5 Minimum clearances
RVS 50 - 180 DC
Minimum clearances
Fig. 5
shows the minimum
clearances for trouble-free
operation of the units.
The protective zones serve to
provide unhindered air intake and
outlet, as well as providing sufficient
room for performing maintenance
and repairs and preventing the unit
from being damaged.
Condensate drainage connection
and secure discharge
Condensate drainage connection
If the temperature falls below
the dew point, condensation will
form on the finned condenser
during
heating mode
.
A condensate tray should be
installed on the underside of
the unit to drain any condensate.
■
The condensate drainage line
should have an incline of min.
2%. This is the responsibility
of the customer.
If necessary, fit vapour-
diffusion-proof insulation.
■
When operating the unit at
outdoor temperatures below
4 °C, care must be taken
that the condensate drainage
line is anti-freeze protected.
The lower part of the housing
and condensate tray is also
to be kept frost free in order
to ensure permanent draining
of the condensate.
If necessary, fit a pipe heater.
■
Following installation, check
that the condensate drain is
unobstructed and ensure that
the line is permanently leak
tight.
Safe drainage in the event
of leakages
Local regulations or environmental
laws, for example the German
Water Resource Act (WHG),
can require suitable precautions
to protect against uncontrolled
drainage in case of leakage
to provide for safe disposal
of escaping air conditioning fluid
or hazardous media.
+
+
+
+
+
+
Condensate drain
Condensate tray
Condensate drainage
Cumulative ice formation
in the lower part of the
finned heated exchanger can
develop under certain weather
conditions. To prevent this ice
formation, we recommend
keeping the heat exchanger
frost free on both sides using a
heating band for example.
NOTE
Failure to comply with
the minimum clearances
is considered a breach of
intended use. The manufacturer
assumes no liability for damage
or malfunctions arising from
this.
NOTE
500mm
1500mm
500mm
1000mm
REMKO series RVS