Troubleshooting  

– unit does not start. 

 

– fan motor is running but burner will not be ignited. 
 

 

– unit shut down without flaming formation. 

 

– unit stops during operation. 
    (fault indicator lamp of the automatic burner relay lights up)

 

 

– smoke forming at the blow-out cone. 

 

– unit can’t be switched off.. 

2 – 3 – 4 – 6 – 7 – 8 – 25 

 

1 – 5 – 9 – 10 – 11 – 12 – 13 – 14 – 15 – 16 – 17 
20 – 21 – 23 – 24 – 26  

 

20 

 

4 – 5 – 6 – 7 – 8 – 9 – 10 – 11 – 13 – 15 – 16 – 17 
19 – 21 – 22 – 23 – 24 – 26 

 

7 – 10 – 11 – 13 – 15 – 17 – 19 – 21 – 22 – 24 

 

18 – 25 

Cause: 

Trouble: 

Cause:

 

Remedy: 

  1.  Air (bubbles) in the fuel system during starting procedure. 

– Press fault clearance button of the automatic burner relay, 
    repeat if necessary (max. 3 x). 

  2.  No electrical connection. 

– Check mains, mains plug and current. 

  3.  No (bridge circuit-/thermostat-) plug in the thermostat socket. 

– Connect bridge circuit plug resp. thermostat plug with the thermostat 

socket. 

  4.  Thermostat setting is too low. 

– Set thermostat higher than the room temperature. 

  5.  Fault indicator lamp of the automatic burner relay lights up. 

– Unlock the automatic burner relay by pressing the reset button. 

  6.  Faults in the automatic burner relay. 

– Replace automatic burner relay. 

  7.  Fan motor is overcharged. 
       (Fan blows irregularly or is blocked) 

– Let motor cool down. 
– Check slight run of fuel pump. 
– Check motor on electrical and mechanical function. 

  8.  Fuel pump is blocked. 

– Check resp. replace fuel pump. 

  9.  Fuel tank is empty. 

– Fill fuel tank with clean fuel. 

10. Fuel filter is blocked (dirty). 

– Clean fuel filter resp. replace if necessary. 

11. Nozzle is blocked resp. wrong dimension (type/size). 

– Replace nozzle (take care of correct type and size!). 

12. Wrong setting of ignition electrodes or damaged insulation. 

– Adjust correctly resp. replace it. 

13. Air flow plate of the burner head is misadjusted resp. dirty. 

– Adjust correctly by means of CO

–indicator and soot pump 

    (CO

2

 : 10 – 13% and  soot figure by Bacharach: 0 – 1). 

14. Solenoid valve does not open. 

– Check solenoid valve resp. replace if necessary. 

(A „click“ should be heard during switching on/off)  

– The safety temperature limiter has released / is defective. 

15. Misadjusted pump pressure. 

– Set pump pressure by means of a pressure-gauge. 

16. Pump clutch is defective. 

– Replace pump clutch. 

17. Leakage in suction pipe or in fuel filter. 

– Check suction pipe and fuel filter, replace if necessary. 

18. Solenoid valve does not close. 

– Pull off the fuel pipe from the main filter - the flame dies. 

19. Air protecting grille is dirty. 

– Clean air protecting grille. 

20. Disconnection by the safety temperature limiter (STB). 

– Check air protecting grille, clean if necessary. 
– Unlock safety temperature limiter (STB-Reset). 

21. Air (bubbles) in the fuel system. 

– Restart the unit in order to discharge the air through the nozzle. 
    (This procedure can be repeated up to max. 3 times). 

22. No adequate ventilation. 

– Open doors or windows. 

23. Photo cell is dirty resp. defective. 

– Clean photo cell resp. replace if necessary. 

24. Improper exhaust system. 

– See chapter “Exhaust system“. 

25. Operating switch not functioning. 

– Check operating switch resp. replace if necessary.

 

– Clean the entire fuel system. 
 
– Replace the damage tank heating. 

26. Fuel with paraffin accumulation. 

(Already occur starting from 5 °C see notes in chapter "Starting"). 

       The tank heating is damage (very rarely). 

The mains plug has been taken out of the mains socket before carrying out any work regarding the unit. 

Setting and maintenance is to be carried out only by authorised experts!

 

G

 

G

 

Содержание AT 25

Страница 1: ...REMKO powerful like a bear Edition GB M04 Operation Technology Spare Parts REMKO AT 25 Automatic oil heater ...

Страница 2: ......

