resideo SmartValve SV9410 Скачать руководство пользователя страница 11

SV9410/SV9420; SV9510/SV9520; SV9610/SV9620 SMARTVALVE™ SYSTEM CONTROLS

11

69-1058—05

MAINTENANCE

WARNING

Fire or Explosion Hazard.

Can cause severe injury, death or property 

damage.

Do not attempt to take the control apart or clean 

it. Improper cleaning or reassembly can cause 

gas leakage.

Regular preventive maintenance is important in 

applications such as in the commercial cooking and 

agricultural and industrial industries that place a heavy 

load on system controls because:

• In many such applications, particularly commercial 

cooking, the equipment operates 100,000 to 200,000 

cycles per year. Such heavy cycling can wear out the 

gas control in one to two years.

• Exposure to water, dirt, chemicals and heat can 

damage the gas control and shut down the control 

system. 

The maintenance program should include regular 

checkout of the control as outlined in the Startup and 

Checkout section, and the control system as described in 

the appliance manufacturer literature.

Maintenance frequency must be determined individually 

for each application. Some considerations are:

• Cycling frequency. Appliances that may cycle 200,000 

times annually should be checked monthly.

• Intermittent use. Appliances that are used seasonally 

should be checked before shutdown and again before 

the next use.

• Consequence of unexpected shutdown. Where the 

cost of an unexpected shutdown would be high, the 

system should be checked more often.

• Dusty, wet, or corrosive environment. Since these 

environments can cause the gas control to deteriorate 

more rapidly, the system should be checked more 

often.

The system should be replaced if:

• It does not perform properly on checkout or 

troubleshooting.

• The gas control is likely to have operated for more 

than 200,000 cycles.

• The control is wet or looks as if it has been wet.

SERVICE

WARNING

Fire or Explosion Hazard.

Can cause severe injury, death or property 

damage. 

Do not disassemble the ignition system control; it 

contains no replaceable components. Attempted 

disassembly or repair can damage the ignition 

system control.

CAUTION

Equipment Damage Hazard.

Improper wiring can damage the equipment.

1. Do not apply a jumper across or short the 

thermostat, 24V hot or 24V common terminal 

in the SV9410/SV9420; SV9510/SV9520; 

SV9610/SV9620 wiring harness. Doing so can 

burn out the heat anticipator in the thermostat 

or damage the system transformer.

2. After servicing, verify proper system operation.

IMPORTANT

Allow 60 seconds after shutdown before 

re-energizing step-opening model to assure 

lightoff at step pressure.

Sequence of Operation

1.

Make sure the ignition system control switch is in 

the ON position.

2.

Follow the sequence of operation as shown in Fig. 

11.

TROUBLESHOOTING

Troubleshooting with LED Indicator 
Assistance  (No cycling of appliance 
power or thermostat call for heat 
since appliance failure has 
occurred)

WARNING

Electrical Shock Hazard.

Can cause severe injury, death or property 

damage.

Only a trained, experienced service technician 

should perform this troubleshooting.

1.

Check the system thermostat to make sure it is in 

an active call for heat mode. (Do not cycle the 

thermostat on and off at this time.)

2.

Remove the appliance burner compartment door. 

Do not interrupt the power to the SV9410/SV9420; 

SV9510/SV9520; SV9610/SV9620 by opening any 

electrically interlocked panels.

3.

Observe LED indicator on SV9410/SV9420; 

SV9510/SV9520; SV9610/SV9620;  check and 

repair the system as noted in Table 9.

4.

After LED flash code analysis and appliance repair 

are complete, turn thermostat below room 

temperature for 10 seconds; turn the thermostat 

above room temperature to initiate a new call for 

heat.

5.

Observe the ignition sequence; comparing it to the 

Sequence of Operation shown in Fig. 11. Allow the 

new ignition sequence to proceed until appliance 

lights or an abnormal or unexpected event is 

observed. See next section.

Содержание SmartValve SV9410

Страница 1: ...g furnaces rooftop furnaces boilers unit heaters infrared heaters water heaters and commercial cooking appliances The specific application of the SmartValve System is the responsibility of the appliance manufacturer See Table 2 for temperature ranges and regulator types Line voltage polarity sensing models monitor the line voltage input connection to assure line voltage polarity is correct If line...

Страница 2: ...atural Gas to LP 393691 Conversion Kit LP to Natural Gas 394588 Conversion Kit Two Stage N Q suffix Conversion Kits Natural Gas to LP 396021Conversion Kit LP to Natural Gas 396025 Conversion Kit WARNING Fire or Explosion Hazard Can cause property damage severe injury or death Do NOT attempt to convert step opening models SV9510P SV9520P SV9610P SV9620P Always change the main burner orifices when c...

Страница 3: ...he control can wear out more quickly Perform a monthly checkout Water or Steam Cleaning If a control gets wet replace it If the appliance is likely to be cleaned with water or steam protect cover the control and wiring from water or steam flow Mount the control high enough above the bottom of the cabinet so it does not get wet during normal cleaning procedures High Humidity or Dripping Water Dripp...

Страница 4: ... contamination of ignition system control CAUTION Equipment Damage Hazard Improper wiring can damage equipment Never apply a jumper across or short the thermostat 24V hot or 24V common terminal in the SV9410 SV9420 SV9510 SV9520 SV9610 SV9620 wiring harness This can burn out the heat anticipator in the thermostat or damage the system transformer Follow the appliance manufacturer instructions if av...

