
Series
WKF 85
WKF-com-
pact 85
Refr. / pre-charge quantity out. mod.
-- / kg
R 410A
2)
/ 1,90
Refrigerant / pre-charge quantity
for up to 10 m length of ordinary pipe
g / m
50
Refrigerant connection
Inches (mm)
3/8" (9,52) / 5/8" (15,9)
Max. refrigerant pipe length
m
50
Max. refrigerant pipe height
m
30
Power supply
V / Hz
220-240 / 50
Max. current consumption
A
10,20
Rated current consumption for A7/W35
A
8,58
Rated power consumption for A7/W35
kW
1,82
Rated power consumption for A2/W35
kW
1,45
Max. power consumption
kW
3,6
Power factor A7/W35 (cosφ)
--
0,98
Fuse protection on-site (o. mod.)
A delax-act.
16
Rated water flow (acc. to EN 14511, at ∆t 5 K)
m³/h
1,38
Pressure-loss at the condenser at nominal flow rate
bar
0,1
Pressure-loss external
kPa
80
Air-nominal flow rate outdoor module
m³/h
2760
Max. operating pressure, water
bar
3
Hydraulic connection, supply / return
Inches (mm)
1" (25,4)
Sound-power level in accordance with
DIN EN 12102:2008-09 and ISO 9614-2
dB(A)
64,0
Sound-pressure level, LpA (out. mod.)
3
dB(A)
38,5
Dimensions, indoor module (h/w/d)
mm
500/800/
500
1928/800/
790
Dimensions, outdoor module (h/w/d)
mm
800 / 880 / 312
Enclosure class outdoor module
--
IP 24
Weight indoor module
kg
50
248
Weight outdoor module
kg
57
1)
COP = coefficient of performance or performance number according to EN 14511
2)
Contains greenhouse gas according to Kyoto protocol, GWP 1975
3)
Distance 5m, VDE tested, A7/W45/58Hz, at full spherical propagation
Data provided without guarantee! We reserve the right to modify the dimensions and constructional design
as part of the ongoing technical-development process.
9
Содержание WKF -compact Series
Страница 110: ...REMKO WKF WKF compact 110 ...
Страница 111: ......