COOL Mode:
thermostat controls the temperature according to the following diagram
o
o
Example for Cooling: (Set point = 80 F, Swing = 1 F)
o
o
=> Cooler turns on when room temp is 81 F and off at 79 F.
AUTO:
thermostat controls the temperature according to the following diagram
o
o
There is a dead band 4 F/2 C between heat set point and cool set point.
Example 1: If user select heat set point is 70F, the minimum cool set point will be
o
o
limited at "heat set point" + 4 F: 74 F
o
o
Pervious heat set point is 70 F and cool set point is 74 F
o
Example 2: If user changes heat set point to 72 F, cool set point will be updated to
o
76 F automatically to maintain the dead band.
Swing
Temperature
Output
Off
Cool
Turn off
Set point
Turn on
Temperature
Output
Off
Heat
st
1 Turn off
nd
2 Turn off
Heat Set point
st
1 Turn on
nd
2 Turn on
Diff
Swing
Swing
Dead band
Cool Set point
28