Страница 5: ... the seals until ready to connect the piping Install Piping to Control All piping must comply with local codes and ordinances or with the National Fuel Gas Code ANSI Z223 1 NFPA No 54 whichever applies Tubing installation must comply with approved standards and practices 1 Use new properly reamed pipe free from chips If tubing is used make sure the ends are square deburred and clean All tubing ben...

Страница 6: ...he appliance manufacturer instructions All wiring must comply with applicable electrical codes and ordinances WARNING Electrical Shock Hazard Can cause severe injury death or property damage Disconnect power supply before making wiring connections to prevent electrical shock or equipment damage 1 Check the power supply rating on the ignition system control and make sure it matches the available su...

Страница 7: ...d be less than ten volts Fig 6 Testing for ground commonality Fig 7 SV9410 SV9420 SV9510 SV9520 SV9610 SV9620 typical wiring connections in fan assisted warm air furnace with ST9160 Fan Board M17570 MULTIMETER LESS THAN 10V APPLIANCE CHASSIS L1 L2 120 VAC C1 C2 C3 CONT EAC HEAT HUM M2 MOTOR PARKING TERMINALS M1 L1 NEUTRALS 24 VAC R W C COM XFMR COOL LOAD COMMON POWER SUPPLY PROVIDE DISCONNECT MEAN...

Страница 8: ...BOARD APPLIANCE CHASSIS MUST HAVE RELIABLE CONNECTION TO EARTH GROUND 1 2 3 2 3 AUXILIARY LIMIT SWITCH OPTIONAL 1 1 5 6 7 8 1 2 2 2 1 3 5 4 6 2 3 3 3 4 4 4 P1 L1 L2 M12397C DATA R 24V THERMOSTAT C R8285D CONTROL CENTER POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED CONNECT THE 120V HOT LEAD AS SHOWN DATA AND R LINES MUST BE CONNECTED TO AQUASTAT CONTROL FOR PROPER SYSTEM...

Страница 9: ...f another leak is detected tighten the adapter screws joints and pipe connections 6 Replace the part if a leak cannot be stopped Check and Adjust Gas Input and Burner Ignition CAUTION Equipment Damage Hazard Exceeding input ratings can damage the controls Do not exceed input rating stamped on appliance nameplate or manufacturer s recommended burner orifice pressure for size orifice s used Make cer...

Страница 10: ...eplace the ignition system control Otherwise take the necessary steps to provide proper gas pressure to the control NOTE If the burner firing rate is above the capacity at 1 in wc pressure drop of the control see Table 3 for capacities it may not be possible to deliver the desired outlet pressure This is an application issue not a control failure Take whatever steps are required to correct the sit...

Страница 11: ... Hazard Can cause severe injury death or property damage Do not disassemble the ignition system control it contains no replaceable components Attempted disassembly or repair can damage the ignition system control CAUTION Equipment Damage Hazard Improper wiring can damage the equipment 1 Do not apply a jumper across or short the thermostat 24V hot or 24V common terminal in the SV9410 SV9420 SV9510 ...

Страница 12: ...nnot reach your gas supplier call the fire department 2 The ignition system control must be replaced in event of any physical damage tampering bent terminals missing or broken parts stripped threads or evidence of exposure to heat IMPORTANT Follow the operating instructions provided by the manufacturer of your heating appliance The information below describes a typical ignition system control appl...

Страница 13: ...R PROVING SWITCH PROVED CLOSED WITHIN 30 SECONDS COMBUSTION AIR BLOWER OFF MAIN VALVE CLOSES COMBUSTION AIR BLOWER OFF AFTER POST PURGE 1 HOUR AUTO LOCKOUT RESET DELAY MAIN VALVE CLOSES COMBUSTION AIR BLOWER OFF AFTER POST PURGE CIRCULATING AIR FAN OFF AFTER DELAY WAIT FOR NEXT CALL FOR HEAT FAILED TRIALS FOR IGNITION LESS THAN FOUR DURING THIS IGNITION SEQUENCE NO NO YES YES YES NO NO MAIN VALVE ...

Страница 14: ... If control system includes ST9160 Electronic Fan Timer the heat speed circulating air fan will be energized until the limit string resets 1 Open manual reset or auto reset burner rollout switch 2 Open high temperature or auxiliary limit switch 3 Limit and rollout switch wiring in good condition and securely connected 5 Flashes Flame signal sensed out of proper sequence Combustion air blower is en...

Страница 15: ...s 5 on this call for heat last failure was Limit Circuit Opened During Run 1 Open high temperature or auxiliary limit switch 2 Open manual reset or auto reset burner rollout switch in the limit circuit 3 Limit and rollout switch wiring in good condition and securely connected 4 Circulating air fan wiring and operation 5 Obstructions in appliance or duct work that prevent proper circulation through...

Страница 16: ... ignition trial A total of four ignition trials will be attempted before the system goes to lockout 1 Line voltage to L1 terminal of ST9160 or Terminal Board must be 120 volts with reference to appliance chassis 2 Appliance must be reliably connected to earth ground 3 Combustion air blower moving main burner flame away from flame sense rod 4 Inlet gas pressure too low for proper flame sensing 5 Fl...

Отзывы: