Remeha Selecta
18
4.4.1 Flue terminal positions
The flue terminal positions for the Remeha Selecta are shown in
Fig. 09.
The minimum
distances to the terminal can be found
in
Table 02.
Fig. 09
Flue terminal positions
Dimensions Terminal
location
Minimum
distance
(in mm) to
terminal
(room sealed)
A
Directly below an opening, air brick,
opening window, etc.
300
B
Above an opening, air brick, opening window, etc.
300
C
Horizontally to an opening, air brick,
opening window, etc.
300
D
Below a gutter or sanitary pipe work
75
1)
E
Below the eaves
200
F
Below a balcony or carport roof
600
G
Above ground, roof or balcony level
300
H
From vertical drain/soil pipe work
75
1)
J
From an internal or extarnal corner
30
K
From a surface or boundary facing the terminal
600
2)
L
Vertically from a terminal on same wall
1500