Erbas Teknoloji - Reporter MX1144-DGR/B/H User Manual 

Responses   

Process Succeed.  

 

// format & pass is correct 

 

 

 

 

Process Failed!   

 

// format is wrong 

5.8.

 

Change SMS Text Message Contents 

You can change Alarm SMS Text Message Contents according to your requirements. Thus, you will be 
able to rename Alarm words instead of remembering which input is connected to which equipment. 

Note: Message Content is limited to 32 characters. Upper or lower case letters and digits are allowed to 
use. Only English letters are accepted according to ASCII. 

Content index list is below: 

PAT0 

 

: Keep Alive 

PAT1…

 

: Input1...4 Low-to-High change alert 

PAT9…1

2   

: Input1...4 High-to-Low change alert (i.e. Input1 matches with PAT9) 

PAT17 

 

: Device Activated (or power restored) 

PAT18 

 

: Power Failed (/B versions only) 

PAT19 

 

: Low Battery (/B versions only) 

Authorization 

Admins only  

Format 

 

Password

<space>

PATx:AlarmText# 

Examples   

1111 PAT1:Office Door Opened# // Input1 High alarm content changed 

 

 

 

 

1111 PAT9:Office Door Closed#  // Input1 Low alarm content changed 

Responses   

Process Succeed.  

 

// format & pass is correct 

 

 

 

 

Process Failed!   

 

// format is wrong 

5.9.

 

Input Delay Configurations 

As factory default, any instant change on input status will trigger an alert. In some cases, you might 
want to add a delay on a specific input change event up to 99 seconds. For example, if 

you don’t want 

to receive alert notifications upon every door open/close event; you may set Input High and/or Input 
Low delays to i.e. 60 seconds. Thus, it will not trigger unnecessary alerts and create the alert in case it 
left open for at least 1 minute. 

Reporter allows you to set these delays on each input individually.  

Also, low-to-high and high-to-low events could be set individually as well. 

 

 

Authorization 

Admins only  

Format 

 

Password

<space>

INPHx:Period 

 

 

 

 

Password

<space>

INPLx:Period 

Examples   

1111 INPH2:60   

 

// Input2 High alarm delay is 60 secs 

 

 

 

 

1111 INPL2:0   

 

// Input2 Low alarm delay set to 0 

Responses   

Process Succeed.  

 

// format & pass is correct 

 

 

 

 

Process Failed!   

 

// format is wrong 

5.10.

 

Set Heartbeat (Keep Alive) Interval Period 

Содержание MX1144-DGR

Страница 1: ...1 Erbas Teknoloji Reporter MX1144 DGR B H User Manual USER MANUAL MX1144 DGR rev1 06 1021 MX1144 DGR B H GSM SMS ALARM CONTROLLER www erbasteknoloji com ERBAŞ TEKNOLOJİ Innovative Solutions ...

Страница 2: ... remote devices via SMS and phone calls Other usages are not permitted Police fire or healthcare emergency call lines are not permitted to call directly from this device Do not configure emergency call numbers into this device BATTERY RECYCLING CR123A Lithium batteries are classified as recycled batteries Please take your empty batteries to a nearest collection point BATTERY LIFE Battery life anno...

Страница 3: ... High Text Message and optional phone call ring Port2 Low Text Message and optional phone call ring Port3 High Text Message and optional phone call ring Port3 Low Text Message and optional phone call ring Port4 High Text Message and optional phone call ring Port4 Low Text Message and optional phone call ring Power Failure Detailed Text Message and optional phone call ring Power Restored Detailed T...

Страница 4: ... plant etc Different kinds of motors and machines and much more As soon as integrated relay power is suitable up to 10A 240VAC any kind of device machine system could be controlled with this device In some cases where required switching power is higher than the device capacity then it can still control those devices by some additional high capacity switching equipment i e contactors 2 2 Input Moni...

Страница 5: ...l Mount Firstly unscrew the Cover Fitting screws and then open the top cover If you want to mount your device to the wall Place device to the wall Point Wall Mount screwing holes shown below to the wall Drill the wall from pointed places Insert fixing plugs into the drilled points Screw in the wall mount screws from the screwing points of the device ...

