background image

12

REMKO ATK

E

D

On account of the construction-
dependent design of the exhaust 
connection (connection nozzle 
with secondary air openings), it is 
not possible to perform a correct 
exhaust analysis in a conventional 
manner in the exhaust pipe behind 
the exhaust connection.

For the performance of the ex-
haust analysis the sensor of the 
exhaust-measurement device must 
be placed in the centre of the pipe 
socket of the heat exchanger.

The measurement sensor is placed 
through the appropriate lateral se-
condary air opening in the exhaust 
connection in the existing mea-
surement opening in the pipe
nozzle of the combustion chamber 
(see drawing below).

Notes for implementing the  
1st. BImSchV

Units that are not expected to be 
operated for longer than 3 months 
in the same location are not sub-
ject to any approvals or monitoring 
as per the 1st. BImSchV.

Exhaust Measurement

s

s

s

Exhaust connection

Legend:

1 = Exhaust connection 150 ø
2 = Pipe socket / Heat exchanger
3 = Auxiliary air opening
4 = Measurement Sensor

  If the main filter frequently    

  becomes dirty

  If condensation water 

  accumulates in the fuel

Please proceed in the following 
way when cleaning the
fuel tank:

1.  Unscrew the discharging  
  screw [D] and discharge the
  fuel into a suitable vessel.

2.  Rinse the container several    
  times if necessary with clean  
  fuel thoroughly.
 

Do not use water!

3.  Please use no cleaning agents  
  which contain solvents.  
 

These can destroy the inner   

  layer of the tank!

4.  Avoid the use of high-pressure  
  cleaners.

5.  Fit the discharging screw [D].  
 

The gasket ring [E] should be  

  replaced after each  
  disassembly!

6.  Fill tank with clean fuel.  
 

Do not use biodiesel!

7.  Start unit and let it run for  
  approx. 5 minutes.

Adjusting the air slide plate

The air slide plate is set at the  
factory. The air throughput may 
only be adjusted to local conditions 
by authorised personnel.

After the clamp screw [K] is a 
loosened, the air slide plate can be 
adjusted using the exhaust mea-
surement.

1

3

4

2

Cleaning the fuel tank

Burner head

Slide plate

K

ca. 3,5 mm

CO

value: approx. 11 - 12 %;

Soot number:

 0 - 1 lt. Bacharach

It is necessary to clean the fuel 
tank:

  After each heating period or,  

  depending on the deployment  
  conditions, even earlier

  Before and after extended idle  

  periods

Содержание ATK 25

Страница 1: ...REMKO ATK 25 Automatic oil heater with built in oil burner tank and exhaust gas connection Operation Technology Spare Parts Edition GB D05...

Страница 2: ......

Страница 3: ...4 Intended use 14 Electrical Wiring Diagram 14 Trouble Shooting 15 Exploded view 16 Spare Parts List 17 Maintenance log 18 Technical Data 19 Before commissioning use of the equipment these operating i...

Страница 4: ...s operation The unit must be set up and operated in such a way that people are not endangered by exhaust fumes and radiated heat and no fires can break out The unit may be set up and operated in rooms...

Страница 5: ...t the automatic tank heater is activated for tempe ratures below 10 C When the unit has been switched on or when heat is required auto matic function with room thermo stat the supply air fan starts Th...

Страница 6: ...is the case if e g 1 The room contents in m corre spond with at least 30 times the nominal heat output of all units operating in the room and a natural change of air is ensured through windows and doo...

Страница 7: ...air supply appropriate to the respective forced air burner capacity see name plate Outdoor mounting Due to the operation of the unit no dangers or unreasonable nuisances may arise The unit operator mu...

Страница 8: ...doors or in open rooms the operation of the device is also possible without an exhaust system However we recommend a 1 m exhaust pipe see example 2 with a rain hood placed on top so as to rule out the...

Страница 9: ...Make sure that combustion air is supplied Make sure that the air can be sucked in and be exhausted freely Avoid overpressure and underpressure in the room where the unit has been installed Make sure...

Страница 10: ...supply Maintenance and Service s s s 4 heating with room thermostat accessories The unit runs fully automatically with the temperature which has been pre selected on the room thermostat 1 Remove the...

Страница 11: ...d and the burner is to be adjusted Observe regular maintenance and care intervals Cleaning the burner Clean the components of the burner as described below s s s 1 Pull the photocell 1 from its mount...

Страница 12: ...he main filter frequently becomes dirty n If condensation water accumulates in the fuel Please proceed in the following way when cleaning the fuel tank 1 Unscrew the discharging screw D and discharge...

Страница 13: ...rried out by authorised qualified techni cians CAUTION An electrical safety check must be carried out in accordance with VDE 0701 after any work on the units CAUTION Never let the pump run without fee...

Страница 14: ...industrial or com mercial use no private living area heating The unit may be operated only by accordingly trained personnel The manufacturer is not liable for damage that occurs due to nonob servance...

Страница 15: ...ith clean fuel 10 Fuel filter is blocked dirty Clean fuel filter resp replace if necessary 11 Nozzle is blocked resp wrong dimension type size Replace nozzle take care of correct type and size 12 Wron...

Страница 16: ...nical progress 51 50 54 52 56 55 58 57 64 65 66 67 59 52 53 61 62 38 58 56 55 63 Siehe Abb AA 96 38 32 40 39 39 41 32 42 34 85 36 35 37 01 02 03 04 05 04 03 26 27 28 29 31 30 A B 32 34 34 33 97 08 98...

Страница 17: ...4 72 Relay socket 1102534 29 Fan housing 1103734 73 Automatic burner 1102239 30 Air baffle plate right 1103756 74 Locking screw PG plate 1102533 31 Air baffle plate left 1103757 75 O ring seal 1103783...

Страница 18: ...ate Signature 18 Date Signature 19 Date Signature 20 Date Signature Remarks Model Model No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Clean unit surface Clean unit interior Clean fan blade Cle...

Страница 19: ...x l h 2 45 Nozzle Danfoss 80 H USG 0 50 Pump pressure approx bar 11 to 12 Tank capacity Ltr 40 Electrical connection 1 V 230 Frequency Hz 50 Rated current max A 2 3 Power consumption max 1 kW 0 43 Fus...

Страница 20: ...and abroad but also unusually highly qualified sales experts REMKO sales representatives are more than just salespeople they must also be customer consultants in air conditioning and heating technolo...

Отзывы: