19.
Potter Program #10
Double Interlock Programming Instructions
(Single Hazard, Cross Zoned, 3 Alarm Zones
(2 Detection & 1 Low Air), 1 Water
fl
ow Zone,
and 1 Supervisory Zone)
1. Apply power to the panel.
2. Slide the program switch down.
3. Press the FUNCTION button until the display reads “PASS-
WORD=000.”
4. To enter a password, press the SELECT button until the proper
number is displayed above the “^” symbol; then press the SET
button to move to the next digit. After entering the third number,
the display will change. (All panels are shipped with a “000”
password.)
5. Press the FUNCTION button until the display reads “PRO-
GRAM ##” (the second “#” character refers to the current pro-
gram number between “0” and “24”).
6. Press the SELECT button until the display reads “PROGRAM
#10.”
7. Press the SETbutton.
8. The panel is completely programmed except for the custom
banner and zone messages. Slide the program switch back
up.
INPUTS:
1 supervisory zone, 2 conventional detection zones, 1 waterflow zone, and 1 low air alarm zone.
OUTPUTS:
1 general alarm, 1 supervisory,1 waterflow, and 1 solenoid release circuit.
OPERATION: Activation of both conventional zones and the low air alarm zone at the same time will operate the
solenoid release circuit and the general alarm bell.
Activation of either conventional zone only will operate the general alarm output.
Activation of the waterflow zone will operate the waterflow bell output.
Activation of the low air alarm zone will operate the supervisory bell output. It will not operate the
alarm
relay.
When either Zone #1 or #2 is in alarm, Output #1 will operate.
When Zone #3 is in alarm, Output #2 will operate.
When Zone #4 is activated, Output #3 will operate. This will create a supervisory condition not an
alarm condition. The alarm relay will not operate, the supervisory relay will.
When Zones #1, #2 and #4 are activated at the same time, the solenoid release circuit will operate.
* The Butter
fl
y valve in the PrePaK assembly is connected to Supervisory 2 input of the Potter PFC-4410RC
Releasing/Control panel.
Refer to the “Installation, Operation and Instruction Manual” for the PFC-4410-RC Releasing
Control Panel for Additional Information.
POTTER PROGRAM #10
OUTPUTS
ZONES
*Supervisory 2
#1
Conventional
#2
Conventional
#3
Water
fl
ow
#4
Low Air Alarm
#1 ALARM
X
X
#2 WATERFLOW
X
#3 SUPERVISORY
X
X
#4 RELEASE
X
X
X
Содержание H PrePak
Страница 3: ...Figure1 InstallationDimension 3 ...
Страница 6: ...6 Figure3 WiringDiagram ...
Страница 10: ...Figure5 WiringDiagram 10 ...
Страница 11: ...11 Figure6 WiringDiagram ...
Страница 12: ...Figure7 WiringDiagram 12 ...
Страница 14: ...14 Figure8 WiringDiagram ...
Страница 16: ...16 Figure9 WiringDiagram ...
Страница 18: ...18 Figure10 WiringDiagram ...
Страница 20: ...Figure6 DoubleInterlockPreaction ComponentIdentification 20 ...
Страница 22: ...22 Figure12 WiringDiagram ...