Страница 6: ...l if you require services should be active on the SIM However Data Internet GPRS services are not required Before inserting the SIM card try it with a mobile phone And then o Disable PIN code protection o Send an SMS to a mobile number for testing o Call a mobile phone number for testing After above steps completed open the screws And insert SIM card into the device by pushing it as shown in below...

Страница 7: ...uipment Reporter inputs are digital and isolated 4 3 Insert Batteries Optional Insert two pieces of CR123A or CR123 lithium batteries in case of power failure feature is required Make sure you followed correct polarity of the batteries You will see indications on the board 4 4 Connect Power Note Wires should pass into the holes of the bottom cover Please check Wiring Diagram Connect 12V DC power s...

Страница 8: ... nr x High to Low Delay INPLx y 0 0 99 secs ADMIN Set Keep Alive Heartbeat SMS Period KA x 0 means disabled 0 999 hours ADMIN Get Device Status Info STATUS ADMIN Restore Factory Settings RESET ADMIN Activate Relay nr x RLYx ON ADMIN USER Deactivate Relay nr x RLYx OFF ADMIN USER Time based Activate Relay nr x for y secs RLYx y 0 99 secs ADMIN USER SMS message format is Password space Command1 spac...

Страница 9: ...d done but now memory is full Record Failed Memory Full cannot record because memory is full 5 2 Change Password Authorization Admins only Format Password space PASS NewPassword Example 1111 PASS 6666 Responses Process Succeed format password is correct Process Failed format is wrong Note New Password must be always different than 1111 5 3 Register Add User s Note Total 20 1 000 for H models peopl...

Страница 10: ...11 CALL ON enables phone calls 1111 CALL OFF disables phone calls Responses Process Succeed format pass is correct Process Failed format is wrong 5 7 MOD1 MOD2 Selection Relay Control by Phone Calls To control Relay Outputs by Phone Calls Reporter has two different mode options Only one of them has to be selected As factory default MOD1 is selected MOD1 is only used to trigger RLY1 in a predefined...

Страница 11: ... High alarm content changed 1111 PAT9 Office Door Closed Input1 Low alarm content changed Responses Process Succeed format pass is correct Process Failed format is wrong 5 9 Input Delay Configurations As factory default any instant change on input status will trigger an alert In some cases you might want to add a delay on a specific input change event up to 99 seconds For example if you don t want...

Страница 12: ...ESET Resetting the device does not mean any performance change on this device Reset only deletes all registered numbers and deletes all configurations password settings Thus device will restore itself into factory settings Authorization Admins only Format Password space RESET Examples 1111 RESET reset device Responses Process Succeed format pass is correct Process Failed format is wrong 6 CHECK DE...

Страница 13: ...ll Turn ON RLY1 for predefined period and it will Turn OFF RLY1 after this period If this mode is selected MOD2 will be automatically disabled 7 2 Call DTMF Dial Method MOD2 MOD2 is used to Turn ON Turn OFF all available Relays individually via DTMF Call Dial Service When you call device it will hang up and wait you dial Relay Nr and dial for ON OFF If your dials are not detected properly please m...

Страница 14: ...iMessage I don t receive power failure SMS notifications Version not suitable Only B versions have this function Batteries not inserted or died Insert replace fresh batteries Alarm occurred I received SMS but I didn t receive a Call Call feature not activated Check Alert Calls Activate instructions SIM card Call service not activated Contact SIM card provider Alarm occurred I received Call but did...

Страница 15: ...ge Events SMS Call Power Up SMS Call Power Failure B versions only SMS for Low Battery SMS for Keep Alive Messages SMS for Status Query Relay Control Modes SMS Call Trigger MOD1 Call DTMF Dial MOD2 Admin User Capacity 8 Admins 20 Users 1 000 users for H versions Configurations via SMS Change password Add delete admins and users Activate deactivate alert Call function Set call control modes Set inp...

Страница 16: ...16 Erbas Teknoloji Reporter MX1144 DGR B H User Manual 10 NOTES Device Phone Number Admin Numbers User Numbers Made in Türkiye ...

Отзывы: