5.3
Electrical connections
5.3.1
Recommendations
Only qualified professionals may carry out electrical connections, always
with the power off.
Earth the appliance before making any electrical connections.
Power the appliance via a circuit that includes an omni-polar switch with
contact opening distance of 3 mm or more.
When making electrical connections to the mains, respect the polarities.
Danger
Position the various electrical cables in such a way that they never
touch the heating pipes.
Keep the various electrical cables far enough from the heating
pipes so that they cannot be damaged by the effect of the heat.
5.3.2
Electrical power supply
Power supply voltage
230 V AC/50 Hz
Caution
Please ensure the polarities shown on the terminals are followed,
i.e live (L), neutral (N) and earth (
)
5.3.3
Recommended cable cross section
Decide on the cable according to the following information:
Distance of the appliance from the power source.
Upstream protection.
Neutral operating conditions.
Tab.2
Specifications of the power cable and the power source
Cable cross section
3 x 1.5 mm²
Curve C (circuit breaker)
10 A
Differential
30 mA
5 Installation
7717201 - v03 - 25062019
MID _HMI T-control - Gas 120 ACE
21