![REMKO RVS 130 DC Скачать руководство пользователя страница 40](http://html.mh-extra.com/html/remko/rvs-130-dc/rvs-130-dc_operating-and-installation-instructions_1438872040.webp)
Malfunction Possible cause
Checks
Remedial measures
Major
F032
Fan motor 1 defective
Check:
- Fan motor operation
- Fan motor current draw
- Replace the fan motor.
X
E081
Communication fault between
motherboard and fan speed
controller
Check:
- Connections between
motherboard and fan speed
controller
- Replace fan speed controller
- Replace motherboard
Temperature
[°C]
Resistance
(k
Ω
)
-30
63.73
-29
60.32
-28
57.12
-27
57.12
-26
51.27
-25
48.60
-24
46.09
-23
43.72
-22
41.49
-21
39.38
-20
37.40
-19
35.53
-18
33.76
-17
32.09
-16
30.52
-15
29.03
-14
27.62
-13
26.29
-12
25.03
-11
23.84
-10
22.72
-9
21.65
-8
20.64
-7
19.68
-6
18.77
Resistance table
Temperature
[°C]
Resistance
(k
Ω
)
-5
17.91
-4
17.10
-3
16.32
-2
15.59
-1
14.89
0
14.23
1
13.60
2
13.01
3
12.44
4
11.90
5
11.39
6
10.90
7
10.44
8
10.00
9
9.58
10
9.18
11
8.80
12
8.44
13
8.09
14
7.76
15
7.45
16
7.15
17
6.87
18
6.59
19
6.33
Temperature
[°C]
Resistance
(k
Ω
)
20
6.09
21
5.85
22
5.62
23
5.40
24
5.20
25
5.00
26
4.81
27
4.63
28
4.46
29
4.29
30
4.13
31
3.98
32
3.83
33
3.70
34
3.56
35
3.43
36
3.31
37
3.19
38
3.08
39
2.97
40
2.97
41
2.77
42
2.67
43
2.58
44
2.49
The resistance values for the probes: AT (ambient), CT (register), SUT (suction gas), OT (medium outlet), IT
(medium inlet) are shown in the following table.
The ET (compressor outlet) probe is an NTC 50.
REMKO series RVS
40
Содержание RVS 130 DC
Страница 2: ......
Страница 41: ...Dimensions Unit dimensions RVS 50 DC RVS 80 DC RVS 130 DC RVS 180 DC 41 ...
Страница 43: ...43 ...