6
Commissioning
Before commissioning the unit or if local require-
ments dictate, the air-inlet grill and air-outlet grill
must be checked for contamination.
NOTICE!
A contaminated grille or filter must be cleaned
or replaced immediately.
Important notes prior to commissioning
n
All extensions to the electrical connection must
be of a sufficient cable size and must only be
used fully rolled out or unrolled.
n
Never use the power supply connection cable
as a pull cord.
n
After being switched on, the units operate fully-
automatically until the desired humidity is
reached.
n
The condensate drainage line must be installed
properly.
n
In order to prevent damage to the condenser,
the units are equipped with a mechanism that
prevents the compressor being immediately
switched back on after it is switched off
The compressor only switches back on
after a waiting time of approx. 3 minutes!
NOTICE!
In room temperatures below
15 °C
and/or rela-
tive humidity below
40%
, economical use of the
unit can no longer be guaranteed.
Starting the unit
Start the unit as follows:
1.
Plug the unit's power plug into a properly
installed and fused mains socket (220-240
V/50 Hz).
If you connect the dehumidifier to the mains
for the first time, the unit should be switched
off (not operating). The system starts up for
approx. 30 seconds until the display shows
"0%" in the top right corner.
2.
Actuate the "ON / OFF" key.
The display switches on and shows the cur-
rent humidity and temperature in the room.
The desired humidity can be set using the
arrow keys. First, the fan is switched on and
ramps up linearly to the set speed. The com-
pressor starts after approx. 2 minutes and
also ramps up linearly to the target speed.
Automatic restart after power failure:
If the electrical power fails or if the power plug is
pulled out during operation, the unit switches off.
When the unit is switched back on again or if the
power plug is put back in again the unit starts up
again automatically.
WARNING!
To avoid damage to the compressor, the unit
must only be switched off from the unit display.
Disconnect from the mains only after the com-
pressor and fan have shut down and come to a
standstill. Control via external switching devices
(e.g. timers or network sockets) is also pro-
hibited.
Control and display panel:
1
2
3
8
7
5
9
10
6
4
Fig. 7: Control panel
15