermostat is set several degrees above room temp...

Отзывы: