![REMKO Smart Com Скачать руководство пользователя страница 21](http://html1.mh-extra.com/html/remko/smart-com/smart-com_instructions-for-use-manual_1438876021.webp)
CO
1)
Grp.-
addr.
2)
Name
3)
DPT
4)
Size
5)
Communica-
tion flag
6)
Function description
20
5/0/21
3rd mixed HC
room temper.
DPT 9.001
(DPT_Value_Te
mp)
-273°C - 670
760°C
2 byte
C
-
W
-
The room temperature is
sent from the KNX bus to
the Smart Control controller
and used for the circuit's
room temperature influ-
ence. The selection param-
eter for the room control
must be set to KNX for this.
21
5/0/22
4th mixed HC
room temper.
DPT 9.001
(DPT_Value_Te
mp)
-273°C - 670
760°C
2 byte
C
-
W
-
The room temperature is
sent from the KNX bus to
the Smart Control controller
and used for the circuit's
room temperature influ-
ence. The selection param-
eter for the room control
must be set to KNX for this.
22
5/0/23
Cooling circuit
room temper.
DPT 9.001
(DPT_Value_Te
mp)
-273°C - 670
760°C
2 byte
C
-
W
-
The room temperature is
sent from the KNX bus to
the Smart Control controller
and used for the circuit's
room temperature influ-
ence. The selection param-
eter for the room control
must be set to KNX for this.
23
5/0/24
Unmix. HC
room humidity
DPT 9.007
(DPT_Value_H
umidity)
0 % - 100 %
2 byte
C
-
W
-
The room temperature is
sent from the KNX bus to
the Smart Control controller
and used for the circuit's
room temperature influ-
ence. The selection param-
eter for the room control
must be set to KNX for this.
24
5/0/25
1st mixed HC
room humidity
DPT 9.007
(DPT_Value_H
umidity)
0 % - 100 %
2 byte
C
-
W
-
The room temperature is
sent from the KNX bus to
the Smart Control controller
and used for the circuit's
room temperature influ-
ence. The selection param-
eter for the room control
must be set to KNX for this.
25
5/0/26
2nd mixed HC
room humidity
DPT 9.007
(DPT_Value_H
umidity)
0 % - 100 %
2 byte
C
-
W
-
The room temperature is
sent from the KNX bus to
the Smart Control controller
and used for the circuit's
room temperature influ-
ence. The selection param-
eter for the room control
must be set to KNX for this.
26
5/0/27
3rd mixed HC
room humidity
DPT 9.007
(DPT_Value_H
umidity)
0 % - 100 %
2 byte
C
-
W
-
The room temperature is
sent from the KNX bus to
the Smart Control controller
and used for the circuit's
room temperature influ-
ence. The selection param-
eter for the room control
must be set to KNX for this.
21