Energy storage integrated machine
LCD operation instructions
-27-
5.3.2 Instruction for setup parameter
Name of
parameter
group
No.
Menu
Name of setup
parameter
Instruction/Range of the set value
PV parameter
1
Connection mode
PV connection
mode:
PV connection mode:
(0: Independent; 1: Parallel)
Grid
parameter
1
PF setup
PF:
PF setup, range: -1.000-1.000
2
Output power
control
Output power
(%)
:
Range: 0-100%
Battery
parameter
1
Battery type
Battery type:
Battery type:
0: Lithium iron phosphate battery 1:
Lead acid battery
3: Ternary lithium battery
2
Battery protocol
Battery protocol:
Battery protocol:
1: Pylon 2: Sunwoda 3: Yinlong 4:
Xstellar 5: FES 6: Olipower 7: GCL
8: DLG 9:Penghui 10:Yiwei
3
Charge voltage
Charge voltage:
Charge voltage range: 0-60 V
4
Charge current
Charge current:
Charge voltage range: 0-100 A
5
Discharge critical
voltage
Discharge critical
voltage:
Discharge critical voltage range:
40-55V
Critical recovery
voltage:
Critical recovery voltage range:
40-55V
(Recovery voltage must be greater
than the critical voltage)
6
Forced charge
voltage
Range: 40-55V
7
Charge time period
1 setup
Charge time period
1 starts:
Start time of charge time period 1,
range: 0-23:59
Charge time period
1 ends:
End time of charge time period 1,
range: 0-23:59
8
Discharge time
period 1 setup
Discharge time
period 1 starts:
Start time of discharge time period
1, range: 0-23:59