www.republic-mfg.com
800.847.0380
62
Recommended Maintenance Schedule for Republic Blowers
Filter Maintenance
(May be performed by untrained personnel)
Filters should be changed as needed to maintain a differential pressure of less than 10 inches (254 mm) of water pressure
differential. The dial on your filter change gauge should be in the green zone. Normal change intervals are between every two (2)
weeks and 90 days depending on the contamination levels in your plant. See Filter Data Reference for additional information.
Replacement Filter Reference
Description
Part No. Max. CFM
Temperature
Micron
Small Paper
340-1000
880 CFM
Min. Temp. -15°F/Max. Temp. 220°F
Min. Temp. -26.1 C/Max. Temp. 104.4°C
99.9% efficiency to 10 Micron
Large Paper
340-1002
1100 CFM
Min. Temp. -15°F/Max. Temp. 220°F
Min. Temp. -26.1 C/Max. Temp. 104.4°C
99.9% efficiency to 10 Micron
Small Polyester
340-2000
880 CFM
Min. Temp. -15°F/Max. Temp. 220°F
Min. Temp. -26.1 C/Max. Temp. 104.4°C
99+% efficiency to 10 Micron
Large Polyester
340-2002
1100 CFM
Min. Temp. -15°F/Max. Temp. 220°F
Min. Temp. -26.1 C/Max. Temp. 104.4°C
99+% efficiency to 10 Micron
HEPA Filter Maintenance
(May be performed by untrained personnel)
The HEPA filter element should be changed to maintain less than 10 inches (254 mm) of water pressure differential. The dial on
your filter change gauge should be in the green zone. The change interval is once every six (6) months. See Filter Data Reference
for additional information.
Replacement Filter Reference
Description
Part No. Max. CFM
Temperature
Micron
Small HEPA
340-3000
800 CFM @ 1”
W.C.
Min. Temp. -15°F/Max. Temp. 220°F
Min. Temp. -26.1 C/Max. Temp. 104.4°C
99.9% efficiency to 10 Micron
Large HEPA
340-3001
1000 CFM @
1”W.C.
Min. Temp. -15°F/Max. Temp. 220°F
Min. Temp. -26.1 C/Max. Temp. 104.4°C
99.9% efficiency to 10 Micron
Enclosure Filter Maintenance
(May be performed by untrained personnel)
Replacement Part No. 292-0001 (paper)
This filter is designed to remove large contaminants from entering the inside of your enclosure. If this filter gets dirty, your blower
could overheat and discharge pressure could be reduced.
Replacement Part No. 292-0002 (metallic)
This filter is designed to remove large contaminants from entering the inside of your enclosure. It is an oil wetted wire mesh filter.
Recommended cleaning interval is weekly or as needed in your facility. If this filter gets dirty, your blower could overheat and
discharge pressure could be reduced.
Cleaning Procedure for Part No. 292-0002
1. Blow off contaminants with compressed air.
2. Clean with solvent in a parts washing tank.
3. Spray with a light coating of WD 40 or similar lightweight oil.
Proper pulley alignment is very important.
Содержание RB-SERIES
Страница 24: ...www republic mfg com 800 847 0380 24 RB2000 Exploded View ...
Страница 50: ...www republic mfg com 800 847 0380 50 340 1040 340 2040 Stainless Steel Large Inlet Filter Assembly ...
Страница 51: ...800 847 0380 www republic mfg com 51 340 1030 340 2030 Stainless Steel Small Inlet Filter Assembly ...
Страница 52: ...www republic mfg com 800 847 0380 52 340 1035 RB2000 Stainless Steel Inlet Filter Assembly ...
Страница 53: ...800 847 0380 www republic mfg com 53 340 2070 340 2071 RB4000 RB4002 Inlet Filter Assembly ...
Страница 56: ...www republic mfg com 800 847 0380 56 RB800 1200HC Low Profile Enclosure Enclosures ...
Страница 59: ...800 847 0380 www republic mfg com 59 RB4000 Painted Aluminum Enclosure ...
Страница 69: ...800 847 0380 www republic mfg com 69 ...