5.4 Wiring the DC input
This subsection provides procedures for wiring the DC input from the PV array
to the Digiwatts unit.
5.4.1 DC Connection Requirements
WARNING!
All electrical installations must be done in accordance with all local
electrical codes and with the National Electrical Code (NEC),
ANSI/NFPA 70. For installation in Canada the installations must be
done in accordance with applicable Canadian standards.
WARNING!
Use #8 AWG-10AWG, 105 °C, copper wire for all DC wiring connections
to the Digiwatts. Voltage drop and other considerations may dictate
that larger size wires be used. Use only solid or stranded wire but not
fine stranded wire.
WARNING!
Any additional DC disconnect for the inverter must have a minimum
rating of 600VDC and 25A continuous.
Information
Series fusing may be required depending on the type of PV module used
in the system. See NEC 690.9.
WARNING!
You must connect the wires that carry the DC voltage from the PV array to the
Digiwatts unit in the order described in the following procedure. Deviating from
this procedure could expose you to lethal voltages that can cause serious injury
and/or death.