Series
WKF 120
WKF-
compact
120
WKF 180
WKF-
compact
180
Refrigerant connection
Inch (mm)
3/8" (9,52) / 5/8" (15,9)
Max. refrigerant pipe length
m
50
75
Max. refrigerant pipe height
m
30
Power supply
V / Hz
220-240 / 50
380-415 / 3~ / 50
Max. current consumption
A
22
11 per phase
Rated current consumption for A7/W35
A
10,44
5,02 (per phase)
Rated power consumption for A7/W35
kW
2,22
3,09
Rated power consumption for A2/W35
kW
1,91
2,64
Max. power consumption
kW
4,0
4,5
Power factor A7/W35 (cosφ)
--
0,97
0,95
Fuse protection on-site (o. mod.)
A Träge
20
3 x 16 A
Rated water flow (acc. to EN 14511, at
∆t 5 K)
m³/h
1,70
2,4
Pressure-loss at the condenser
at nominal flow rate
bar
0,1
Pressure-loss external
kPa
80
Air-nominal flow rate outdoor module
m³/h
3700
5400
Max. operating pressure, water
bar
3
Hydraulic connection, supply / return
Zoll (mm)
1 1/4" (31,8)
Sound-power level in accordance with
DIN EN 12102:2008-09 and ISO 9614-2
dB(A)
67,9
68,3
Sound-pressure level, LpA (out. mod.)
3
dB(A)
42,2
42,4
Dimensions, indoor module (h/w/d)
mm
500/800/
500
1928/800/
790
500/800/
500
1928/800/
790
Dimensions, outdoor module (h/w/d)
mm
998 / 940 / 330
1420 / 940 / 330
Enclosure class outdoor module
--
IP 24
Weight indoor module
kg
50
250
55
252
Weight outdoor module
kg
74
100
1)
COP = coefficient of performance or performance number according to EN 14511
2)
Contains greenhouse gas according to Kyoto protocol, GWP 1975
3)
Distance 5m, VDE tested, A7/W55/58Hz, at full spherical propagation
Data provided without guarantee! We reserve the right to modify the dimensions and constructional design
as part of the ongoing technical-development process.
REMKO WKF / WKF-compact
12
Содержание WKF -compact Series