CO
1)
Grp.-
addr.
2)
Name
3)
DPT
4)
Size
5)
Communica-
tion flag
6)
Function description
5
5/0/6
Outside
temperature
DPT 9.001
(DPT_Value_Te
mp)
-273°C - 670
760°C
2 byte
C
R
-
T
The Smart Control con-
troller transfers the outside
temperature to the KNX
bus.
6
5/0/7
Room
target
temperature
DPT 9.001
(DPT_Value_Te
mp)
-273°C - 670
760°C
2 byte
C
R
W
T
The Smart Control con-
troller converts the "hotter/
colder" parameter setting
into a target value (e.g.
+2K corresponds to 22°C)
and sends this to the KNX
bus. This can be used by a
KNX room temperature
controller as the basic
target value.
7
5/0/8
Defrosting
(status)
DPT 1.001
(DPT_Switch)
(0) Off
(1) On
1 bit
C
R
-
T
The Smart Control con-
troller transfers the outdoor
unit's defrosting status to
the KNX bus (1 =
defrosting active).
8
5/0/9
HW target
temperature
DPT 9.001
(DPT_Value_Te
mp)
-273°C - 670
760°C
2 byte
C
-
W
-
The HW target temperature
is transferred from the KNX
bus to the Smart Control
controller.
9
5/0/10
HW actual
temperature
DPT 9.001
(DPT_Value_Te
mp)
-273°C - 670
760°C
2 byte
C
R
-
T
The Smart Control con-
troller transfers the HW
actual temperature to the
KNX bus.
10
5/0/11
One-off
hot water
DPT 1.017
(DPT_Trigger)
(0,1) Trigger
signal
1 bit
C
-
W
-
A trigger pulse activates/
deactivates the function
(regardless of the value
received)
11
5/0/12
Alarm signal
(Status)
DPT 1.005
(DPT_Alarm)
(0) No alarm
(1) Alarm
1 bit
C
R
-
T
The Smart Control con-
troller transfers a signal to
the KNX bus if there is a
malfunction.
12
5/0/13
Unmix. HC
actual temper.
DPT 9.001
(DPT_Value_Te
mp)
-273°C - 670
760°C
2 byte
C
R
-
T
The Smart Control con-
troller transfers the hot
water temperature
(average of the inlet tem-
perature and the return
temperature) to the KNX
bus.
19