2.5 Unit data WKF 120/180 Duo
Series
WKF 180
WKF-com-
pact 180
Function
Heating or Cooling
System
Split air/water
Heat pump manager
Smart Control
Enamelled drinking water storage tank
External
Auxiliary heater / rated output
kW
Optional / 9 kW
Domestic hot-water heating (changeover valve)
Optional, external
Connection oil/gas-fired boiler
External
Heating capacity min. / max.
kW
2.5-25.0
3.1-35.4
Heating capacity / compressor frequency / COP
for A12/W35
kW/Hz/COP
21.92/61/4.82
32.4/56/5.33
Heating capacity / compressor frequency / COP
1)
for A7/W35
kW/Hz/COP
19.72/61/4.44
28.04/56/4.53
Heating capacity / compressor frequency / COP
1)
for A2/W35
kW/Hz/COP
13.90/60/3.64
18.64/56/3.53
Heating capacity / compressor frequency / COP
1)
for A7/W35
kW/Hz/COP
12.28/61/2.89
16.40/56/2.87
Heating capacity / compressor frequency / COP
1)
for A15/W35
kW/Hz/COP
9.64/61/2.39
12.72/56/2.40
Heating capacity / compressor frequency / COP
1)
for A7/W45
kW/Hz/COP
20.30/58/3.67
24.54/56/3.46
Heating capacity / compressor frequency / COP
1)
for A7/W55
kW/Hz/COP
17.98/61/2.78
25.70/56/2.92
Heating capacity / compressor frequency / COP
1)
for A7/W55
kW/Hz/COP
9.26/61/1.79
13.98/56/1.94
Cooling capacity min. / max.
kW
3.30 -18.00
5.50 -32.00
Cooling capacity / compressor frequency / EER
for A35/W7
kW/Hz/EER
13.58/66/2.33
24.40/72/2.60
Cooling capacity / compressor frequency / EER
for A35/W18
kW/Hz/EER
10.60/38/3.66
25.4/38/3.81
Cooling capacity / compressor frequency / EER
for A27/W18
kW/Hz/EER
18.92/66/3.61
36.40/66/4.01
Usable limits, heating
°C
-20 to +45
Service limits, cooling
°C
+15 to +45
Max. inlet temperature, heating water
°C
55
Min inlet temperature, cooling
°C
7
Refrigerant / basic capacity per outdoor unit
-- / kg
410A / 2.00
410 A / 2.80
Refrigerant /
pre-charge quantity for up to 10 m length of ordinary pipe
g/m
50
Refrigerant connections
Inches (mm)
3/8" (9.52) / 5/8" (15.9)
REMKO WKF / WKF-compact