21
22
VDE4105, VDE 0126-1-1+A1, G83/2, G59/3, AS4777.2/.3
IEC62109-1&-2, AS3100, IEC62040-1
EN61000-6-1, EN61000-6-2, EN61000-6-3, EN61000-6-4, EN61000-3-11, EN61000-3-12
30
28
516*440*184mm
516*440*184mm
Protection
Residual current monitoring unit
Anti-islanding protection
DC switch(PV)
AC over current protection
Insulation monitoring
Certifications&Standards
Grid regulation
Safety
EMC
General Data
Dimensions (WxHxD)
Weight (kg)
Mounting
Ambient temperature range
Relative humidity
Moisture location category
Max. operating altitude
Protection degree
Environment category
External environment pollution degree
Topology
Standby losses(W)
Cooling
Noise emision(dB)
Display
Communication
Standard warranty(years)
Integrated
Integrated
Integrated (optional)
Integrated
Integrated
Wall-mounted
-25~60°C
(>45°C derating)
0~95%
4K4H
2000m
IP65
Outdoor & indoor
Grade1
、
2
、
3
Transformerless
<8
Nature convection
<25
LED light & APP
USB2.0 or Wi-Fi
5/10/15/20/25 (optional)
Bracket
Model
Replus 5048ME
Replus 3648ME
*
listed in the table.
It is recommended that the total peak power of PV strings should not exceed 130% of maximum DC power of inverter
10 Certificates
59
VDE0126-1-1
Note
Overvoltage category definition
Category I
:
applies to equipment connected to a circuit where measures have been taken to reduce transient overvoltage to a
low level.
Category II
:
applies to equipment not permanently connected to the installation. Examples
are appliances, portable tools and
other plug-connected equipment;
Category III
:
applies to fixed equipment downstream of and including, the main distribution board. Examples are switchgear
and other equipment in an industrial installation;
Category IV
:
applies to equipment permanently connected at the origin of an installation (upstream of the main distribution
board). Example are electricity meters, primary overcurrent protection equipment and other equipment connected
directly to outdoor open lines.
Environment category definition
Outdoor : the ambient air temperature is -20~50°C, Relative humidity range is 4 % to 100 %, applied to PD3
Indoor unconditioned: the ambient air temperature is -20~50°C, Relative humidity range is 5 % to 95%,applied to PD3
Indoor conditioned: the ambient air temperature is 0~40°C, Relative humidity range is 5 % to 85%,applied to PD2
Pollution
degree
d
efinition
Pollution degree 1
:
No pollution or only dry, non-conductive pollution occurs. The pollution has no influence.
Pollution degree 2
:
Normally only non-conductive pollution occurs. Occasionally, however, a temporary conductivity caused by
condensation must be expected.
Pollution degree 3
:
Conductive pollution occurs, or, dry, non-conductive pollution occurs which becomes conductive due to
condensation which is expected.
Pollution degree 4
:
Persistent conductive pollution occurs, for example, the pollution cause by conductive dust, rain and snow.
Moisture
parameters
Level
Temperature Range
Humidity Range
3K3
0~+40℃
5%
~
85%
4K2
-33~+40℃
15%
~
100%
4K4H
-20~ +55°C
4%
~
100%
Moisture
location
category
definition