15.
Potter Program #7
Single Interlock Programing Instructions (Single
Hazard - Cross-Zoned, 2 Alarm Zones, 1 Water
fl
ow
Zone and 2 Supervisory Zones)
1. Apply power to panel.
2. Slide the program switch down.
3. Press the FUNCTION button until the display reads “PASS-
WORD = 000.”
4. To enter a password, press the SELECT button until the proper
number is displayed above the “^” symbol; then press the SET
button to move to the next digit. After entering the third number
the display will change. (All panels are shipped with a “000”
password.)
5. Press the FUNCTION button until the display reads “PRO-
GRAM ##” (the second “#” character refers to the current pro-
gram number between “0” and “24”).
6. Press the SELECT button until the display reads “PROGRAM
#7.”
7. Press the SET button.
8. The panel is completely programmed except for the custom
banner and some zone messages. Slide the program switch
back up.
INPUT:
2 conventional zones (cross-zoned), 1 waterflow zone, 1 low air zone, 1 supervisory zone.
OUTPUT:
1 general alarm bell, 1 waterflow bell, 1 supervisory bell, 1 solenoid release circuit.
OPERATION: Activation of both conventional zones at the same time will operate the solenoid release circuit and
the general alarm bell.
Activation of either conventional zone will operate the general alarm bell.
Activation of the waterflow zone will operate the waterflow bell.
Activation of either the low air zone or the supervisory zone will operate the supervisory bell.
When either Zone #1 or #2 is in alarm, Output #1 (general alarm) will operate.
When Zones #1 and #2 are in alarm at the same time, Output #4 (solenoid release) and Output #1
(general alarm) will operate.
When Zone #3 is in alarm, Output #2 (waterflow bell) will operate.
When either Zone #4 or the supervisory zone is activated, Output #3 (supervisory bell) will operate.
* The Butter
fl
y valve in the PrePaK assembly is connected to Supervisory 2 input of the Potter PFC-4410RC
Releasing/Control panel.
Refer to the “Installation, Operation and Instruction Manual” for the PFC-4410-RC Releasing
Control Panel for Additional Information.
POTTER PROGRAM #7
OUTPUTS
ZONES
*Supervisory 2
#1
Conventional
#2
Conventional
#3
Water
fl
ow
#4
Low Air Supervisory
#1 ALARM
X
X
#2 WATERFLOW
X
#3 SUPERVISORY
X
X
#4 RELEASE
X
X
Содержание H PrePak
Страница 3: ...Figure1 InstallationDimension 3 ...
Страница 6: ...6 Figure3 WiringDiagram ...
Страница 10: ...Figure5 WiringDiagram 10 ...
Страница 11: ...11 Figure6 WiringDiagram ...
Страница 12: ...Figure7 WiringDiagram 12 ...
Страница 14: ...14 Figure8 WiringDiagram ...
Страница 16: ...16 Figure9 WiringDiagram ...
Страница 18: ...18 Figure10 WiringDiagram ...
Страница 20: ...Figure6 DoubleInterlockPreaction ComponentIdentification 20 ...
Страница 22: ...22 Figure12 WiringDiagram ...