Страница 3: ...10 Wiring diagram 10 Troubleshooting 11 Exploded view 12 Spare part list 13 Maintenance log 14 Automatic oil heater REMKO AT 25 Make sure to read these instructions carefully before starting using the unit Our guarantee will become void when the unit supplied by us is used and installed for inadequate purposes or maintained incorrectly etc or if it is changed without our prior consent Subject to a...

Страница 4: ...rner with optical flame monitoring a low mainte nance axial ventilator a connection cable with plug a room thermostat socket and a fivefold filter system The unit complies with the basic safety and health re quirements of the relevant EU stipulations and is reli able and simple to operate The unit can be used e g in the following areas for drying new buildings for point heating of outdoor workplac...

Страница 5: ...nd doors or openings which are not lockable are present in the region of ceiling and floor for the air supply and for out going air and the size of these openings in m corresponds with at least 0 003 times the nominal heat output in kW of all units operating in the room 2 6 The unit must not be installed or operated in rooms and areas where the danger of fire or explosion ex ists 3 Room drying 3 1...

Страница 6: ...he units are generally to be operated in accordance with the safety rules the building code of the land con cerned and the fire protection code Avoid under or overpressure in the room where the unit is installed as this would result in combustion troubles Suction and blow out cross sections may not be re duced It is prohibited to connect conduits or hoses to the unit blow out opening Make sure tha...

Страница 7: ...It is not possible to get rid of paraffin discharge which is already present using the tank heating The requirement for this is the cleaning of the entire fuel system G The unit is to be installed only in well aerated rooms but not in living rooms or similar recreation rooms 1 Put operating switch 1 into 0 position OFF 2 Connect unit plug to a suitable mains socket 230V 1 50 Hz Connect the unit wi...

Страница 8: ...e a long service life and trouble free operation After each heating period or even earlier depending on the deployment conditions the entire unit including combustion chamber and burner head must be cleaned of soot sediments dust and dirt The oil filters must also be cleaned replaced at least once a year or depending on the degree of contamina tion of the fuel frequently G Setting and maintenance ...

Страница 9: ...ustment of air slide plate Fine adjustment of air slide plate by means of CO2 indi cator and soot pump CO2 value approx 10 13 Soot figure 0 1 by Bacharach 4 When maintenance has been carried out re assemble all parts carefully in reverse order 5 Pre set air flow plate air slide plate and the ignition electrode distance according to the approximate indi cations 4 2 3 4 8 air slide plate air flow pl...

Страница 10: ...re counter clockwise reduce the pressure The required pump pressure is determined according to the heating capacity please refer to unit type plate and to the nozzle size The pressure setting screw A is to be secured with the counter nut B after having set the pressure Fuel Pump The standard type of the pump runs in a system of 1 pipe The required fuel is sucked in through the suction line S For t...

Страница 11: ...f ignition electrodes or damaged insulation Adjust correctly resp replace it 13 Air flow plate of the burner head is misadjusted resp dirty Adjust correctly by means of CO2 indicator and soot pump CO2 10 13 and soot figure by Bacharach 0 1 14 Solenoid valve does not open Check solenoid valve resp replace if necessary A click should be heard during switching on off The safety temperature limiter ha...

Страница 12: ...12 Exploded View We reserve the right to make modifications in dimensions and construction in the interests of technical progress See fig A See fig B Fig A Fig B 74 ...

Страница 13: ...ition cable kit 1102159 40 ignition electrode 1102132 41 traction relief 1108325 No Description Ref No 42 thermostat socket 1101018 43 bridge circuit plug 1101019 44 protective socket big 1101615 45 capacitor 1102907 46 connection cable solenoid valve 1102825 47 hose connection fitting 1102109 48 fuel pump with solenoid valve 1103717 49 copper pipe 4 mm cpl 1102315 50 angle clutch 1 8 x 4 1102112 ...

Страница 14: ...ing screws Electric safety inspections Test run Maintenance Log Model Model No Setting and maintenance work is to be carried out only by authorised specialists Remarks 1 Date 2 Date 3 Date 4 Date 5 Date Signature Signature Signature Signature Signature 6 Date 7 Date 8 Date 9 Date 10 Date Signature Signature Signature Signature Signature 11 Date 12 Date 13 Date 14 Date 15 Date Signature Signature S...

Страница 15: ......

Страница 16: ...REMKO GmbH Co KG Klima und Wärmetechnik D 32791 Lage Im Seelenkamp 12 D 32777 Lage PO Box 1827 Phone 49 5232 606 0 Fax 49 5232 606260 ...

Отзывы: