14.2 Error messages on the outdoor modules
Outdoor modules error display
1
1
A
B
Fig. 83: Displays on outdoor modules
1: Display
A: WKF/WKF-compact 85
B: WKF/WKF-compact 120/180 / WKF 120/180 Duo
Display
LED display
Replace Meaning
Red
Green
Yellow
E101
-
-
-
IM
Communication error between indoor unit and outdoor
unit or wrong platinum versions
E102
-
-
-
IM
Interruption in communication between indoor unit and
outdoor unit
E162
-
-
-
IM
EEPROM error
E177
l
(+)
m
OM
Outdoor unit has received an emergency stop signal
E201
l
Z
m
OM
Communication error between indoor unit and outdoor
unit or wrong platinum versions
E202
l
l
or
m
m
OM
Interruption in communication between indoor unit and
outdoor unit
E203
l
l
Z
OM
Communication error between main and inverter board
E221
l
Z
m
OM
Error in outside temperature probe
E231
l
Z
m
OM
Evaporator probe error
E251
l
Z
m
OM
Hot gas temperature probe error
E320
l
Z
m
OM
Overload switch probe error
E403
l
Z
m
OM
Ice protection compressor (in cooling mode only)
E404
l
Z
m
OM
Safety operation after compressor overload
(normal operation)
E407
l
Z
m
OM
Disruption by high pressure switch
E416
l
Z
m
OM
Compressor overheated
E419
l
Z
m
OM
Malfunction of electronic expansion valve
E425
l
Z
m
OM
Phase error malfunction. Minimum a phase conductor is
missing (WKF 180 only) or wrong EEPROM on the
motherboard (WKF 120 only)
E440
l
Z
m
OM
Heating mode is not possible; outdoor temp. > 35°C
E441
l
Z
m
OM
Cooling mode is not possible; outdoor temp. < +10°C
E443
l
Z
m
OM
Gas leakage error (before operation)
E458
m
m
l
OM
Compressor start error
79