The physical address setting for the KNX inter-
face is required to find the correct interface in a
network with multiple KNX interfaces. This
parameter setting must therefore match the
physical address of the KNX interface. For
instructions on setting the physical address, see
the operating manual for the KNX interface that
is used.
Set the physical address for the Smart Control
Touch controller.
If the setting is 0.0.0, an address that is assigned
by the interface is adopted. This address may
change each time the connection is established
again.
Use the controller's operating unit to set the
physical address for the SMT controller (tun-
neling connection address). The parameter is
only displayed when activating programming
mode and the setting is only adopted once pro-
gramming mode is deactivated. The physical
address for the SMT controller must be located
topologically in line with the KNX interface, i.e. if
the KNX interface has address 1.1.1, the con-
troller must receive address 1.1.2 or 1.1.3, for
example.
KNXnet/IP
¯
IA for the controller
Activating the Smart Com connection
The Smart Com connection can be activated once
the configuration has been adjusted.
KNXnet/IP
¯
Smart Com
¯
Activated
Deactivated
After you activate the Smart Com function, communication objects such as those shown in the following
table are enabled to program the group address and communication flags.
Communication flags:
Parameter
Option / area
Factory setting
Customer setting
Smart Com
Activated / Deacti-
vated
Deactivated
Interface search
Unicast / multicast
Multicast
IP for the KNX interface
Enter the IP address
192.168.0.115
IA for the KNX interface
0.0.0 - 15.15.255
0.0.0
Multicast address
Enter the IP address
224.0.23.12
IA for the controller
0.0.0 - 15.15.255
0.0.0
Programming mode
Activated / Deacti-
vated
Deactivated
REMKO Smart Com
14