GB
Resideo Technologies
6
MU1H-1254GE23 R1020
1. Safety Guidelines
1.
Follow the installation instructions.
The factory-set position of the ball valves may not be
altered. Non-compliance with this instruction will make
^
any warranty claims null and void.
2.
Use the appliance
•
according to its intended use
•
in good condition
•
with due regard to safety and risk of danger.
3.
Note that the appliance is exclusively for use in the appli-
cations detailed in these installation instructions. Any
other use will not be considered to comply with require-
ments and would invalidate the warranty.
4.
Please take note that any assembly, commissioning,
servicing and adjustment work may only be carried out by
authorized persons.
5.
Immediately rectify any malfunctions which may influence
safety.
2.
Description of function
BA type backflow preventers are divided into three pressure
zones. The pressure in zone
is higher than in zone
,
which in turn is higher than in zone
. A discharge valve is
connected to zone
which opens at the latest when the
differential pressure between zones
and
drops to 0.14
bar. The water from zone
discharges to atmosphere, both
check valves close and therefore separate zone
from zone
and
. In this way the danger of back pressure or back
syphonage into the supply network is prevented. The pipe-
work connection is interrupted and the drinking water network
is protected.
3.
Application
5.
Scope of delivery
The backflow preventer consists of:
•
Housing
•
Integrated strainer, mesh size approx. 0.2 mm
•
Valve cartridge with integrated check valve and discharge
valve
•
Outlet check valve
•
Three ball valves for the connection of a differential pres-
sure gauge
•
Connection fittings
•
Discharge connection
6.
Options
BA295CS-... A = Version with shutoff valve, threaded
connections
1
/
2
",
3
/
4
", 1
1
/
4
", 1
1
/
2
", 2"
BA295CS-1B = Version with shutoff valve, threaded
connections 1"
7.
Assembly
7.1.
Installations Guidelines
•
Install shutoff valves before and after backflow preventer
•
Install in horizontal pipework with the discharge valve
downwards
•
Ensure good access
- Simplifies maintenance and inspection
•
If a fine filter is not installed in the drinking water system,
the installation of a filter with a mesh width of 100μ m is
recommended in front of the backflow preventer.
•
In the case of fluctuating pre-pressure or an input pressure
over 10 bar, we recommend the insertion of a pressure
regulator in front of the backflow preventer.
•
Do not install in places where flooding can occur
The installation environment should be protected against
frost and ventilated well. Do not install in polluted atmo-
sphere, for example toxic vapor, aerosol, gas or dust
Install discharge pipework which has adequate capacity
Use and type of installation according to EN 1717
Installation position Horizontal with discharge valve down-
wards
Max. operating
temperature
Discharge pipe
connection
65 °C
DN50 for connection sizes
1
/
2
" - 1
1
/
4
"
DN70 for connection sizes 1
1
/
2
" - 2"
Connection size
1
/
2
" - 2"
Medium
Water
•
Maximum inlet
pressure
10.0 bar
•
Minimum inlet pressure
1.5 bar
4. Technical data
Содержание Braukmann BA295CS