Bare Wire Length

Conductor Material
Sectional Area

Value

10~12mm

2

20~25mm

10mm around

08

07

Figure

 

4.2-3

Installation instruction of SUNCLIX please refer to Figure 4.2-2.

Installation instruction of MC4 please refer to Figure 4.2-3.

Negative 

plug

Positive 

plug

Figure

 

4.2-2

Figure

 

4.3-1

A

B

C

Special tools are used to stitching

Inverter

 

side

4.3 Battery Connection

Before connecting to battery, please install a separate DC breaker (60A for Replus 3648ME and 120A for 

) between 

inverter and battery. This will ensure the inverter can be securely disconnected during maintenance. 

● 

Be aware of electric shock and chemical hazards!

● 

It is a normal phenomenon that electric arc occurs when connecting battery to the inverter without use a DC breaker.

●  

It's  very  important  for  system  safety  and  efficient  operation  to  use  appropriate  cable  for  battery  connection. To  reduce  risk  of 

injury, please use the proper recommended cable size. Refer to Figure 4.3-1.

Replus 5048ME

● 

if

 

t

to

 

be

 

for

 

● 

Suggestion: Batteries

 

must be installed with a distance to each other, details please refer to battery manufacture's user manual.

● 

As

 

for the number of cells used, it will be decided by customer's choice, the choice must

 

comply with the followed requirement: 

the rated voltage is 48V.

Please follow below steps to implement battery connection: 

(

1

)

 Check the nominal voltage of batteries. The nominal output voltage should meet ReneSola product Spec.

(

2

)

 Disconnect DC breaker between inverter and battery.

(

3

)

 Disconnect screw cap from insulator.

(

4

)

 Disconnect waterproof ring from insulator.

(

5

)

  Put  the  cable  through  the  components  in  this  order:  screw  cap,  waterproof  ring,  insulator,  battery  cover  and  battery  terminal. 

Refer to Figure 4.3-2.

(

6

)

 Compress the terminal head by professional tool and screw down screw cap slight. Refer to Figure 4.3-3, Figure 4.3-4.

(

7

)

 Put battery terminals into the corresponding holes and fasten them by screwdriver and spanner 

(

recommended torsion:50~70Kg-

f.cm), then fasten battery cover with pan head screws in accessory bag. Refer to Figure 4.3-5, Figure 4.3-6, Figure 4.3-7.

(

8

)

 Screw down screw cap again.

Suggestion: 

he battery is 

installed indoor, 

details please refer to battery manufacture's user manual.

Positive 

plug

N

egative 

plug

Inverter

 

side

7mm

7mm

2

2

.

5

~

4mm

2

2

.

5

~

4mm

Figure

 

4.3-3

Crimp

Cable

Figure

 

4.3-2

Waterproof

 

ring

Battery

 

cover

Battery

 

terminal

Screw

 

cap

Insulator

SUNCLIX

 

Series

MC4

 

Series

Figure

 

4.2-1

There are two types of DC plugs, SUNCLIX and MC4 series. Please refer to Figure 4.2-1.

●  

permanently damage the inverter.

·

● 

Check the short-circuit current of the PV string. The total short-circuit current must not exceed the inverter’s maximum PV current. 

·

● 

PV array should not be connected to the grounding conductor.

·

● 

Must be use DC plugs in accessory bag.

·

● 

The  minimum  insulation  resistance  to  ground  of

 

the

 

PV  pannels

 

must

 

exceed  19.33k

Ω

,  there  is  a  risk  of  shock  hazard  if  the 

requirement of

 

minimum resistance is not met.

Before  connecting  the  PV  panels,  ensure  the  plug  connectors  have  the  correct  polarity.  Incorrect  polarity  could 

4.2 PV Connection 

● 

Reversed

 

polarity

 

will

 

damage

 

the

 

inverter

!

Содержание Replus 3648ME

Страница 1: ...rned off and disconnected to ensure safety in any installation operation The package product should be handled carefully and never be tipped over or slung 2 2 Safety Installation maintenance and conne...

Страница 2: ...n head screw 8 Flat head screw 5 Max 15 than the following value In consideration of heat dissipation and convenient dismantlement the minimum clearances around the inverter should be no less Upward 3...

Страница 3: ...ver and AC terminal Refer to Figure 4 1 2 7 Compress the terminal head by professional tool and screw down screw cap slight Refer to Figure 4 1 3 Figure 4 1 4 8 Insert AC terminals into the correspond...

Страница 4: ...breaker between inverter and battery 3 Disconnect screw cap from insulator 4 Disconnect waterproof ring from insulator 5 Put the cable through the components in this order screw cap waterproof ring i...

Страница 5: ...e terminal Negative terminal Figure 4 3 6 Figure 4 3 7 Hexagon head screw Pan head screw 4 5 EzMeter Connection EzMeter can detect the current magnitude and direction to control the working condition...

Страница 6: ...munication connects to EzConverter via CAN interface if lithium battery communication protocol is CAN Refer to Figure 4 6 2 Lithium battery communication connects to EzConverter via RS 232 interface i...

Страница 7: ...8 1 Figure 4 8 1 Open USB cover Touch switch 5 LED Lights Illustration 6 EzManage Operation Illustration Hybrid Series inverter has no LCD screen it can be controlled via mobile device with the APP so...

Страница 8: ...me charge is preferred Battery Selection Advanced Settings Feeding To Grid When the switch is yes excess energy of PV can feed to grid Shadow Scan When switch is on it can resolve the multiple wave pr...

Страница 9: ...ssfully created Please enter the registered user name and password when you created the solar station 7 Work Modes Hybrid series inverters have the following main work modes based on different conditi...

Страница 10: ...y Communication Fail Battery Output Short 8 Error Messages 9 Technical Parameters Model Category SUNCLIX MC4 Optional Replus 5048ME 5400 580 125 550 125 15 15 20 2 2 can parallel Lead acid or Li Ion 4...

Страница 11: ...installation Examples are appliances portable tools and other plug connected equipment Category III applies to fixed equipment downstream of and including the main distribution board Examples are swi...

Отзывы: