LEDS AND SOUNDER

 

The 5800SMOKEV has one bi-color (red and yellow) LED with an 85dB sounder.  Refer to the 
following table below for operation of these features. 

 
 

 
 
 

LED and Sounder Indication Chart

 

 

 

Normal Operation 

Action 

Red LED 

Yellow LED 

Sounder 

Reaction 

Power Up 

Pull Battery Tab 

1 Flash 

1 Flash 

Off 

 

Tamper 

Remove from base  Off 

Off 

Off 

 

Standby - Normal 

 

Off 

Off 

Off 

 

Sensing Smoke / Heat 

Smoke / Fire 
Condition 

Rapid 

flashing 

Off 

Temporal 3 

Evacuate Premises 

Alarm Hush 

Action 

Red LED 

Yellow LED 

Sounder 

Reaction 

Silence Sounding Alarm 

Press & Release  

Button 

1 flash every 

8 seconds 

Off 

Off for 10 mins 

 

Silence Low Battery 

Press & Release  

Button 

Off 

Off for 12 hours  Off for 12 hours 

Replace both batteries 

Silence Faulty Sensor 

(only possible once) 

Press & Release  

Button 

Off 

2 flashes every 

48 seconds 

Off for 12 hours 

Replace unit 

Silence End of Life (up to 
30 days) 

Press & Release  

Button 

Off 

Off for 72 hours  Off for 72 hours 

Replace unit 

Self-Diagnostics 

Action 

Red LED 

Yellow LED 

Sounder 

Reaction 

Low Battery 

Automatic every 
16 minutes 

Off 

1 flash every 

48 seconds 

1 beep with 1 

flash 

Replace both batteries 

Faulty Smoke Sensor 

Automatic every 
16 seconds 

Off 

2 flashes every 

48 seconds 

2 beeps with 2 

flashes 

Replace unit 

Faulty Heat Sensor 

Automatic every 
second 

Off 

2 flashes every 

48 seconds 

2 beeps with 2 
flashes 

Replace unit 

End of Life 

Automatic every 4 
hours 

Off 

3 flashes every 

48 seconds 

3 beeps with 3 
flashes 

Replace unit 

Maintenance 

Automatic every 
16 seconds 

Off 

4 flashes every 

48 seconds 

Off 

Clean unit; see Cleaning 
section 

Test Button 

Action 

Red LED 

Yellow LED 

Sounder 

Reaction 

Detector Status Good – 
Normal Alarm 

Press & Hold  

Button 

Rapid 

flashing 

Off 

Temporal 3 

Release button 

Low Battery 

Press & Hold  

Button 

Off 

1 flash then 

rapid flashing 

1 beep then 

Temporal 3 

Replace both batteries 

Faulty Sensor 

Press & Hold  

Button 

Off 

2 flashes then 

rapid flashing 

2 beeps only 

Replace unit 

End of Life 

Press & Hold  

Button 

Off 

3 flashes then 

rapid flashing 

3 beeps then 

Temporal 3 

Replace unit 

Maintenance  

Press & Hold  

Button 

Off 

4 flashes then 

rapid flashing 

4 beeps then 

Temporal 3 

Clean unit; see Cleaning 

section 

Alarm Memory 

Action 

Red LED 

Yellow LED 

Sounder 

Reaction 

24 Hour Memory 

After Alarm 

2 flashes every  

48 seconds for  

24 hours 

Off 

Off 

Press & Hold Button for 
Long Term Memory 

Long Term Memory 

Press & Hold  
Button 

Rapid 
flashing 

Off 

Rapid chirping 

Memory is reset after 
releasing the test button 

 

 
 
CLEANING

 

Recommended

:  To prevent unwanted alarms, notify the Central Station that the 

smoke detector system is undergoing maintenance before cleaning the detector. 

To clean the detector, carefully vacuum the side vents all the way around, then, 
wipe them with a clean damp cloth and dry thoroughly.   

Do NOT attempt to take the detector apart.  This could result in damaging the unit. 

 
 
 

 

Cleaning

 

 

 