Code
Display text
Description
Range
Submenu
Zone SysTReturn
PM
Current system return
temperature from power
manager of the zone
-327.68 °C - 327.67 °C
Zone manager
Request P to PM
Request from the producer to
the producer manager to take
action
Producer Generic
Producer<>Consumer
Prod. manager bridge
Actual power PM
Actual power sent from the
producer manager
0 % - 100 %
Producer Generic
Producer<>Consumer
Prod. manager bridge
Time update stat
RU
Time update status for devices
communicating via the RUbus
Time R to L/S-bus
AM024
Actual rel. Power
Actual relative power of the
appliance
0 % - 100 %
Gas fired appliance
AM036
Flue gas
temperature
Temperature of the exhaust gas
leaving the appliance
0 °C - 250 °C
Gas fired appliance
AM043
Pwr dwn reset
needed
A power down reset is needed
0 = No
1 = Yes
Gas fired appliance
AM101
Internal setpoint
Internal system flow
temperature setpoint
0 °C - 250 °C
Gas fired appliance
DM001
DHW tank temp
bottom
Domestic Hot Water tank
temperature (bottom sensor)
-25 °C - 150 °C
Tank DHW
DM005
DhwSolarTankTe
mp
Domestic Hot Water solar tank
temperature
-25 °C - 150 °C
Internal DHW
Tank DHW
DM008
DHW out temp
Temperature sensor for the tap
temperature leaving the
appliance
-25 °C - 150 °C
Internal DHW
GM025
STB status
High limit status (0 = open, 1 =
closed)
0 = Open
1 = Closed
2 = Off
Gas fired appliance
GM027
Flame Test Active Flame test 1=active, 0=inactive 0 = Inactive
1 = Active
Gas fired appliance
GM044
ControlledStopRe
ason
Possible reason for Controlled
Stop
0 = None
1 = CH Blocking
2 = DHW Blocking
3 = Wait for burner
4 = TFlow > absolute max
5 = TFlow > start temp.
6 = Theat exch. > Tstart
7 = Avg Tflow > Tstart
8 = TFlow > max setpoint
9 = T difference too big
10 = TFlow > stop temp.
11 = Anti cycle on off HD
Gas fired appliance
PM002
CH Setpoint
External winning Central
Heating setpoint
0 °C - 250 °C
Gas fired appliance
PM003
ChTflowAverage
Actual average flow
temperature
-25 °C - 150 °C
Gas fired appliance
Tab.52 Navigation for advanced installer level
Level
Menu path
Advanced installer
> Installation Setup > CU-GH08 > Submenu
> Parameters, counters, signals > Signals > Adv.
Signals
(1) See the column "Submenu" in the following table for the correct navigation. The signals are grouped in specific functionalities.
9 Settings
7717201 - v03 - 25062019
MID _HMI T-control - Gas 120 ACE
65