background image

8

REMKO PGM (E) series

s

s

s

Assembly note

During the assembly or 
disassembly of the gas hose, it is 
necessary to 

counter-hold

 the unit 

by the 

gas connection nipple

 

with an open-end wrench size 17, 
whilst observing the left-handed 
thread. 
This process also applies 
to the pressure controller, hose 
breakage protection and all further 
gas components.

Tighten gas hose:

Turn the union nut 

anticlockwise

Loosen gas hose:

Turn the union nut 

clockwise

Icing up of gas cylinders

With insufficiently dimensioned 
gas supply systems, there is a risk 
of the pressurised gas cylinder 
icing up. 
Due to the reduction of the gas 
pressure, it is no longer possible 
to guarantee the correct gas 
supply to the unit.

Crystalline 

frost formation 

on 

the gas cylinder(s) must not 
be defrosted with naked flames, 
glowing objects, radiators, etc.

In order to avoid the gas 
cylinder(s) icing up, it is necessary 
to configure the gas supply 
in accordance with the unit 
connection value, the time 
in operation and the ambient 
temperature of the supply tank. 

1

6

2

4

5

4

3

6

5

6

Attachment multi-cylinder set 

(accessory)

In order to ensure a regular gas take-off insofar as possible, 
all cylinder valves must be open.
The cylinder battery can be expanded with ease,  
through the use of additional sets.

Legend:

1 = Gas hose to the unit
2 = Hose breakage protection
3 = Gas pressure controller
4 = HP hose 0.4 m
5 = T-connection
6 = Cylinder valve

Connecting the gas supply

1.  Connect pressure 

controller 
to the gas 
cylinder or gas 
supply system.

 

Observe left-handed thread!

2.  Open cylinder 

valve(s) or shut-
off valve of the 
supply line. 
 
 

With simultaneous discharge 
from multiple gas cylinders, all 
valves must be opened.

3.  Push the unlock 

button on 
the hose breakage 
protection after 
opening 
the valve(s). 

This process is also necessary 
after every cylinder change.

4.  Check all gas connections for 

leak-tightness using suitable 
media. 
 

for example with:

Soap solution or 

leak detection 

spray.

counter

-hold

counter

-hold

NOTE

Because these are ball 
nipple screw connections 
in accordance with DIN 4815, 
part 2, only appropriate, 
fitting hoses may be used.

NOTE

Only hoses for liquid gas in 
accordance with DIN EN 16436-1, 
pressure class 30 may be used  
for construction site operations.

Содержание PGM 30

Страница 1: ...g and installation instruction This product is not suitable as a main heater Edition GB Q04 Read the instructions prior to performing any task PGM 30 E PGM 60 E REMKO PGM E series Propane gas heating...

Страница 2: ......

Страница 3: ...modifications no liability accepted for errors or misprints Safety notes 4 Unit description 5 Installation instructions 6 Gas connection 7 9 Commissioning 9 10 Shutdown 11 Care and maintenance 11 12 T...

Страница 4: ...prior to delivery However dangers can arise from the units if they are used improperly or not as intended by untrained personnel Please observe the following information The units may only be operate...

Страница 5: ...ust gas burners with thermal monitoring electric solenoid valve piezo ignition and mains cable with earthed safety plug The units are intended exclusively for manual operation and cannot be thermostat...

Страница 6: ...n well ventilated spaces and not in living areas or similar recreational areas Installation instructions The safety regulations of the accident prevention and insurance associations the respective reg...

Страница 7: ...nit connection pressure of 1 5 bar It is prohibited to exceed or undershoot the connection pressure When using longer hose lines consider the respective pressure loss Only use components that have bee...

Страница 8: ...supply tank 1 6 2 4 5 4 3 6 5 6 Attachment multi cylinder set accessory In order to ensure a regular gas take off insofar as possible all cylinder valves must be open The cylinder battery can be expa...

Страница 9: ...switch to the 0 off position 2 Connect the unit s power plug to a properly installed and fused mains socket Connect 230 V 50 Hz The units should be checked for visible defects on the operating and saf...

Страница 10: ...es 4 After a flame appears depress the pressure pin 2 for a further approx 10 15 sec until the thermal flame monitoring is activated 5 If the flame goes out when the pressure pin 2 is released repeat...

Страница 11: ...ve or solvent based cleaners Use only suitable cleaners even for heavy contamination Check the inlet and outlet grille for contamination on a regular basis Check hoses and seals for damage on a regula...

Страница 12: ...extremely sensitive capillary tube here 8 Carefully remove any adhered deposits from the ignition electrode and thermocouple 9 Detach the fastening screws of the gas burner and remove the complete gas...

Страница 13: ...niter Check the thermocouple or temperature limiter and replace if necessary Check the connection and clean if necessary Fit an original pressure controller Disengage or replace the hose breakage prot...

Страница 14: ...not intended for domestic use without heat exchangers with forced convection The units must only be operated by appropriately instructed personnel With non observance of the manufacturer s specificati...

Страница 15: ...15...

Страница 16: ...PGM 30 E 1 2 3 4 5 6 7 8 9 11 14 12 15 14 18 13 19 17 16 12 21 19 15 23 24 25 26 27 32 33 34 35 36 10 28 10 37 6 20 9 31 30 29 We reserve the right to modify the dimensions and design as part of the...

Страница 17: ...101396 24 Solenoid valve 1101376 25 Gas connection nipple 1101134 26 Adjusting knob cpl 1101192 27 Operating switch 1101188 28 Strain relief 1101267 29 Mains cable with plug 1101320 30 Completion pane...

Страница 18: ...60 E We reserve the right to modify the dimensions and design as part of the ongoing technical development process 8 7 9 10 12 18 15 14 13 16 17 19 8 20 21 16 22 23 28 11 24 22 26 27 29 30 32 31 35 36...

Страница 19: ...1101134 30 Adjusting knob cpl 1101192 31 Strain relief 1101267 32 Operating switch 1101188 33 Terminal block 6x 1101366 34 Grommet 1101304 35 Mains cable with plug 1101320 36 Protective intake grille...

Страница 20: ...9 Date Signature 20 Date Signature Comments Unit to be maintained only by authorised specialists in accordance with the statutory regulations Unit type Unit number 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15...

Страница 21: ...umption at nominal heating capacity elmax kW 0 070 0 100 at minimum heating capacity elmin kW 0 070 0 100 in Standw By mode elSB kW 0 000 0 000 Pilot flame power requirement Ppilot kW N A N A Thermal...

Страница 22: ...2 1 5 4 3 2 1 6 STB MV M 1 S C 1 A3 A2 A1 B4 B5 B6 PZ TMV TE Z Legend KL Terminal block M Fan motor MV Solenoid valve PZ Piezo igniter S Operating switch STB Safety temperature limiter TE Thermocoupl...

Страница 23: ...23...

Страница 24: ...5232 606 260 E mail info remko de URL www remko de REMKO GmbH Co KG Klima und W rmetechnik Im Seelenkamp 12 32791 Lage Hotline within Germany 49 0 5232 606 0 Hotline International 49 0 5232 606 130 W...

Отзывы: