45
Service
parameters:
(according
to Recom)
Description
Adjustment range
Factory
setting
System
boiler
Factory
setting
Combi
boiler
4/5
Flow temperature
set point during
forced part load
20 - 90
°
C
60
60
6/6-7
Fan speed at full load
(HTG)
D.N.C.
1000 - 6000 rpm
3900
3900
7/10-11
Fan speed at part load
(HTG and DHW)
D.N.C.
1000 - 6000 rpm
2300
2300
8/12
Modulation start point
F/R,
d
t °C
D.N.C.
5 - 30
°
C
25
25
b/13
Switch on differential
(DHW)
D.N.C.
1 - 20
°
C
5
1
c/8-9
Fan speed at full load
(DHW)
D.N.C.
1000 - 6000 rpm
5450
5450
G/14
Forced part load time
after start (HTG)
3 - 10 minutes
3
3
H/15
Fan speed at start
D.N.C.
1000 - 6000 rpm
2500
2500
J/17
DHW control mode
0 / 1
0
0
L/18
Pump setting in
heating mode
0 / 1
1 = high
0 = low
(manual adjustable)
1
1
L/18
Pump setting during cir-
culation
0 / 1
0
0
n/19
HTG cut in Dt (based on
return)
D.N.C.
0 - 20
3
3
o/20
Pre heat period
0 -10 hours
0
0
P/21
Boiler type
0: not used
1: Combi
2: System
2
1
U/38
Max. shut down time
during continuous
heat demand
0 -30: minutes
15
15
51/32
Hysteresis before ending
DHW
D.N.C.
1 - 30
°
C
8
8
11/16
Differention end
DHW-demand
D.N.C.
-5 - 15
°
C
0
0