8
REMKO ATK
Exhaust system
Example 1
operating with
extended
waste gas pipe
condensate trap
necessarily
Example 2
operating wi-
thout
extended
waste gas pipe
max. 1m
Example 3
Inadmissible
arrangement.
max. 1 m.
More than 1 m.
In order to prevent the combu-
stion chamber from becoming
damaged due to condensation of
moisture (condensate) in example
3, make sure that the exhaust gas
ducting is correctly installed with
a condensate trap as shown in
example 1.
■
Malfunction-free operation is
guaranteed if the exhaust
system is installed in an ascen
ding direction and with
vertical end pipes
■
The exhaust system must
terminate at least above the
height of the eaves but better
still above roof height in
order to avoid counter pressure
caused by weatherrelated
circumstances (e.g. wind)
■
The minimum distance of 0.6 m
to combustible parts must not
be exceeded
■
Exhaust-pipe parts including
attachment material are
available as accessories
In the outdoors or in open rooms,
the operation of the device is
also possible without an exhaust
system.
However, we recommend a 1 m
exhaust-pipe (see example 2) with
a rain hood placed on top so as to
rule out the penetration by rain-
water and dirt.
If the device is used for tempora-
ry room heating, the combustion
gases may have to be removed to
the exterior.
■
The exhaust-pipe parts must
be laid in such a way that a
minimum suction of 0.1 mbar is
guaranteed
■
It must be made sure in all
cases that counter pressure due
to an incorrect exhaust system
is ruled out
Notes for implementing the
1st. BImSchV
Units that are not expected to be
operated for longer than 3 months
in the same location are not sub-
ject to any approvals or monitoring
as per the 1st. BImSchV
■
All exhaust-pipe parts must be
attached reliably. Their diameter
must not be smaller than that
of the exhaust nozzle of the
device
■
The lateral openings in the
exhaust connection must not
be closed or covered
■
The exhaust pipe must not be
pushed beyond the stop
(swage)
HINWEIS
Counter pressure must not
arise under any circumstances
from the incorrect installation
of exhaust gas ducting.